ST-72 User's Manual
Document: UM-1007
Revision Level A
94
Channel
Enable
1-64
47697 47760 1
3
6, 16
No = 0,
Yes
= 1
Zone
1-64
47761 47824 1
3
6, 16
Zone 1
= 0,
Zone 2 = 1,
Zone 3 = 2,
Zone 4 = 3,
Zone 5 = 4,
Zone 6 = 5,
Zone 7 = 6,
Zone 8 = 7,
Deadband%
1-64
47825 47952 2
3
16
32bit IEEE Float (0.0 –
5.0)
5.3.11
PROGRAMMABLE RELAYS
The programmable relay option allows 16 relays to be configured. The configuration
parameters are the same for all 16 relays. The following table shows the base address of each
programmable relay.
Programmable Relay
Number
Base Modbus Address
Relay 1
49000
Relay 2
49040
Relay 3
49080
Relay 4
49120
Relay 5
49160
Relay 6
49200
Relay 7
49240
Relay 8
49280
Relay 9
49320
Relay 10
49360
Relay 11
49400
Relay 12
49440
Relay 13
49480