11 - SAFETY DEVICES AND ALARMS
Technical Dept. - All rights reserved - Reproduction prohibited
TAMPERING WITH THE SAFETY DEVICES IS PROHIBITED
If the product is NOT used as described in this instruction manual, the manufacturer declines all liability for any
damage caused to persons and property. In particular:
•
All the necessary measures and/or precautions must be adopted when performing maintenance, cleaning and
repairs.
•
Do not tamper with the safety devices.
•
Do not remove the safety devices.
•
Connect the product to an efficient smoke expulsion system.
•
First, check that the environment where it is to be installed is properly ventilated.
Only after eliminating the cause of the intervention of the safety system is it possible to start the product back up.
This manual will help you understand which anomaly has occurred, and explain how to intervene according to the
alarm message displayed on the appliance.
Boiler stop
The following conditions may cause the boiler to be stopped:
•
Overheating of the structure and pellet tank
•
Overheating of the water in the boiler
•
High pressure of the outlet fumes (read on the pressure switch) and possible obstruction of the outlet.
The control panel will indicate the cause of the alarm and sound an acoustic warning.
In this situation, the automatic shut-down sequence is activated.
When this sequence is initiated, any attempt to restart the system will be ineffective.
Safety thermostat with manual rearming at 85°C
The boiler enters a safety ALARM state called “
A03
” Thermostat alarms, caused by high water temperature. To reset the thermostat and
cancel the alarm, lift the front lid and, with a non-metal tool and without removing the rubber cap covering the thermostat, press the
button to reset it. You will hear a click from the thermostat, which means it has been reset.