SmokeSight SS10MAMA V0.5 

Page 11 

 

 

itself from the network.  All alarms will remain in ‘Radio Interlink Configuration Mode’ as indicated by  
3beep every 10secs. 

2.

 

All smoke alarms will be placed into ‘Operation Mode’ 1hr after the last tap of the Test+Hush button or by 4Tap 
of the Test+Hush button.  On any network alarm confirm that the built node count reported in ‘Operation Mode’ 
agrees with your expected node count. 

Auto Test 

The Auto Test function provides scheduled, automatic testing of the smoke alarm.  Testing consists of momentarily 
simulating smoke internal to the smoke alarm which activates the smoke alarm’s siren.  The option card listens for 
the correct smoke alarm tone and reports an option card alarm if the test failed.  The test establishes, on a regular 
basis, that the smoke alarm’s smoke sensor, controller and siren are functional.  Test duration is 5secs and can be 
configured to be performed at a convenient time.  The Auto Test establishes that only the local smoke alarm, on 
which the test is performed, is functional.  While interlinked alarms may also sound, Auto Test does not confirm 
operation of interlinked smoke alarms.  Access to Auto Test, Configuration Mode is only possible if the Auto Test 
switch is switched to ON. 

Setup 

1.

 

Switch on/Confirm that the Auto Test switch is set to ON.  Refer to Configuration Switches for details.  The 
factory default, test settings are every two weeks from the day and time that the option card is first supplied 
with power.  Continue with the following steps only if you wish to change Auto Test times. 

2.

 

Select ‘Auto Test Configuration Mode’ - From Operation Mode this can be achieved by 4Tap, 2Tap of the 
Test+Hush button. Confirmation of this mode is reported by 4beep. 

3.

 

If you wish to alter the test ‘Frequency’ 1Tap, followed by 1Tap for every week, 2Tap for every two weeks, 3Tap 
for every four weeks.   

4.

 

If you wish to alter the test day ‘Days from Now’ 2Tap, followed by 1Tap for tomorrow, 2Tap for two days time 
up to 7Tap for the current day ie 0 days from now.  

5.

 

If you wish to alter the test hour ‘Hours from Now’ 3Tap, followed by 1Tap for 1 hour from now, 2Tap for two 
hours from now up to 24Tap for the current hour ie 0 hours from now. 

6.

 

The smoke alarm will be placed into ‘Operation Mode’ 2mins after the last tap of the Test+Hush button or by 
4Tap of the Test+Hush button.  Confirm that the Auto Test Time from Now reported in ‘Operation Mode’ agrees 
with your expected test time. 

 

Example 
Now: 

 

 

8am, Tuesday 

Desired Auto Test Time: 

12 Noon, Friday, Fortnightly 

Configuration: 

 

Frequency = 2Tap (Fortnightly) 
Days from Now = 3Tap (Tuesday to Friday = 3 days) 
Hours from Now = 4Tap (8am to 12 Noon = 4 hours) 

Confirmation: 

 

3 beep/flash, 4 beep/flash (3 days from today, 4 hours from now) 

Clap Silence 

If the smoke alarm is in alarm state, two loud hand claps in quick succession immediately below the alarm is 
equivalent to pressing the Test+Hush button on that alarm.  An alarm in alarm state is evidenced by its red LED 
flashing rapidly.  As clap volume and timing may vary, you may need to repeat clap silence more than once.  The 
alarm must incorporate an option card for clap silence to function. 

Содержание SmokeSight SS10MAMA

Страница 1: ...tages may be present at wires connected to this product Before working on this product isolate the electrical supply Ensure that the product has been correctly installed and tested for safe operation...

Страница 2: ...The smoke alarm contains NO radioactive material Environment Altitude 0m to 2 000m Temperature 0 C to 40 C Humidity 5 to 95 Audible Indication Alarm 85dBA at 3m ISO 8201 Battery Low Chirp Visual Indic...

Страница 3: ...r the ceiling Alarm Locations to Avoid Within 1 metre of air conditioner ducts ceiling fans and other high air flow areas Smoke may be blown away or diffused in these areas In areas where the temperat...

Страница 4: ...ncorporates radio interlinking functionality As such it can operate as a gateway device to connect wired and wireless interlinked alarms Refer to Installation for the interlink connection arrangement...

Страница 5: ...e mounting base unless the smoke alarm batteries are installed as damage may result Ready to slide Engages with a click Slide 11 Turn on the mains power and check that the green red and white LEDs fun...

Страница 6: ...iguration command success is reported by one long flash beep while command failure is reported by two long flashes beeps The current configuration mode menu is reported every 10secs if no command is r...

Страница 7: ...eeps 0 Add Radio Node Build Radio Network Mode Active 5flash 5beep every 10sec 4 Return to Operation Mode Auto Test Configuration Mode Command Taps Description Response White LED Flashes Beeps 0 Radio...

Страница 8: ...Interlink Loss Master or Network Lost After 10mins 4 White LED Flashes Beeps Auto Test Fail Replace the smoke alarm Alternatively press the Test Hush button and if the smoke alarm sounds disable Auto...

Страница 9: ...s on each smoke alarm eg the smoke alarms are mounted on a high ceiling Return to Factory Defaults would allow the Initial Setup procedure to be repeated It is assumed that the Radio Interlink switch...

Страница 10: ...d the network as a slave 4 Once all alarms have been configured they will all be placed into Operation Mode 2mins after the last alarm has joined the network as a slave or by 4Tap of any node s Test H...

Страница 11: ...plied with power Continue with the following steps only if you wish to change Auto Test times 2 Select Auto Test Configuration Mode From Operation Mode this can be achieved by 4Tap 2Tap of the Test Hu...

Страница 12: ...LED is illuminated when the mains power is applied When the Alarm Sounds 1 Alert small children in the home 2 Leave immediately by your plan of escape Don t waste time getting dressed or picking up va...

Страница 13: ...during this period from a smoke or fire event the unit will go into alarm mode Before using the alarm HUSH feature identify the source of smoke and be certain that a safe condition exists Replacing th...

Страница 14: ...operation While the Test Hush button is pressed the alarm does not sound The smoke alarm may not be operating correctly Check that the green LED is ON and the red LED flashes once every 5mins If probl...

Страница 15: ...has accumulated ALWAYS TEST THE SMOKE ALARM AFTER CLEANING If the smoke alarm is defective in any way do not tamper with the smoke alarm The smoke alarm does not contain any user serviceable parts As...

Страница 16: ...SmokeSight SS10MAMA V0 5 Page 16 This page is intentionally left blank...

Отзывы: