Please also take into account any fitting that could restrict flow such as water meters, softeners etc.  

Connection to the unit – Use 22mm compression for all connections. Use gunmetal, DZR or brass fittings,
noting local water conditions.

COLD MAINS COMPONENT LAYOUT

No valve is to be fitted between the expansion valve and the cylinder, except a drain point.

It  is recommended that a stop cock is fitted to the above to facilitate servicing. Install before the
pressure reducing valve.  Always fit a drain tap in an appropriate position for drain down as low as
possible.

DON’T USE MONOBLOC MIXERS IF THE COLD SERVICE IS UNEQUALISED AS IT WILL BACK – PRESSURISE
THE UNIT AND RESULT IN DISCHARGE.

PRESSURE REDUCING

VALVE/FILTER

NON RETURN VALVE

PRESSURE GAUGE

EXPANSION VESSEL

(OPTIONAL)

DRAIN POINT

EXPANSION VALVE

COLD TAPS

COLD FEED

22mm

EXPANSION

VALVE

22mm

TUNDISH

15mm

15mm

PRESSURE AND

TEMPERATURE

RELIEF VALVE

2

DISCHARGE

Both the pressure and temperature
relief valve fitted to the unit and
the expansion valve supplied loose
must be arranged to comply with
G3 regulations and each discharge
into an open (visible) tundish.

A 300mm vertical drop of 22mm
diameter pipe must be fitted to the
tundish. 

NB: THE TUNDISH AND DRAIN
MUST BE POSITIONED AWAY FROM
ELECTRICAL DEVICES.

ALWAYS CONSULT THE REGULATIONS!
IMPORTANT: Discharge arrangements are the responsibility of the installer and reference to current
building regulations should always be made.  Applied Energy  Products Ltd. offers the foregoing as 
guidelines only.

The main purpose of discharge pipework is to allow full flow from relief valves to be accumulated and
safely routed to a point outside the building at low level.

New Stainless imp_alt  2/15/05  12:15 PM  Page 3

Содержание LWSS STAINLESS STEEL

Страница 1: ...R LWSS STAINLESS STEEL UNVENTED WATER STORAGE HEATER APPLIED ENERGY PRODUCTS LTD TEL 08709 000430 THIS UNIT IS SUPPLIED BY INSTALLATION COMMISSIONING MAINTENANCE...

Страница 2: ...re will result in a fall in flow rate A flow rate of 20 litres per minute is a minimum requirement for single bath applications and must rise proportionately for greater demands 1 PRESSURE AND TEMPERA...

Страница 3: ...RESSURE GAUGE EXPANSION VESSEL OPTIONAL DRAIN POINT EXPANSION VALVE COLD TAPS COLD FEED 22mm EXPANSION VALVE 22mm TUNDISH 15mm 15mm PRESSURE AND TEMPERATURE RELIEF VALVE 2 DISCHARGE Both the pressure...

Страница 4: ...ween 9m and 18m equivalent resistance length should be at least larger than the nominal outlet size of the safety device between 18m and 27m at least 3 sizes larger and so on Bends must taken into acc...

Страница 5: ...systems so that any installation can be traced reasonably easily The single common discharge pipe should be at least one pipe size larger than the largest individual discharge pipe to be connected If...

Страница 6: ...up to 9m up to 18m up to 27m up to 9m up to 18m up to 27m 22mm 28mm 35mm 28mm 35mm 42mm 35mm 42mm 54mm 15mm 22mm 28mm G1 2 G3 4 G1 0 8m 1 0m 1 4m 1 0m 1 4m 1 7m 1 4m 1 7m 2 3m GUIDANCE NOTES TYPICAL D...

Страница 7: ...y HOT WATER OUTLETS Dynamic pressure always drops across a system when more than one outlet is opened The unit has a working pressure of 3 bar Good system design should take this into consideration pi...

Страница 8: ...with a 3mm contact gap separation Appropriate wiring for the electrical load must be used The twin immersion heaters supplied with direct units can be switched to utilise low tariff electricity supply...

Страница 9: ...75 or CP15 Programmer L C 2 C 2 1 Power Supply E Junction Box N L G Y BR BL 2 4 1 ITD Dual Stat ITD Dual Stat The wiring diagram for Danfoss systems is given as guidance For modified Danfoss Randall Y...

Страница 10: ...rammers recommended are FP715 7 5 and 2 day programming and the CP15 5 2 and 24 hour programming S PLAN Zone Valve Htg Room Stat Zone Valve DHW HP22 1 2 2 8 9 10 7 6 5 4 3 2 1 1 2 3 2 3 3 2 2 1 RMT 23...

Страница 11: ...e FP715 7 5 and 2 day programming and the CP15 5 2 and 24 hour programming 8 9 10 7 6 5 4 3 2 1 2 1 2 3 3 3 2 2 1 L N E L N E Htg On Dhw On Dhw Off L L N 4 3 1 NOT USED N E Basic Boiler 2 Port Valve P...

Страница 12: ...he charge should be checked with an accurate pressure gauge and maintained at 3 0 bar If the reading is less than 3 0 bar to recharge the vessel ensure that the unit is decommissioned by turning off t...

Страница 13: ...RE SET TEMPERATURE HIGH LIMIT CUT OUT C TEMPERATURE AND PRESSURE RELIEF VALVE D EXPANSION RELIEF VALVE E PRESSURE REDUCING VALVE LINE STRAINER F EXPANSION VESSEL SUPPLIED LOOSE G NON RETURN VALVE H PR...

Страница 14: ...WITH MANUAL RE SET TEMPERATURE HIGH LIMIT CUT OUT C TEMPERATURE AND PRESSURE RELIEF VALVE D EXPANSION RELIEF VALVE E PRESSURE REDUCING VALVE LINE STRAINER F EXPANSION VESSEL SUPPLIED LOOSE G NON RETUR...

Страница 15: ...IMMERSION HIGH LIMIT THERMOSAT IMMERSION CONTROL THERMOSTAT EXPANSION VESSEL UP TO 170 LITRE MODELS EXPANSION VESSEL FOR 200 250 LITRE MODELS TUNDISH INSTALLATION GUIDE LABEL CYLINDER THERMOSTAT 2 PO...

Страница 16: ...priately approved competent personnel following relevant Code of Practice 5 Installation must be in an appropriate location and use is restricted to potable water Please note that the extended guarant...

Страница 17: ...H LIMIT CUT OUT IS ALL WIRING TO THE CONTROLS OK YES NO NO NO NO YES RE SET YES REPLACE THERMOSTAT RE WIRE IS CONTROL TEMPERATURE SET AT 55 o C 60o C YES NO RE SET SET PROGRAMME IS BOILER ON START YES...

Страница 18: ...G NO HOT WATER DIRECT IS POWER ON TO ELEMENTS IS CONTROL TEMPERATURE SET AT 55 o C 60o C START END YES HAS HIGH LIMIT TRIPPED YES NO NO NO YES CHECK WIRING LINKS CONTINUITY AND RE SET REPLACE ELEMENT...

Страница 19: ...URE ADEQUATE IS IN LINE STRAINER IN PRV DIRTY START END YES IS PRV FAULTY IS SYSTEM FREE FROM RESTRICTIONS BLOCKAGES NO YES YES NO YES NO NO WATER SERVICE CHECK BY SUPPLYCOMPANY REQUIRED CLEAN OR REPL...

Страница 20: ...o C IS EXPANSION VESSEL CHARGE CORRECT IS ERV TPRV DISCHARGING REPLACE ERV TPRV RESET TEMPERATURE END CLEAN OR REPLACE AS REQUIRED RECOMMISSION EXPANSION LEVEL RE CALIBRATE PRV IS VALVE SEAL AND SEAT...

Страница 21: ...CE 2 DATE ENGINEER NAME COMPANY NAME TEL No ID SERIAL No COMMENTS SIGNATURE SERVICE 3 DATE ENGINEER NAME COMPANY NAME TEL No ID SERIAL No COMMENTS SIGNATURE SERVICE 4 DATE ENGINEER NAME COMPANY NAME T...

Страница 22: ...PRESSURE BAR HAS STRAINER IF FITTED BEEN CLEANED OF INSTALLATION DEBRIS YES NO HAS A WATER TREATMENT DEVICE BEEN FITTED YES NO IF YES TO ABOVE THEN WHAT TYPE ALL MAINS PRESSURE SYSTEMS ARE T P AND EX...

Страница 23: ...etc CUSTOMER DETAILS NAME ADDRESS TEL No INSTALLER DETAILS NAME DATE ADDRESS TEL NO REGISTRATION DETAILS Where applicable for unvented systems etc REG No ID SERIAL No etc COMMISSIONING ENGINEER DETAI...

Страница 24: ...ustomer APPLIANCE DETAILS COMMISSIONING RECORDS SERVICE INTERVAL RECORD IMPORTANT FAILURE TO INSTALL COMMISSION THIS APPLIANCE TO THE MANUFACTURER S INSTRUCTIONS MAY INVALIDATE THE WARRANTY This note...

Отзывы: