background image

REC TwinPeak Series Installation Manual - UL 1703
Rev B - 03.15 

Ref: NE-06-08-B

4

ELECTRiCaL iNSTaLLaTioN 

ElECtRICal REQuIREmEnts
i)  system Requirements

REC TwinPeak panels are only for use where they meet the specific technical requirements of the complete system.  Ensure other components do not 

cause mechanical or electrical damage to the panels. 

ii) Connection

if panels are connected in series, they should have the same amp rating.  if panels are connected in parallel, they should have the same voltage rating.

iii)  string configuration

when using string configuration, plan and execute it according to inverter manufacturer’s instructions.  The number of panels connected to an inverter 

should be within the inverter voltage limits and operating range.  Do not exceed the total system voltage permitted by the manufacturer, nor under any 

circumstance exceed the maximum system voltage of 1000 v.  The maximum reverse current is 15 a and the maximum series fuse rating is 15 a.

iv)  wiring layout

To minimize voltage surges (e.g. indirect lightning strikes), cables of the same string should be bundled together so loops are as small as possible.  

String configurations must be checked before commissioning.  if open circuit voltage (v

oC

) and short circuit current (i

SC

) deviate from specification, 

this may indicate a configuration fault.  Correct DC polarity should be observed at all times.

v)  Junction box, connectors and materials

The panel junction box is rated iP67, the connectors are rated iP67 only when correctly connected.  all connectors and cables must be secure and 

tight as well as electrically and mechanically sound.  Uv-resistant cables and connectors approved for outside use must be used.  Conductor gauge 

must ensure DC power losses (voltage drop) are kept to a minimum (< 1%).  observe all local regulations when selecting cables.  For field connections, 

use minimum 12 awg (4 mm²) or copper wires insulated for a maximum operating temperature of 90°C.

vi)  Cable management

Cables must be secured using Uv-resistant cable ties or other sunlight-resistant device.  Loose and unsecured cables should be protected from 

damage (e.g. mechanical, abrasion, sharp objects, animals).  as far as possible, avoid exposing cables to direct sunlight and permanent tension.

REC prohibits any modification to the panel, including the cutting of cables in order to change the connector type or the opening of the 

junction box unless explicitly authorized by REC.  Doing so will invalidate the warranty.

vii)  Electrical Ratings

Under normal conditions, a photovoltaic panel is likely to experience conditions that produce more current and/or voltage than reported at STC.  The 

requirements of the National Electric Code (NEC) in article 690 must be followed to address these increased outputs.  in installations not under the 

requirements of the NEC, the values of i

SC

 and v

oC

 marked on the panels must be multiplied by a factor of 1.25 when determining component voltage 

ratings, conductor ampacities, overcurrent device ratings and size of controls connected to the Pv output.

safEty mEasuREs

wiring installation shall be in accordance with the NEC (or CSa C22.1, Safety Standard for Electrical installations, Canadian Electrical Code, Part 1 

where applicable).  all relevant electrical installation codes and regulations should be observed for regulations on working at heights and fall protection.

i)  safety in the working area

installation of REC TwinPeak panels may involve working on a roof.  Ensure all local regulations regarding working at heights are followed.  before 

beginning work on a photovoltaic system, ensure all working surfaces are structurally sound and capable of bearing the weight of employees and 

required equipment.  Remember to isolate the system from the grid before carrying out any maintenance or repair work.

ii)  preventing current generation

Solar panels automatically generate current (electricity) when exposed to light.  To prevent this, shield the system with a non-transparent cover during 

installation, maintenance or repair work.

ii)  specific hazards of DC electricity

Solar panels generate direct current (DC).  once current is flowing, breaking or opening a connection (e.g. removing a DC cable from the inverter) can 

cause an electrical arc.  Unlike low voltage aC wiring, DC arcs are not self-extinguishing.  They are potentially lethal burn and fire hazards, capable of 

high temperatures that can destroy contacts and connectors:

• 

Follow panel and inverter manufacturers’ installation, handling and operating instructions

• 

Remove/open the inverter aC fuse/circuit breaker before disconnecting from the public grid.

• 

Switch off or disconnect the inverter and wait for the time specified by the manufacturer before commencing work.  High-voltage components 

need sufficient time to discharge.

iv)  safety requirements

The voltage produced by a single panel and panels connected in series (voltages added together) or in parallel (currents added together) can be 

dangerous.  although the fully insulated plug contacts on the panel’s output cables provide touch-safe protection, the following points must be 

observed during handling to avoid the risk of sparking, fire hazards, burns and lethal electric shocks.

• 

Exercise extreme caution when wiring panels and look out for damaged or dirty cables etc.

• 

Never insert metallic or other conductive objects into plugs or sockets.

• 

Ensure that all electrical connections are completely dry before assembly.

• 

keep all materials, tools and working conditions dry and tidy.

• 

Use appropriate safety equipment e.g. nonslip footwear, insulated gloves and insulated tools. 

• 

Solar panels produce current when exposed to sunlight.  Do not connect the system to the inverter during solar exposure.

Содержание REC265 Series

Страница 1: ...Installation manual rec TwinPeak SERIEs FortheinstallationofRECTwinPeakSeriessolarpanels certifiedaccordingtoUL1703 ...

Страница 2: ...on 4 ii Specific hazards of DC electricity 4 iv Safetyrequirements 4 MECHANICAL INSTALLATION 5 FIRE GUIDELINES 5 ORIENTATION 5 ENVIRONMENTAL FACTORS 5 Panel HANDLING 5 MOUNTING the panels 6 Panel Installation 6 i Rail specifications 6 ii Clamp Specification 6 iii Mounting holes 7 iv Slide in Systems 7 v Drainage holes 7 vi Long side mounting using clamps 8 vii Shortside mounting using clamps 8 vii...

Страница 3: ...hich highlight important information or notes Indicates potential for damage to the array or property or personal safety Indicates important notes on best practice to help with the installation or to avoid potential damage to the panels array or property For further information on installation procedures please call your distributor or contact your local REC Solar office Details available at www r...

Страница 4: ...outputs In installations not under the requirements of the NEC the values of ISC andVOC marked on the panels must be multiplied by a factor of 1 25 when determining component voltage ratings conductor ampacities overcurrent device ratings and size of controls connected to the PVoutput SAFETY Measures Wiring installation shall be in accordance with the NEC or CSA C22 1 Safety Standard for Electrica...

Страница 5: ...it can be easily accessed in the event of a building fire Check with local authorities for applicable regulations concerning setbacks or other placement restrictions that may apply for roof mounted arrays The use of DC ground fault interrupters is recommended This may also be required by local and national codes All electrical appliances are a fire risk The panel should therefore be mounted over a...

Страница 6: ...ling load Fig 2 Rail specification C channel rail H channel rail The clamps should be fastened to C or H channel rails fig 2 Thickness of walls for mechanical connections min 0 156 in 4 0 mm Thickness of walls exposed to buckling load min 0 08 in 2 0 mm Moment of Inertia for profile area about X X min array mounting diagram 0 4 in4 19 2 cm4 The overlap between support rail and the outer edge of th...

Страница 7: ...g clamps Mounting utilizing clamps on the two short sides of the panel have been found to be in compliance with UL 1703 requirements for a maximum design load of 33 4 lbs ft 1600 Pa fig 9 Fix the panels so that the lower short side of the frame is supported by the mounting structure to reduce risk of damages due to sliding snow load Clamps must be secured between a distance of 4 9 and 9 8 inches 1...

Страница 8: ...ls are preferred however galvanized or hot dipped zinc plated fasteners are equally suitable Grounding cable Star washer Grounding lug dimensions and wire fastening torque for GBL 4DBT Fig 7 Drainage holes v Drainage holes There are eight drainage holes 0 47 x 0 30 in 12 x 7 5 mm in the panels frame each spaced 2 2 in 55 mm from the corner of the panel frame fig 5 This allows water caused by rain ...

Страница 9: ...cal integrity of the cables is intact Bonding points to ground are tight secure and free from corrosion which could break the continuity between the panels and ground Recycling REC has made every effort to ensure panel packaging is kept to a minimum The paper and cardboard packaging can be recycled and the protective wrapping and panel separating blocks are also recyclable in many areas Please rec...

Страница 10: ...nder standard test conditions STC Values at STC airmass AM 1 5 irradiance 1000 W m cell temperature 25 C 77 F At low irradiance of 200 W m AM 1 5 and cell temperature 25 C at least 94 of the STC panel efficiency will be achieved followed by TP TP BLK TP ECO Fig 12 Panel dimensions in Dimensions 65 55 x 39 02 x 1 5 in Area 17 76 ft Weight 39 6 lbs Operational Temperature 40 185 F 40 85 C Maximum Sy...

Страница 11: ...10 A First release 12 2014 A 2 Update to Electrical data STC 275 Wp IMPP 12 2014 A 3 Update to Electrical data STC addition of 260 280 Wp revision of low light behavior data in Electrical Data 03 2015 B Updated to include information on panel variants ...

Страница 12: ...RECSolarPte Ltd 20TuasSouthAvenue14 Singapore637312 Singapore Tel 6564959228 Mail post recgroup com www recgroup com ...

Отзывы: