This parameter sets the amount of digital filtering applied to the input signal.

If the temperature display is difficult to read due to small variations or noise,
increased  levels  of  filtering  will  help  to  stabilize  the  display.  Although  the
digital  filter  features  a  “moving  window”  to  help  minimize  response  time,
higher levels of filtering will result in slightly longer response times.

Set the desired level of input filtering by pressing the up or down arrow keys.

Press the 

PAR

key to save the selection and advance to the next parameter.

- normal filtering

- maximum filtering

 

 

DECIMAL POINT POSITION

TEMPERATURE DISPLAY OFFSET

 

DIGITAL FILTERING

THERMOCOUPLE TYPE

6

TEMPERATURE SCALE

 

 

 

to 

- no digital filtering

- increased filtering

SELECTION

TC TYPE

TC TYPE

SELECTION

mV indicator

N

B

tc-j

tc-t

Select the thermocouple type by pressing the arrow keys (

L

or 

M

) to sequence

through the selection list. When the desired selection is displayed, press the 

PAR

key  to  save  the  selection  and  advance  to  the  next  parameter.  Refer  to  the
thermocouple range and accuracy specification for additional TC information.

Select the desired temperature scale by pressing the up or down arrow keys.

This  setting  does  not  change  the  Custom  Units  Overlay  display  (if  installed).
Press the 

PAR

key to save the selection and advance to the next parameter.

Select  the  decimal  point  position  by  pressing  the  up  or  down  arrow  keys.

This  sets  the  display  resolution  to  1  or  0.1  degree.  This  parameter  is  not
available  for  thermocouple  types  R,  S  and  B,  where  the  display  resolution  is
always 1 degree. When mV indicator mode is selected for thermocouple type,
the display resolution is fixed at 0.01 mV (10 

µ

V). 

Press the 

PAR

key to save the selection and advance to the next parameter.

The temperature display can be corrected with an offset value. This can be used

to compensate for probe errors or errors due to variances in probe placement, or
to  adjust  the  readout  to  a  reference  thermometer.  Set  the  desired  display  offset
value by pressing (and/or holding) the up or down arrow keys. When the desired
offset value is displayed, press the 

PAR

key to save the selection and advance to

the next parameter. The display resolution for the offset value is the same as the
decimal  point  position  programmed  above.  The  display  offset  is  not  available
when mV indicator mode is selected for thermocouple type.

When the Input display is above the present HI value or below the present

LO value for the entered delay time, the meter will capture the Input display as
the new HI or LO reading. A delay time helps to avoid false captures of sudden
short spikes or Input display variations that may occur during start-up. 

Set the desired capture delay time by pressing the up or down arrow keys.

Press the 

PAR

key to save the selection and advance to the next parameter.

PEAK (HI)/ VALLEY (LO) CAPTURE DELAY TIME

 

seconds

4.0 P

ROGRAMMING THE

M

ETER

PROGRAMMING SEQUENCE

The Thermocouple Meter has up to seven programmable parameters that are

entered  in  the  sequence  shown  above,  using  the  front  panel  push  buttons.
Depending  on  the  thermocouple  type  selected,  some  parameters  are  not
applicable and are bypassed in the sequence.

The  last  programming  step  offers  the  choice  of  entering  calibration  mode.

From  this  mode,  the  user  can  restore  the  meter  to  factory  default  settings,  or
recalibrate  the  signal  input  and  cold  junction  temperature  if  necessary.  To
prevent  inadvertent  entries,  an  access  code  must  be  keyed-in  to  perform  any
operations in calibration mode.

Note: Programming mode can be locked out using the Program Disable input

terminal. With the PGM.DIS. terminal connected to COMM, the meter displays

” when the 

PAR

key is pressed, and will not enter programming mode.

PROGRAMMING MODE ENTRY

Press the 

PAR

key to enter Programming Mode. The meter briefly displays

 

followed by the first programming parameter described below.

PROGRAMMING MODE TIMEOUT

The  Programming  Mode  has  an  automatic  time  out  feature.  If  no  keypad

activity is detected for approximately 60 seconds, the meter automatically exits
Programming Mode. The meter briefly displays 

and returns to the normal

display mode. When automatic timeout occurs, any changes that were made to
the parameter currently being programmed will not be saved.

PROGRAMMING PARAMETERS

In Programming Mode, the display alternates between the parameter and the

current  selection  or  value  for  that  parameter.  The  dual  display  with  arrows  is
used below to illustrate the alternating display. The selection choices or value
range for each parameter is shown to the right of the alternating display.

Содержание PAXLTC

Страница 1: ...the stability of the reading All set up data is stored in EEPROM which will hold data for a minimum of 10 years without power The meter has several built in diagnostic functions to alert operators of...

Страница 2: ...ns and Display 5 Programming the Meter 6 Calibrating the Meter 7 Troubleshooting 8 TABLE OF CONTENTS PAXL 0 0 TC Thermocouple Temperature Meter TC Accessories Part Numbers MODEL NO DESCRIPTION PART NU...

Страница 3: ...rds Type 4X Enclosure rating Face only UL50 IECEE CB Scheme Test Certificate UL 7470A UL CB Scheme Test Report 03ME09282 08292003 Issued by Underwriters Laboratories Inc IEC 1010 1 EN 61010 1 Safety r...

Страница 4: ...ING TC SENSOR Remove power and connect the negative thermocouple lead always red to TC Terminal 6 and the positive lead to TC Terminal 5 Be certain that connections are clean and tight If the thermoco...

Страница 5: ...Install them on Signal and Control cables as close to the unit as possible Loop the cable through the core several times or use multiple cores on each cable for additional protection Install line fil...

Страница 6: ...ution for the offset value is the same as the decimal point position programmed above The display offset is not available when mV indicator mode is selected for thermocouple type When the Input displa...

Страница 7: ...ype and verifying unit accuracy at various points over the range of the meter 10 to 80 mV 7 The factory settings for the programming parameters are shown in the previous section in the alternating dis...

Страница 8: ...wiring 1b Verify power IN DISPLAY 1 Program data error 1 Press PAR and check data set ups or IN DISPLAY 1 Input display out of range 2 Loss of data set ups DISPLAY WANDERS 1 Loss of data set ups JITTE...

Отзывы: