SenSmart 6000 wiring
3
Remote
Sensor
1.
Connect 10-30VDC power lead to TB1.1.
(See Figure 1)
2.
Connect Common (ground) lead to TB1.4
(See Figure 1)
FOR ANALOG OUTPUT:
3.
Connect signal lead to TB1.2. (Channel 1) and/or
TB1.3 (Channel 2) (4-20mA Out)
(See Figure 1)
FOR ETHERNET OUTPUT:
4.
Connect Ethernet cable to J3. (Ethernet output)
(See Figure 1)
(optional)
(By default, DHCP is enabled on the transmitter,
allowing the device to be discovered by its IP
address.)
Installation of Gas Detector
Remove windowed lid from unit.
1.
AL Enclosure -
a.
Loosen lid set screw
b.
Rotate lid clockwise and remove
c.
Loosen thumb screws on display to remove
display and access terminals
2
.
PY Enclosure -
a.
Unscrew lid screws (4) to access terminals.
What you need (not included)
1.
Small Flathead Screwdriver
2
.
Phillips Screwdriver (for poly enclosure)
3
. Wire
(RC Systems recommends: Belden 3124A
Multi-Conductor wire or equivalent.)
Figure 1