Module 6 is the programming module for the Setpoint (Alarm) Output
Parameters. This programming module can only be accessed if a
Setpoint card is installed. Depending on the card installed, there will be
two or four Setpoint outputs available. The Setpoint Assignment and
Setpoint Action parameters determine the applicable Setpoint features,
and dictate which subsequent parameters will appear for the Setpoint
being programmed.
This section of the bulletin replaces the bulletin shipped with the Dual and
Quad Setpoint option cards. Discard the separate bulletin when using
Setpoint option cards with the PAXCK and PAXTM.
SETPOINT
SELECT
Select the Setpoint (alarm) output to be programmed. This provides
access to the parameters for that particular Setpoint. The “
” in the
following parameter displays, reflects the chosen Setpoint number (1 thru
4). After the chosen Setpoint is programmed, the display returns to
. Select the next Setpoint to be programmed and continue this
sequence for each Setpoint. Select
to exit the module.
and
apply to Quad Setpoint cards only.
SETPOINT
ASSIGNMENT
Select the meter display to which the Setpoint is assigned: Timer (t
), Cycle Counter (
), Real-Time Clock Date display (
) or
Real-Time Clock Time display (
). (The
and
selections
only appear if a Real-Time Clock option card is installed
.)
By selecting
, the Setpoint is not assigned to a specific display.
However, the output can still be activated (set) and deactivated (reset) by
various “events”. Such events include the Timer starting or stopping, or
another Setpoint output turning On or Off. The output can also be set and
reset through a User Input function or through serial communications.
SETPOINT
ACTION
This parameter determines the mode for output
deactivation
as shown
below. Output
activation
is controlled by the
SETPOINT ON
parameter
setting.
The
and
selections are not available when Setpoint is
assigned to
.
OUTPUT
LOGIC
Normal Output Logic (
) turns the output “on” when activated and
“off” when deactivated. Reverse Output Logic (
) turns the output “off”
when activated and “on” when deactivated.
SETPOINT
ON
This parameter determines when the Setpoint output will activate.
Output activation can occur at a specific Setpoint Value (
) or can be
triggered by various “events”, as shown in the parameter list. Such events
include the Timer starting (
) or stopping (
), or by the action
(event) that causes another Setpoint output to turn On or Off. When
programmed for an event, the Setpoint must not be used as the Setpoint
On event for another Setpoint.
Selecting
displays a sub-menu where the Setpoint value is
entered. The Setpoint value is based on the meter display to which the
Setpoint is assigned (
). When assigned to the Timer or Cycle
Counter, the Setpoint value is entered in the same format as the assigned
display. When assigned to the Real-Time Clock Date Display (
), the
date value is entered in month.day.year format (
). When assigned
to the Real-Time Clock Time Display (
), the Setpoint value is always
entered in
format (Hours-Minutes with AM/PM selection). In
Setpoint One-shot mode (See Daily On Occurrence), the One-shot
Setpoint is enabled (armed) by scrolling the AM/PM digit until the 2nd
digit decimal point is lit.
SETPOINT
OFF
The Setpoint Off parameter only appears when the Setpoint Action
(
) is programmed for On-Off Output mode (
). In this mode,
this parameter determines when the Setpoint output will deactivate.
Output deactivation can occur at a specific Setpoint Off Value (
) or
can be triggered by various “events”, as shown in the parameter list. Such
events include the Timer starting (
) or stopping (
), or by the
action (event) that causes another Setpoint output to turn On or Off.
When programmed for an event, the Setpoint must not be used as the
Setpoint Off event for another Setpoint.
Selecting
will display a sub-menu where the Setpoint Off value is
entered. The Setpoint Off value is based on the meter display to which
DISPLAY
DESCRIPTION
OUTPUT DEACTIVATES
Latched Output Mode
At Reset (Manual or Automatic)
Timed Output Mode
After “Time-Out
Value” Elapses
On-Off Output Mode
Based on “Setpoint Off”
Setting
to
6.6
MODULE
6
‐
SETPOINT
(ALARM)
PARAMETERS
(
)
Setpoint
Assignment
Setpoint
Action
Time-Out
Value
Output
Logic
Setpoint
On
Setpoint
Off
Daily Off
Occurence
Daily On
Occurence
414&-
Setpoint
Select
PAR
41U
"4/O
06UO
0/O
0''O
U06UO
E0/O
E0''O
1SP
"$UO
-JUO
Setpoint
Annunciator
"6U0O
Timer/Counter
Auto Reset
U4U1O
Timer
Stop
0S4EO
Output Reset w/
Display Reset
161O
Power-up
State
PAXCK
ONLY
PAXCK
ONLY
PARAMETER MENU
This module can only be accessed if a setpoint card is installed.
= Setpoint Number 1 thru 4