SmokeSight SS10MAMA V0.5 

Page 7 

 

 

Configuration Mode 

Command 

(Taps) 

Description 

Response 

(White LED Flashes, Beeps) 

Configuration Mode Active 

 2beep every 10sec 

Radio Interlink, Configuration Mode – Requires Radio Interlink Switch 
= ON 

Auto Test, Configuration Mode - Requires Auto Test Switch = ON 

Spare 

Return to Operation Mode 

5,5 

Return to Factory Defaults  

Radio Interlink Configuration Mode 

Command 

(Taps) 

Description 

Response 

(White LED Flashes, Beeps) 

Radio Interlink, Configuration Mode Active 

 3beep every 10sec 

Add Radio Node / Build Radio Network Mode 

2,2 

Remove Slave Radio Node (not for removal of this node) 

3,3 

Delete Radio Network 

Return to Operation Mode 

Add Radio Node / Build Radio Network Mode 

Command 

(Taps) 

Description 

Response 

(White LED Flashes, Beeps) 

Add Radio Node / Build Radio Network Mode Active 

 5beep every 10sec 

Return to Operation Mode 

Auto Test Configuration Mode 

Command 

(Taps) 

Description 

Response 

(White LED Flashes, Beeps) 

Radio Interlink, Configuration Mode Active 

 4beep every 10sec 

Weekly Frequency – Following 1 long flash beep, Tap 1,2,3 

Days from Today – Following 1 long flash beep, Tap 1 to 7 

Hours from Now – Following 1 long flash beep, Tap 1 to 24 

Return to Operation Mode 

Enable Switches 

Some functions require activation using enable 
switches accessible through the base of the smoke 
alarm.  Following activation of each function using the 
enable switches, configuration of the function is 
performed using the Test+Hush button and white LED 
to navigate the applicable configuration mode.  
Changing of any switch will require removing power to 
the option card for 1min before repowering.  

 

Switch Assignment 

Switch  Function 

Radio 
Interlink 

Auto Test 

Spare 

Spare 

 

Enable Switches 

Содержание SmokeSight SS10MAMA

Страница 1: ...tages may be present at wires connected to this product Before working on this product isolate the electrical supply Ensure that the product has been correctly installed and tested for safe operation...

Страница 2: ...The smoke alarm contains NO radioactive material Environment Altitude 0m to 2 000m Temperature 0 C to 40 C Humidity 5 to 95 Audible Indication Alarm 85dBA at 3m ISO 8201 Battery Low Chirp Visual Indic...

Страница 3: ...r the ceiling Alarm Locations to Avoid Within 1 metre of air conditioner ducts ceiling fans and other high air flow areas Smoke may be blown away or diffused in these areas In areas where the temperat...

Страница 4: ...ncorporates radio interlinking functionality As such it can operate as a gateway device to connect wired and wireless interlinked alarms Refer to Installation for the interlink connection arrangement...

Страница 5: ...e mounting base unless the smoke alarm batteries are installed as damage may result Ready to slide Engages with a click Slide 11 Turn on the mains power and check that the green red and white LEDs fun...

Страница 6: ...iguration command success is reported by one long flash beep while command failure is reported by two long flashes beeps The current configuration mode menu is reported every 10secs if no command is r...

Страница 7: ...eeps 0 Add Radio Node Build Radio Network Mode Active 5flash 5beep every 10sec 4 Return to Operation Mode Auto Test Configuration Mode Command Taps Description Response White LED Flashes Beeps 0 Radio...

Страница 8: ...Interlink Loss Master or Network Lost After 10mins 4 White LED Flashes Beeps Auto Test Fail Replace the smoke alarm Alternatively press the Test Hush button and if the smoke alarm sounds disable Auto...

Страница 9: ...s on each smoke alarm eg the smoke alarms are mounted on a high ceiling Return to Factory Defaults would allow the Initial Setup procedure to be repeated It is assumed that the Radio Interlink switch...

Страница 10: ...d the network as a slave 4 Once all alarms have been configured they will all be placed into Operation Mode 2mins after the last alarm has joined the network as a slave or by 4Tap of any node s Test H...

Страница 11: ...plied with power Continue with the following steps only if you wish to change Auto Test times 2 Select Auto Test Configuration Mode From Operation Mode this can be achieved by 4Tap 2Tap of the Test Hu...

Страница 12: ...LED is illuminated when the mains power is applied When the Alarm Sounds 1 Alert small children in the home 2 Leave immediately by your plan of escape Don t waste time getting dressed or picking up va...

Страница 13: ...during this period from a smoke or fire event the unit will go into alarm mode Before using the alarm HUSH feature identify the source of smoke and be certain that a safe condition exists Replacing th...

Страница 14: ...operation While the Test Hush button is pressed the alarm does not sound The smoke alarm may not be operating correctly Check that the green LED is ON and the red LED flashes once every 5mins If probl...

Страница 15: ...has accumulated ALWAYS TEST THE SMOKE ALARM AFTER CLEANING If the smoke alarm is defective in any way do not tamper with the smoke alarm The smoke alarm does not contain any user serviceable parts As...

Страница 16: ...SmokeSight SS10MAMA V0 5 Page 16 This page is intentionally left blank...

Отзывы: