background image

REC Peak Energy Series Installation Manual - UL 1703
Ref: NE-06-03-M 

Rev M - 03.2014

10

aNNex 1. iNsTallaTioNs oN waTer PlaTforMs

reC Peak energy panels have not been certified by ul for installation on water platform-type mounting systems.  when installating reC Peak 

energy panels on fixed position (e.g., anchored) water platforms, for example, floating pontoons, follow the instructions below specific to such 

applications.  failure to do so will invalidate the warranty.

For all installations on water platforms, first advise REC before the start of installation in case of any site specific instructions or 

constraints

InstallatIon enVIRonment
i)  Installation site

• 

reC panels may only be installed on closed bodies of fresh water where water salinity does not exceed 15 Psu at 77°f (25 ms/cm at 25°C).  

This specifically excludes mounting on sea and ocean applications.

• 

The maximum permitted wave height must not exceed 3.3 ft (1 m) from the crest to the trough of the wave.

ii) floating platforms

• 

when using a floating platform, follow the  manufacturer’s instructions regarding installation, maintenance, inspection and cleaning at all times.

iii) minimum installation height

• 

The minimum installation height of reC Peak energy panels is 6 in (15 cm) and is defined as the height between the water surface and the 

lowest edge/part of the panel during normal operation.  This will help to shield the panel from direct water spray.

InstallatIon InstRuCtIon
i) system installation

• 

all cables used for the installation must have sufficient length and slack to prevent damage due to water level changes and wave motions.

Negative system grounding is required for REC Peak Energy panels installed on a floating platform

ii) mounting panels

• 

installation of reC Peak energy panels must be in accordance with the aforementioned standard mounting instructions.

• 

The junction box should be oriented as far as possible from the water surface according to system design and the junction box, cables and 

connectors must be protected from direct water splash.

iii) panel protection

• 

in areas with high avian activity, additional bird repelling devices may be installed as long as they do not adversely affect system performance.

• 

if using lightning protection equipment on the floating installation, all relevant local regulations must be respected.

maIntenanCe

• 

regularly inspect the installation to ensure all panels are securely mounted.

For installations with high avian activity, system cleaning may be required at more frequent intervals to reduce shading of panels 

caused by bird defecation

safety

• 

immediately disconnect the system if the installation or the floating platform exhibits deviation from standard operating conditions.

• 

in the event of the floating platform being submerged, disconnect the DC connection at the inverter immediately.  Do not attempt to salvage 

panels when sunlight is present.

Содержание REC235 Series

Страница 1: ...InstallatIon manual rec Peak energy series For the installation of panels certified according to UL 1703...

Страница 2: ...ireMeNTs 4 meCHanICal InstallatIon 5 fire guiDeliNes 5 orieNTaTioN 5 eNviroNMeNTal faCTors 5 PaNel HaNDliNg 5 mountInG tHe panels 6 PaNel iNsTallaTioN 6 i rail sPeCifiCaTioNs 6 ii ClaMP sPeCifiCaTioN...

Страница 3: ...w icons which highlight important information or notes Indicates potential for damage to the array or property or personal safety Indicates important notes on best practice to help with the installati...

Страница 4: ...requirements of the NeC the values of isC andvoC marked on the panels must be multiplied by a factor of 1 25 when determining component voltage ratings conductor ampacities overcurrent device ratings...

Страница 5: ...th local authorities for applicable regulations concerning setbacks or other placement restrictions that may apply for roof mounted arrays The use of DC ground fault interrupters is recommended This m...

Страница 6: ...rails fig 2 Thickness of walls for mechanical connections min 0 156 in 4 0 mm Thickness of walls exposed to buckling load min 0 08 in 2 0 mm Moment of inertia for profile area about x x min array moun...

Страница 7: ...1703requirementsforamaximumdesignloadof75 2lbs ft 3600Pa fig 5 when mounting using mounting holes the frame and panel edge must be supported by two transverse rails fig 1 p 8 of aluminium or galvanize...

Страница 8: ...reC Peak energy panels utilizing clamps on the two long sides of the panel have been found to be in compliance with ul 1703 require ments for a maximum design load of 75 2 lbs ft 3600 Pa fig 8 Clamps...

Страница 9: ...ical integrity of the cables is intact bonding points to ground are tight secure and free from corrosion which could break the continuity between the panels and ground ReCyClInG reC has made every eff...

Страница 10: ...normal operation This will help to shield the panel from direct water spray InstallatIon InstRuCtIon i system installation all cables used for the installation must have sufficient length and slack t...

Страница 11: ...of the indicated values of isC voC and PMPP under standard test conditions sTC values at sTC airmass aM 1 5 irradiance 1000 w m cell temperature 25 C 77 f at low irradiance of 200 w m aM 1 5 and cell...

Страница 12: ...2013 i 2 addition of low watt classes 214 230wp for ul records 04 2013 i 3 update of tightening torque for clamping and mounting holes 06 2013 i 4 update of torque rating for long side clamping and m...

Страница 13: ...RECSoLaRPtE Ltd 20tuasSouthavenue14 Singapore637312 Singapore tel 6564959228 Mail post recgroup com www recgroup com...

Отзывы: