Installation 

The PAX meets NEMA 4X/IP65 requirements when properly installed. The

unit is intended to be mounted into an enclosed panel. Prepare the panel cutout
to the dimensions shown. Remove the panel latch from the unit. Slide the panel

gasket over the rear of the unit to the back

of the bezel. The unit should be installed

fully  assembled.  Insert  the  unit  into

the panel cutout. 

While holding the unit in place, push the panel latch over the rear of the unit

so that the tabs of the panel latch engage in the slots on the case. The panel latch
should be engaged in the farthest forward slot possible. To achieve a proper seal,
tighten  the  latch  screws  evenly  until  the  unit  is  snug  in  the  panel  (Torque  to
approximately 7 in-lbs [79N-cm]). Do not over-tighten the screws.

Installation Environment

The unit should be installed in a location that does not exceed the maximum

operating  temperature  and  provides  good  air  circulation.  Placing  the  unit  near
devices that generate excessive heat should be avoided.

The bezel should be cleaned only with a soft cloth and neutral soap product.

Do NOT use solvents. Continuous exposure to direct sunlight may accelerate the
aging process of the bezel.

Do not use tools of any kind (screwdrivers, pens, pencils, etc.) to operate the

keypad of the unit.

PANEL CUT-OUT

POWER WIRING

Primary AC power is connected to Terminals 1 and 2. To reduce the chance of

noise spikes entering the AC line and affecting the indicator, the AC power should
be relatively “clean” and within the specified limits. Drawing power from heavily
loaded  circuits  or  circuits  which  also  power  loads  that  cycle  on  and  off,
(contactors, relays, motors, machinery, etc.) should be avoided.

SIGNAL WIRING (TC SENSOR)

Remove power and connect the negative thermocouple lead (always red) to

TC-  (Terminal  6)  and  the  positive  lead  to  TC+  (Terminal  5).  Be  certain  that
connections  are  clean  and  tight.  If  the  thermocouple  probe  is  to  be  mounted
away from the meter, thermocouple extension grade wire must be used (copper
wire  will  not  work).  Use  the  correct  type  and  observe  the  correct  polarity.
Always  refer  to  the  sensor  manufacturer’s  instructions  for  probe  wiring
connections,  if  available.  For  multi-probe  temperature  averaging  applications,
two or more thermocouple probes may be connected at the meter. (Always use
the  same  type.)  In  order  to  minimize  the  chances  of  coupling  noise  into  the
wires  and  subsequently  causing  bouncy  and  erroneous  readings,  proper
guidelines for thermocouple wire routing must be followed.

PROGRAM DISABLE INPUT WIRING

PGM.DIS.  (Terminal  3)  is  a  digital  input  that  is  active  when  connected  to

Comm (Terminal 4). Any form of mechanical switch or current sinking logic with
less than 0.7 V saturation may be used. The use of shielded cable is recommended.
Follow the EMC Installation Guidelines for shield connection.

WIRING OVERVIEW

Electrical  connections  are  made  via  screw-clamp  terminals  located  on  the

back  of  the  meter.  All  conductors  should  conform  to  the  meter’s  voltage  and
current  ratings.  All  cabling  should  conform  to  appropriate  standards  of  good
installation,  local  codes  and  regulations.  It  is  recommended  that  the  power
supplied to the meter be protected by a fuse or circuit breaker.

When  wiring  the  meter,  compare  the  numbers  embossed  on  the  back  of  the

meter case against those shown in wiring drawings for proper wire position. Strip
the wire, leaving approximately 0.3" (7.5 mm) bare lead exposed (stranded wires
should  be  tinned  with  solder).  Insert  the  lead  under  the  correct  screw-clamp
terminal and tighten until the wire is secure. (Pull wire to verify tightness.) 

AC Power

Terminal 1: VAC

Terminal 2: VAC

Thermocouple

Содержание PAXLTC

Страница 1: ...the stability of the reading All set up data is stored in EEPROM which will hold data for a minimum of 10 years without power The meter has several built in diagnostic functions to alert operators of...

Страница 2: ...ns and Display 5 Programming the Meter 6 Calibrating the Meter 7 Troubleshooting 8 TABLE OF CONTENTS PAXL 0 0 TC Thermocouple Temperature Meter TC Accessories Part Numbers MODEL NO DESCRIPTION PART NU...

Страница 3: ...rds Type 4X Enclosure rating Face only UL50 IECEE CB Scheme Test Certificate UL 7470A UL CB Scheme Test Report 03ME09282 08292003 Issued by Underwriters Laboratories Inc IEC 1010 1 EN 61010 1 Safety r...

Страница 4: ...ING TC SENSOR Remove power and connect the negative thermocouple lead always red to TC Terminal 6 and the positive lead to TC Terminal 5 Be certain that connections are clean and tight If the thermoco...

Страница 5: ...Install them on Signal and Control cables as close to the unit as possible Loop the cable through the core several times or use multiple cores on each cable for additional protection Install line fil...

Страница 6: ...ution for the offset value is the same as the decimal point position programmed above The display offset is not available when mV indicator mode is selected for thermocouple type When the Input displa...

Страница 7: ...ype and verifying unit accuracy at various points over the range of the meter 10 to 80 mV 7 The factory settings for the programming parameters are shown in the previous section in the alternating dis...

Страница 8: ...wiring 1b Verify power IN DISPLAY 1 Program data error 1 Press PAR and check data set ups or IN DISPLAY 1 Input display out of range 2 Loss of data set ups DISPLAY WANDERS 1 Loss of data set ups JITTE...

Отзывы: