APPENDIX “D” - PROGRAMMABLE FUNCTIONS (Cont’d)
-35-
“Pro 4” - PROGRAM DIGITAL FILTERING AND REMOTE INPUT
FUNCTION
“FILtEr”
-
Enter level of digital filtering
0
-
no digital filtering
1
-
normal filtering
2
-
increased filtering
3
-
maximum filtering
“E1-CON”
-
Enter function of remote switch (E1-CON)
0
-
re-zero input
1
-
reset total
2
-
reset and gate totalizer
3
-
gate totalizer
4
-
display hold
5
-
reset peak/valley
6
-
reset peak and start peak indicator
7
-
reset valley and start valley indicator
8
-
reset latched alarms
9
-
reset all alarms
10
-
toggle display between input and total
11
-
re-zero input and totalize the tared values
12
-
display hold with tare
13
-
instrument reading synchronization
“E2-CON”
-
Same functions as E1-CON
“Pro 5” - PROGRAM TOTALIZER
“dECPNt”
-
Enter decimal point for totalizer
“tbASE”
-
Enter time base
0
-
second
1
-
minute
2
-
hour
“SCLFAC” -
Enter multiplying scale factor
“Lo-cut”
-
Enter low-signal cut out
“Pro 6” - PROGRAM ALARMS
“trAc”
-
Enable alarm value tracking
“dISP”
-
Enable display alarm annunciators
“LAtC-1”
-
Enable alarm #1 latching
“ASN-1”
-
Enter alarm #1 trigger source (input or total)
“AL-1”
-
Enter alarm #1 value
“HYS-1”
-
Enter hysteresis value for alarm #1
“Act-1”
-
Enter alarm #1 action (high or low)
“LAtC-2”
-
Enable alarm #2 latching
“ASN-2”
-
Enter alarm #2 trigger source (input or total)
“AL-2”
-
Enter alarm #2 value
“HYS-2”
-
Enter hysteresis value for alarm #2
“Act-2”
-
Enter alarm #2 action (high or low)
“Pro 7” - NOT USED
“Pro 8” - PROGRAM RE-TRANSMITTED ANALOG OUTPUT
“ASIN”
-
Select source of analog output (input or total)
“AN-Lo”
-
Enter 4 mA or 0 VDC display value
“AN-HI”
-
Enter 20 mA or 10 VDC display value
“Pro 9” - SERVICE OPERATION
(Protected by access codes)
“Code 48”
-
Basic input calibration
“Code 66”
-
Reset programming to factory configuration