Scroll Display
This parameter determines whether or not the secondary
display will scroll or sequence automatically to the next
available value.
-26-
Serial Unit Address (00-99)
This parameter configures the Serial Unit Address. The
Address is used to uniquely identify each unit when
multiple units are connected on an RS485 bus.
Serial Abbreviate Mnemonics
When transmitting data, the unit can be programmed to
suppress the address number, mnemonics, and some spaces
by selecting
for this parameter. A selection of
results in a faster transmission and may be useful when
interfacing with a computer. However, when interfacing
with a printer, sending mnemonics is usually desirable.
Enables display scrolling (2.5 Sec display time)
Disables or turns off display scrolling
DESCRIPTION
MODE
DESCRIPTION
1200 Baud; No Parity (8 data bits)
1200 Baud; Odd Parity (7 data bits)
1200 Baud; Even Parity (7 data bits)
2400 Baud; No Parity (8 data bits)
2400 Baud; Odd Parity (7 data bits)
2400 Baud; Even Parity (7 data bits)
4800 Baud; No Parity (8 data bits)
4800 Baud; Odd Parity (7 data bits)
4800 Baud; Even Parity (7 data bits)
9600 Baud; No Parity (8 data bits)
9600 Baud; Odd Parity (7 data bits)
9600 Baud; Even Parity (7 data bits)
MODE
MODE
DESCRIPTION
Unit sends Serial Address, Value Mnemonic,
and right justified numeric value when a serial
Transmit Value command, Print Request
command, or User Input Print Request is
issued. A 400 msec “printer delay” is inserted
between each value when a Serial Print
Request command or User Input Print Request
is performed.
Only the numeric data value is transmitted
when a serial Transmit Value command, Print
Request command, or User Input Print Request
is issued. No unit address, mnemonics, or 400
msec printer delay are transmitted. This option
is beneficial when communicating with a
computer and faster data throughput is desired.
Note: The next five parameters pertain to serial communications, and are only
available on Dual Preset and Batch Models with the RS485 serial option
installed.
Serial Baud Rate and Parity Settings
This parameter configures the Baud Rate and Parity
Settings for RS485 Serial Communications.
Содержание C48C