14
14
10 - MENU ITEMS AND FUNCTION
l - Maximum power
Allows you to set the maximum power limit of the flames which the boiler can use to reach the set target temperature.
Modify the power as follows:
•
Press the “menu” key.
•
Use the arrow keys to scroll through and select “Settings”
•
Press “menu” to confirm.
•
Scroll with the arrows and select ‘’Maximum power’’.
•
Press “menu” to confirm.
•
Change the power from 01 to 05 using the + - keys.
•
Press ‘’menu’’ to confirm and ‘’esc’’ to exit.
m - Components test
This can be done only when the boiler is off and allows you to select the components to be tested:
•
Glow plug:
it is turned on for a fixed test period of 1 minute during which the panel displays the countdown in seconds.
•
Feed screw
: it is powered for a fixed period of 1 minute during which the panel displays the countdown in seconds.
•
Extractor
: it is activated at 2500 rpm for a fixed period of 1 minute during which the panel displays the countdown in seconds.
•
Heat exchanger
: enables you to conduct the test in V5 for a fixed period of 1 minute during which the panel displays the countdown
in seconds.
•
Pump
: it is activated for a fixed period of 10 seconds during which the panel displays the countdown.
•
3-way valve:
the 3-way valve is activated for a fixed test period of 1 minute during which the panel displays the countdown in
seconds.
Enable the “Component test” function (only with boiler off) as follows:
•
Press the “menu” key.
•
Use the arrow keys to scroll through and select “Settings”
•
Press “menu” to confirm.
•
Use the arrow keys to scroll through and select ‘’Component test’’
•
Press “menu” to confirm.
•
Use the + - keys to select the test to be carried out.
•
Press ‘’menu’’ to confirm and ‘’esc’’ to exit.
n - Chimney sweep Function
This function can only be activated when the boiler is on and power is supplied, and it forces operation of the boiler at the parameters
P5, with the ventilator (if present) in V5. Any corrections to the loading/smoke ventilation percentage must be read. This state lasts 20
minutes, the countdown is displayed on the panel. During this interval, the system ignores any thermostat/puffer/room set point/ H
2
0 set
point values, only the safety shut-down at 85°C remains active. The technician can stop this phase at any moment by quickly pressing the
on/off key.
Enable the “Chimney sweeper” function as follows:
•
Press the “menu” key.
•
Use the arrow keys to scroll through and select “Settings”
•
Press “menu” to confirm.
•
Use the arrow keys to scroll through and select ‘’Chimney sweeper function’’
•
Press “menu” to confirm.
•
Use the + - keys to select “On” (Off by default)
•
Press ‘’menu’’ to confirm and ‘’esc’’ to exit.
Содержание SELECTA 30 S1
Страница 18: ...18 3 2 5 5 17 13 11 4 4 15 14 7 6 1 V 18 10 MENU ITEMS AND FUNCTION CONFIGURATION 4...
Страница 39: ......