EMC INSTALLATION GUIDELINES

Although this meter is designed with a high degree of immunity to Electro-

Magnetic  Interference  (EMI),  proper  installation  and  wiring  methods  must  be
followed to ensure compatibility in each application. The type of the electrical
noise,  source  or  coupling  method  into  the  meter  may  be  different  for  various
installations.  The  meter  becomes  more  immune  to  EMI  with  fewer  I/O
connections.  Cable  length,  routing,  and  shield  termination  are  very  important
and can mean the difference between a successful or troublesome installation.
Listed  below  are  some  EMC  guidelines  for  successful  installation  in  an
industrial environment.
1.  The  meter  should  be  mounted  in  a  metal  enclosure,  which  is  properly

connected to protective earth.

2. Use shielded (screened) cables for all Signal and Control inputs. The shield

(screen)  pigtail  connection  should  be  made  as  short  as  possible.  The
connection  point  for  the  shield  depends  somewhat  upon  the  application.
Listed below are the recommended methods of connecting the shield, in order
of their effectiveness.
a.  Connect  the  shield  only  at  the  panel  where  the  unit  is  mounted  to  earth

ground (protective earth).

b. Connect the shield to earth ground at both ends of the cable, usually when

the noise source frequency is above 1 MHz.

c. Connect the shield to common of the meter and leave the other end of the

shield unconnected and insulated from earth ground.

3. Never run Signal or Control cables in the same conduit or raceway with AC

power  lines,  conductors  feeding  motors,  solenoids,  SCR  controls,  and
heaters,  etc.  The  cables  should  be  run  in  metal  conduit  that  is  properly 

grounded. This is especially useful in applications where cable runs are long
and portable two-way radios are used in close proximity or if the installation
is near a commercial radio transmitter.

4. Signal or Control cables within an enclosure should be routed as far as possible

from contactors, control relays, transformers, and other noisy components.

5.  In  extremely  high  EMI  environments,  the  use  of  external  EMI  suppression

devices, such as ferrite suppression cores, is effective. Install them on Signal
and Control cables as close to the unit as possible. Loop the cable through the
core several times or use multiple cores on each cable for additional protection.
Install line filters on the power input cable to the unit to suppress power line
interference.  Install  them  near  the  power  entry  point  of  the  enclosure.  The
following EMI suppression devices (or equivalent) are recommended:

Ferrite Suppression Cores for signal and control cables:

Fair-Rite # 0443167251 (RLC# FCOR0000)
TDK # ZCAT3035-1330A
Steward # 28B2029-0A0

Line Filters for input power cables:

Schaffner # FN610-1/07 (RLC# LFIL0000)
Schaffner # FN670-1.8/07
Corcom # 1 VR3

Note: Reference manufacturer’s instructions when installing a line filter.

6. Long cable runs are more susceptible to EMI pickup than short cable runs.

Therefore, keep cable runs as short as possible.

3.0 R

EVIEWING THE

F

RONT

B

UTTONS AND

D

ISPLAY

Display Valley (LO) Reading

Display Peak (HI) Reading

PAR

PROGRAMMING MODE OPERATION

DISPLAY MODE OPERATION

KEY

Store selected parameter and index to next parameter

Increment value or change selection

Decrement value or change selection

Access Programming Mode or Display Input Reading

PEAK/VALLEY DETECTION

The meter will automatically record the highest input reading (peak) and the

lowest input reading (valley) for later recall. These values are stored at power-
down to allow monitoring the process limits over any length of time (shifts, days,
etc.). A selectable capture delay time is used to prevent detection of false peak or
valley readings caused by sudden short spikes or unusual process events. 

The peak and valley readings can be viewed and reset using the front panel

keys as described below.

View Peak, Valley and Input readings:

To view Peak, press 

. Meter displays 

followed by the Peak reading.

To view Valley, press 

. Meter displays 

followed by the Valley reading.

To  view  Input,  press 

PAR

.  Meter  displays 

 

followed  by  the  current

Input reading.

Note: The decimal point to the right of digit 1 flashes while the peak or valley

reading is displayed.

Reset Peak and/or Valley to the current Input reading:

To reset Peak and Valley, press 

and 

simultaneously. 

To reset Peak only, press and hold 

then press 

PAR

To reset Valley only, press and hold 

then press 

PAR

In each case, the meter displays 

followed by the current Input reading.

Содержание PAXLTC

Страница 1: ...the stability of the reading All set up data is stored in EEPROM which will hold data for a minimum of 10 years without power The meter has several built in diagnostic functions to alert operators of...

Страница 2: ...ns and Display 5 Programming the Meter 6 Calibrating the Meter 7 Troubleshooting 8 TABLE OF CONTENTS PAXL 0 0 TC Thermocouple Temperature Meter TC Accessories Part Numbers MODEL NO DESCRIPTION PART NU...

Страница 3: ...rds Type 4X Enclosure rating Face only UL50 IECEE CB Scheme Test Certificate UL 7470A UL CB Scheme Test Report 03ME09282 08292003 Issued by Underwriters Laboratories Inc IEC 1010 1 EN 61010 1 Safety r...

Страница 4: ...ING TC SENSOR Remove power and connect the negative thermocouple lead always red to TC Terminal 6 and the positive lead to TC Terminal 5 Be certain that connections are clean and tight If the thermoco...

Страница 5: ...Install them on Signal and Control cables as close to the unit as possible Loop the cable through the core several times or use multiple cores on each cable for additional protection Install line fil...

Страница 6: ...ution for the offset value is the same as the decimal point position programmed above The display offset is not available when mV indicator mode is selected for thermocouple type When the Input displa...

Страница 7: ...ype and verifying unit accuracy at various points over the range of the meter 10 to 80 mV 7 The factory settings for the programming parameters are shown in the previous section in the alternating dis...

Страница 8: ...wiring 1b Verify power IN DISPLAY 1 Program data error 1 Press PAR and check data set ups or IN DISPLAY 1 Input display out of range 2 Loss of data set ups DISPLAY WANDERS 1 Loss of data set ups JITTE...

Отзывы: