background image

2

1. 

POWER REQUIREMENTS

:

Must use Class 2 or SELV rated power supply.
Power connection via removable three position terminal block.

Supply Voltage:

+24 VDC ±20% 

Typical Power

1

:

8  W

Maximum Power

2

:

14 W

Notes: 

1. Typical power with +24 VDC, RS232/485 communications, Ethernet

communications, CompactFlash card installed, and display at full brightness.

2. Maximum power indicates the most power that can be drawn from the

G306A. Refer to “Power Supply Requirements” under “Installing and
Powering the G306A.”

3. The G306A’s circuit common is not connected to the enclosure of the

unit. See “Connecting to Earth Ground” in the section “Installing and
Powering the G306A.”

4. Read “Power Supply Requirements” in the section “Installing and

Powering the G306A” for additional power supply information.

2. 

BATTERY

: Lithium coin cell. Typical lifetime of 10 years.

3. 

LCD DISPLAY

:

*Lifetime at room temperature. Refer to “Display” in “Software/Unit Operation”
4. 

5-KEY KEYPAD

: for on-screen menus.

5. 

TOUCHSCREEN

: Resistive analog

6. 

MEMORY

:

On Board User Memory

: 8 Mbyte of non-volatile Flash memory.

Memory Card

: CompactFlash Type II slot for Type I and Type II

CompactFlash cards.

7. 

COMMUNICATIONS

:

USB Port

: Adheres to USB specification 1.1. Device only using Type B

connection.

Serial Ports

: Format and Baud Rates for each port are individually software

programmable up to 115,200 baud.
PGM Port: RS232 port via RJ12.
COMMS Ports: RS422/485 port via RJ45, and RS232 port via RJ12.
DH485 TXEN: Transmit enable; open collector, V

OH

= 15 VDC, 

V

OL

= 0.5 V @ 25 mA max.

Note: For additional information on the communications or signal

common and connections to earth ground please see the “Connecting to
Earth Ground” in the section “Installing and Powering the G306A.”

Ethernet Port

: 10 BASE-T / 100 BASE-TX

RJ45 jack is wired as a NIC (Network Interface Card).
Isolation from Ethernet network to G3 operator interface: 1500 Vrms

8. 

ENVIRONMENTAL CONDITIONS

:

Operating Temperature Range

: 0 to 50°C

Storage Temperature Range

: -20 to 70°C

Operating and Storage Humidity

: 80% maximum relative humidity (non-

condensing) from 0 to 50°C.

Altitude

: Up to 2000 meters.

9. 

CERTIFICATIONS AND COMPLIANCES

:

SAFETY

IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment

for measurement, control, and laboratory use, Part 1.

IP66 Enclosure rating (Face only), IEC 529
Type 4X Enclosure rating (Face only), UL50

ELECTROMAGNETIC COMPATIBILITY

Emissions and Immunity to EN 61326: Electrical Equipment for

Measurement, Control and Laboratory use.

Note:

1. Criterion A: Normal operation within specified limits.

10. 

CONNECTIONS

: Compression cage-clamp terminal block.

Wire Gage: 12-30 AWG copper wire
Torque: 5-7 inch-pounds (56-79 N-cm)

11.

CONSTRUCTION

: Steel rear metal enclosure with NEMA 4X/IP66

aluminum front plate for indoor use only when correctly fitted with the gasket
provided. Installation Category II, Pollution Degree 2.

12. 

MOUNTING REQUIREMENTS

: Maximum panel thickness is 0.25" (6.3

mm). For NEMA 4X/IP66 sealing, a steel panel with a minimum thickness of
0.125" (3.17 mm) is recommended.

Maximum Mounting Stud Torque

: 17 inch-pounds (1.92 N-m)

13. 

WEIGHT

: 3.0 lbs (1.36 Kg)

DIMENSIONS  In inches (mm)

S

PECIFICATIONS

SIZE

5.7-inch

TYPE

TFT

COLORS

256

PIXELS

320 X 240

BRIGHTNESS

500 cd/m

2

BACKLIGHT

*

50,000 HR TYP.

Class A

EN 55011

Emissions

Emissions:

3 V/rms

Criterion A

EN 61000-4-6

RF conducted interference

2 kV L&N-E power

2 kV power

Criterion A

EN 61000-4-4

Fast transients (burst)

Criterion A

EN 61000-4-5

Surge

1 kV L-L,

10 V/m

Criterion A

EN 61000-4-3

Electromagnetic RF fields

1 kV signal

8 kV air discharge

4 kV contact discharge

Criterion A

EN 61000-4-2

Electrostatic discharge

Immunity to Industrial Locations:

WARNING - DO NOT CONNECT OR DISCONNECT CABLES
WHILE POWER IS APPLIED UNLESS AREA IS KNOWN TO BE
NON-HAZARDOUS. USB PORT IS FOR SYSTEM SET-UP AND
DIAGNOSTICS AND IS NOT INTENDED FOR PERMANENT
CONNECTION.

Содержание G306A

Страница 1: ...ww redlion net 3 Red Lion offers RJ modular jack adapters Refer to the DR literature for complete details 4 Battery type is lithium coin type CR2025 5 Industrial grade two million write cycles 6 The G...

Страница 2: ...net network to G3 operator interface 1500 Vrms 8 ENVIRONMENTAL CONDITIONS Operating Temperature Range 0 to 50 C Storage Temperature Range 20 to 70 C Operating and Storage Humidity 80 maximum relative...

Страница 3: ...ates to Crimson for new features and drivers are posted on the website as they become available By configuring the G306A using the latest version of Crimson you are assured that your unit has the most...

Страница 4: ...PC By using a cable with RJ12 ends on it and a twist in the cable RS232 communications with another G3 product or the Modular Controller can be established Red Lion part numbers for cables with a twis...

Страница 5: ...er CBLRLC05 TxA 8 TxA 8 TxB 7 TxB 7 COM 6 COM 6 TxEN 5 TxEN 5 RxA TxA 3 2 2 3 RxA TxA 3 2 2 3 RxB 4 1 RxB 4 1 TxB 1 4 TxB 1 4 Name Modular Controller Name G3 Connections DH485 COMMUNICATIONS The G306A...

Страница 6: ...ck the drive unless they need to write data Windows 98 may lock the drive any time it is mounted thereby interfering with logging Refer to Mounting the CompactFlash in the Crimson 2 User Manual TOUCHS...

Страница 7: ...our local waste regulations Also the battery must not be disposed of in fire or in a manner whereby it may be damaged and its contents come into contact with human skin The battery used by the G306A i...

Страница 8: ...conditions The Company s liability under this limited warranty shall extend only to the repair or replacement of a defective product at The Company s option The Company disclaims all liability for an...

Отзывы: