ST-72 User's Manual
Document: UM-1007
Revision Level A
40
ST-90 controller detects an alarm condition. If SYMPATHY ENABLED is set to YES then
the ST-72 controller, which is the master in the network, broadcasts alarm flags to all ST-
90s in the network. ST-90 controllers that are configured to react to these flags then
energize their relays configured to trip for that alarm. The following sympathy
parameters only show up if sympathy is set to
YES
.
2.5.1.6.1
FAULT TRANSMIT
When set to
YES
the ST-72 broadcasts the Fault alarm flag out of the communication
port. This option is only available if SYMPATHY ENABLED is set to YES.
2.5.1.6.2
A1 TRANSMIT
When set to
YES
the ST-72 broadcasts the alarm 1 alarm flag out of the communication
port. This option is only available if SYMPATHY ENABLED is set to YES.
2.5.1.6.3
A2 TRANSMIT
When set to
YES
the ST-72 t broadcasts the alarm 2 alarm flag out of the communication
port. This option is only available if SYMPATHY ENABLED is set to YES.
2.5.1.6.4
SYMPATHY A2 ACK
When set to
YES
the ST-72 broadcasts the alarm acknowledge flag to acknowledge all
ST-90 relays on the network configured to be acknowledgeable. This option is only
available if SYMPATHY ENABLED is set to YES.
2.5.1.6.5
A3 TRANSMIT
When set to
YES
the ST-72 broadcasts the alarm 3 alarm flag out of the communication
port. This option is only available if SYMPATHY ENABLED is set to YES.
2.5.1.7 RADIO SETUP
RADIO SETUP
is used to configure radio kits that are connected directly to the ST-72.
2.5.1.8 SLAVE BYTE ORDER
If Modbus Slave is selected, a
BYTE ODER
entry appears in the menu. This
determines WORD and BYTE alignment of data at the remote Modbus transmitter when
sending its 4 byte IEEE Floating Point values. With the select bar on this entry, the
Edit
toggles between the 4 possible modes. Min / Max Raw values are not used in this
mode.
2.5.1.9 WIRELESS TIMEOUT
If Wireless Monitor is selected, a
WIRELESS TIMEOUT
entry appears in the menu.
The
Edit
toggles between 1m, 6m, 12m, and 18m. These represent the number of
minutes the ST-72 will wait before going into COMM. ERROR.
Содержание ST-72
Страница 106: ...ST 72 User s Manual Document UM 1007 Revision Level A 100...
Страница 108: ...ST 72 User s Manual Document UM 1007 Revision Level A 102 Figure 6 4...
Страница 127: ...ST 72 User s Manual Document UM 1007 Revision Level A 121 8 5 2 CHANNEL CONFIGURATION Figure 8 6...
Страница 128: ...ST 72 User s Manual Document UM 1007 Revision Level A 122 8 5 3 COPY CHANNELS Figure 8 7...
Страница 129: ...ST 72 User s Manual Document UM 1007 Revision Level A 123 8 5 4 PROGRAMMABLE RELAYS Figure 8 8...
Страница 130: ...ST 72 User s Manual Document UM 1007 Revision Level A 124 8 5 5 SYSTEM CONFIGURATION Figure 8 9...