red lion APOLLO IMH Series Скачать руководство пользователя страница 32

WIRING CONNECTIONS

After the unit has been mechanically mounted, it is ready to be wired. All

wiring connections are made on removable plug-in terminal blocks. There is a
separate terminal block for the bottom board

(TBA)

and optional top board

(TBB)

. All conductors should meet voltage and current ratings for each terminal.

Also cabling should conform to appropriate standards of good installation, local
codes and regulations. It is recommended that power supplied to the unit be
protected by a fuse or circuit breaker. When wiring the unit, remove the terminal
block and use the numbers on the label to identify the position number with the
proper function. Strip the wire, leaving approximately 1/4" bare wire exposed

(stranded wires should be tinned with solder)

. Insert the wire into the terminal

and tighten down the screw until the wire is clamped tightly. Each terminal can
accept up to one 14-gage, two 18-gage or four 20-gage wire

(s)

. After the terminal

block is wired, install it into the proper location on the PC board. Wire each
terminal block in this manner.

POWER WIRING

Primary AC power is connected to TBA #1 and 2

(marked VAC 50/60 Hz,

located on the left hand side of the bottom terminal block, as you face the rear of

the meter)

. To reduce the chance of noise spikes entering the AC line and

affecting the indicator, the AC power should be relatively

“clean”

and within the

spe/-10% variation limit. Drawing power from heavily loaded circuits or
circuits which also power loads that cycle on and off,

(contactors, relays, motors,

machinery, etc.)

should be avoided.

CAUTION: Disconnect power to all unit terminals before removing
terminal blocks. This includes deenergizing the current transformer
primary circuit.

SIGNAL WIRING

AC signal wires are connected to TBA #5 and 6. If AC signal current greater

than 5 amps AC is going to be applied, the appropriate size slow blow fuse should
be installed.

CAUTION: The IMH is intended to be used with a 5 amp AC
current transformer. Use without a current transformer will place
the meter’s input and output terminals at the measured circuit’s
potential.

CAUTION: It is recommended that the current transformer be
internally protected or that a voltage clamping circuit be provided,
preventing dangerous high voltage across the CT secondary
windings in case of accidental opening of the secondary output
leads when the primary is energized. In order to prevent risk of
electric shock ensure CT is installed according to local NEC
regulations for installation of current instrument transformers.

USER INPUT WIRING

User inputs (PGM.DIS., E1-CON, and optional E2-CON) are digital inputs

that are active when connected to TBA #5 Common. Any form of mechanical
switch, sinking collector logic with less than 0.7 V saturation may be used. The
use of shielded cable is recommended. Follow the EMC Installation Guidelines
for shield connection.

OUTPUT WIRING

RELAY CONNECTIONS

To prolong contact life and suppress electrical noise interference due to the

switching of inductive loads, it is good installation practice to install a snubber
across the contactor. Follow the manufacturer’s instructions for installation.

Note: Snubber leakage current can cause some electro-mechanical devices to be

held ON.

-30-

Basic Connection

Содержание APOLLO IMH Series

Страница 1: ...THE APOLLO INTELLIGENT METER SERIES MODEL IMH INSTRUCTION MANUAL IMHCVR QXD 8 7 2006 4 46 PM Page 1...

Страница 2: ...o different indication and control requirements The Intelligent Meter which you have purchased has the same high quality workmanship and advanced technological capabilities that have made Red Lion Con...

Страница 3: ...mple 20 F Motor Monitoring Example 21 TOTALIZER LINEARIZER PEAK VALLEY TARE Optional 22 24 A Totalizer Example 22 23 B Linear Segmenting Example 23 24 ALARMS Optional 25 RE TRANSMITTED ANALOG OUTPUT O...

Страница 4: ...optional integrator totalizer linearizer can be used to totalize or integrate signals up to a maximumdisplay value of 999999 It features independent scaling and a low signal cut out to suit a variety...

Страница 5: ...r wiring connections INPUT 115 230 VN POWER POWER 50 60 Hz SUPPLY 1 4 VA 2 51 DC PGM DIS 5WC E1 CON Il I COMMON SIGNAL E2 CON 5V 12VDC DISPLAY 15V 8 8 8 8 8 8 12V E M N C PROGRAM DISABLE E1 CON NONVOL...

Страница 6: ...signal display graph automatically No span zero interaction occurs making scaling a one pass exercise Basic scaling is complete after decimal point selection unit rounding dummy zeros and digital filt...

Страница 7: ...ty to change the information that can be accessed from the front panel when the PGM DIS terminal is connected to COMM DISPLAY RESULT OF P BUTTON Pro 4 Module 4 programs the digital filtering level and...

Страница 8: ...e used to add dummy zeros to the scaled readings as desired round 1 2 5 10 20 50 100 At this stage a choice of either to return to Pro 0 or to continue with scaling of the display is offered SCALE yES...

Страница 9: ...lower segments would override higher segments ex changing SEGt from 5 to 3 causes slopes 4 5 to be replaced by an extension of slope 3 SEGt 1 9 If 1 was selected the indicator will return to Pro 0 si...

Страница 10: ...100 may also be used to add dummy zeros to the scaled readings as desired round 1 2 5 10 20 50 100 At this stage a choice of to either return to Pro 0 or to continue with scaling of the display is of...

Страница 11: ...ope was already completed Otherwise a choice of either returning to Pro 0 or commencing with the multislope linearization scaling is offered SCALE yES NO If yes was selected the display value for the...

Страница 12: ...sis values may be modified from the front panel If NO was selected for display hysteresis values then this step will default to NO and will not be displayed for selection ENtHYS yES or NO RESET LATCHE...

Страница 13: ...buffer can be cleared by walking through Pro 2 using the P button Depending on functions selected under Pro 3 and Pro 6 alarms hysteresis peak and valley values can be monitored and or changed when P...

Страница 14: ...s regardless of the state of the input 2 A negative going edge resets the contents of the totalizer to zero and allows totalization as long as the input is low If the input goes high totalization is s...

Страница 15: ...be used to span the standard time ranges or divide if scale factor 1 The following equation expresses the totalization process S F D T x T B x D T D P I D TIME I D D P S F Programmable Scale Factor D...

Страница 16: ...RESET FOR ALARM 1 The reset action of alarm 1 may be programmed to reset automatically unlatched or be programmed to require a manual reset latched through either a remote input Pro 4 E1 CON or option...

Страница 17: ...ough the front panel Latched alarms are usually used when an operator is required to take corrective action for the alarm condition LATC 2 yES or NO ALARM 2 ASSIGNMENT TO INPUT SIGNAL OR TOTALIZER Ala...

Страница 18: ...lue for the AN LO programming step and the low display value for the AN HI step Note DO NOT ADJUST THE ANALOG OUTPUT POTS ON THE BACK OF THE UNIT Fine offset and span adjustment pots are externally ac...

Страница 19: ...9 If the code number for the previous step was not recognized the indicator returns to Pro 0 with no action taken Otherwise the calibration procedure is started ENTER ZERO REFERENCE This can be accomp...

Страница 20: ...entered the alarms and hysteresis values can be modified in the same manner as in the regular programming mode The new alarm and hysteresis values will take effect when P is pressed The other operatio...

Страница 21: ...or 2 dECPNt 0 00 round 0 01 dSP 1 0 00 INP 1 0 000 dSP 2 100 00 INP 2 5 000 SEGt 1 Pro 3 dSP AL yES ENt AL yES dSPHYS yES ENtHYS yES rSt AL yES dSPbUF yES rStbUF yES SELdSP yES rSttOt yES tArE yES Pro...

Страница 22: ...RANSMISSION Drive chart recorder 4mA 0 00 and 20mA 100 00 Pro 1 Not required since scaling done in Pro 2 Pro 2 dECPNt Enter 0 00 round Enter 0 05 SCALE Enter yES dSP 1 Enter 0 00 INP 1 Enter 0 000 dSP...

Страница 23: ...nominal of 60 amps AC Alarm 1 is disabled by external control pin during motor start up due to current surges Peak and valley max min reading for each day are to be recorded The amount of current draw...

Страница 24: ...this will stop totalization when the signal level drops below this programmed value low cut At loss of power to the indicator the contents of the totalizer are saved This will allow totalizing over co...

Страница 25: ...ent of full scale for the display value These values are then used by the program user to compute the actual input and display scaling points To use the program copy it into any computer with GWBASIC...

Страница 26: ...NEXT I 2040 END 10000 REM D DISPLAY Y P PROCESS X 10010 D SQR P 10020 RETURN PEAK VALLEY The indicator will record the lowest reading valley and the highest reading peak automatically for later recall...

Страница 27: ...Alarm 2 by enabling alarm tracking This is useful in alarm set ups where a pre warning control activates before a second alarmshuts off the process When tracking is programmed changing the shut off t...

Страница 28: ...de a 4 mA or 0 VDC output AN LO and a 20 mA or 10 VDC output AN HI The analog output then follows the assigned value and as such will update every measurement cycle Nonstandard current or voltage rang...

Страница 29: ...pendix B for maximum input Adjust the span potentiometer left side so that 20 00 mA is flowing Repeat the zero and span adjustments until both are accurate Analog output calibration is complete 0 to 1...

Страница 30: ...ION Only minimum pressure is required to seal panel Do NOT overtighten screws APPENDIX A INSTALLATION CONNECTIONS INSTALLATION ENVIRONMENT Before Installing the IM into the panel the user should first...

Страница 31: ...same conduit or raceway with AC power lines conductors feeding motors solenoids SCR controls and heaters etc The cables should be run in metal conduit that is properly grounded This is especially use...

Страница 32: ...d CAUTION Disconnect power to all unit terminals before removing terminal blocks This includes deenergizing the current transformer primary circuit SIGNAL WIRING AC signal wires are connected to TBA 5...

Страница 33: ...protecting the instrument 7 ACCURACY 23 C 85 R H 45 500 Hz 0 5 of reading 5 digits 8 RESOLUTION 1 mA 9 PROGRAMMABLE DISPLAY READING RANGE 99999 to 999999 10 SIGNAL CONNECTION 2 Wire 11 READING RATE 2...

Страница 34: ...SAFETY IEC 1010 1 EN 61010 1 Safety requirements for electrical equipment for measurement control and laboratory use Part 1 IP65 Enclosure rating Face only IEC 529 Type 4 Enclosure rating Face only U...

Страница 35: ...data set ups 1a Check data set ups b Disconnect and reconnect power c Check for electrical disturbance JITTERY DISPLAY 1 Electrical Noise process or sensor lines 1a Increase digital filtering b Increa...

Страница 36: ...y reading for scaling point 1 INP 1 Apply signal level for scaling point 1 dSP 2 Enter display reading for scaling point 2 INP 2 Apply signal level for scaling point 2 SEGt Pro 2 SCALE UNIT BY KEY IN...

Страница 37: ...mal point for totalizer tbASE Enter time base 0 second 1 minute 2 hour SCLFAC Enter multiplying scale factor Lo cut Enter low signal cut out Pro 6 PROGRAM ALARMS trAc Enable alarm value tracking dISP...

Страница 38: ...OUTPUT PART NUMBERS 115 230 VAC IMH 5 AMP AC Intelligent Current Meter NO NO NO IMH40060 NO YES NO IMH40062 YES NO NO IMH43060 YES YES NO IMH43062 YES YES 4 to 20 mA IMH43066 YES YES 0 to 10 VDC IMH43...

Страница 39: ...inst damages claims and expenses arising out of subsequent sales of RLC products or prod ucts containing components manufactured by RLC and based upon personal injuries deaths property damage lost pro...

Страница 40: ...64 0839 Red Lion Controls AP 31 Kaki Bukit Road 3 06 04 05 TechLink Singapore 417818 Tel 65 6744 6613 Fax 65 6743 3360 Red Lion Controls BV Basicweg 11b NL 3821 BR Amersfoort Tel 31 0 334 723 225 Fax...

Отзывы: