FUTERA FUSION INSTALLATION AND OPERATION INSTRUCTIONS

5.   The outside surfaces of the copper tubes should 

be free of any soot deposits. A slight black smudge 
is normal with some types of gases. Black soot 
indicates poor combustion. Green deposits indicate 
condensation due to low return water temperatures. 
Water returned to the water heater inlet must not be 
less than 

125°F

52°C

 or excessive condensation of the 

products of combustion will damage the water heater 
voiding the warranty. In either case the heat exchanger 
must be cleaned thoroughly and the problem resolved 
before the boiler/water heater is returned to service. 

6.   If there are no signs of damage, sooting or corrosion, 

reassemble the unit following the previous steps in 
reverse order. 

7.   A badly corroded or damaged heat exchanger must 

be replaced, see the 

Heat Exchanger Repair & 

Replacement

 section.

Heat Exchanger Cleaning

1.   Close the shut off valves in the inlet and outlet piping. 

On heating systems close the system fi ll valve and 
relieve the system pressure from the boiler by carefully 
lifting the relief valve or opening the drain valve. 

2.   Disconnect the boiler/water heater from the system 

piping. 

3.   Remove the eight bolts on the rear pipe enclosure 

panel. 

4.   Remove the front jacket panel and combustion 

chamber door. 

5.   Slide the heat exchanger out of the unit. 
6.   Remove the “V” baffl e straps and “V” baffl es. 
7.   Thoroughly clean the heat exchanger with water from 

a high-pressure hose. Use a soft bristle brush if 
necessary. 

8.   Replace the cleaned heat exchanger and other 

components in the reverse order of their removal.

Heat Exchanger Repair & Replacement

1.   A leaking or otherwise damaged tube(s) can be 

replaced as outlined in steps 2 through 8. 

2.   Remove the heat exchanger from the boiler/water 

heater as outlined in the 

Heat Exchanger Cleaning

 

section. 

3.   Remove the pipe plugs from the inlet/outlet and return 

headers opposite from the ends of the tube(s) being 
replaced. 

4.   Carefully cut the damaged tube(s) in half, taking care 

not to damage the adjacent tubes and remove. 

5.   Install and swage/expand in place the new tube(s). 
6.   Replace the pipe plugs using a suitable thread sealant 

on each one. 

7.   Sagging or distorted heat exchanger tubes are an 

indication of low water fl ow through the system. A 
damaged heat exchanger must be replaced and the 
condition that caused the damage resolved before the 
boiler/water heater is returned to service. 

8.   Replace the heat exchanger and other components in 

the reverse order of their removal.

RIOM-18-REV.

 

A

Air Intake & Vent System

Thoroughly inspect the air intake and vent systems for 
any signs of blockage, corrosion or leakage. Immediately 
replace any unsound vent system piping. Inspect the air 
fi lter and wash with warm water and soap if dirty.

Controls

Use the “GENERAL OPERATION” and “CHECKING AND 
ADJUSTMENTS” sections of this manual for reference.
1.   Check the operating controls for proper operation. 
2.   A fl oat type low water cutoff device must be fl ushed 

out per the manufacturers’ instructions. The probe on 
a probe low water cut off must be removed, cleaned 
and inspected at least once a year. Ensure that the 
low water cutoffs operate properly. If not, replace 
them. 

3.   The fl ow switch contacts must be open when water 

fl ow is not present. 

4.   The relief valve should not weep or discharge water 

at normal system pressure. If it does, contact a 
qualified service technician to have it inspected. 
NEVER try to clean or repair the relief valve! If the 
valve fails to operate properly, have it replaced! 

5.   The aquastat high limit controls the maximum water 

temperature in the boiler. It is adjustable from 

140°F

60˚C

 to 

250°F

121°C

. If the water temperature reaches 

the set temperature before the demand for heat has 
been met, the aquastat high limit should shut the boiler 
off. The water temperature should never exceed the 
maximum set point of 

250°F

121°C

.  The aquastat high 

limit cannot be repaired. If it fails to function properly, 
replace it. 

6.   Visually check the pilot and main burner fl ames to 

ensure proper operation, see Figures 16 & 17.

WARNING: A yellow, fl oating fl ame indicates a lack 
of combustion air. Do not operate the boiler/water 
heater until the problem is solved or severe 
personal injury or death may occur!

Figure 17 – Main Burner Flame

Содержание FUTERA FUSION CB-1000

Страница 1: ...or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch D...

Страница 2: ...tretien doivent tre assur s par un installateur ou un service d entretien qualifi ou par le fournisseur de gaz The Futera Fusion Series finned copper heating boiler water heaters have been design cert...

Страница 3: ...duction of combustion air into the unit or subject it to a negative pressure see GENERAL VENTING GUIDELINES 6 NEVER place this boiler water heater in a location that would subject it to temperatures a...

Страница 4: ...given to the blockage effects of louvers grills and screens Screens must have a minimum mesh size of 1 4 in 6 4 mm If the free area through a louver or grill is not known ducts should be sized per Tab...

Страница 5: ...r terminal are equal to 10 linear ft 3 0 m of pipe see Table 3 An approved nonrestrictive intake air terminal must be used The intake air terminal must terminate as shown in Figure 3 The penetration p...

Страница 6: ...400 F 204 C Horizontal vent systems shall terminate at least 4 ft 1 2 m below 4 ft 1 2 m horizontally from or 1 ft 0 30 m above any door window or gravity air inlet into any building It must not term...

Страница 7: ...ts exhaust and combustion air terminals must be installed on the same plane outside wall in order to prevent pressure differences due to prevailing winds In cold climates double wall or insulated inle...

Страница 8: ...N AND OPERATION INSTRUCTIONS Figure 3 Vertical Air Intake and Venting for Direct Vent System Figure 4 Combination Direct Vent Systems 10 FT 3 1 m 4 FT 1 2 m 5 FT 1 5 m 1 5 FT 0 5 m 5 1 2 FT 1 7 m 1 5...

Страница 9: ...ower is used to push the flue products horizontally to the outdoors see Figure 5 The air for combustion is taken from the space in which the unit is installed The applicable instructions under the COM...

Страница 10: ...10 FUTERA FUSION INSTALLATION AND OPERATION INSTRUCTIONS Figure 6 Vertical Venting with a Metal Chimney System 10 FT 3 1 m...

Страница 11: ...e as shown in Figure 8 WARNING Never install any type of valve between the boiler water heater and the relief valve or an explosion causing extensive property damage severe personal injury or death ma...

Страница 12: ...igure 8 Futera Fusion Piping Air Vent Aquastat Union Automatic Thermometer Flow Switch Pressure Relief Valve Reducing Valve Check Valve Pressure Pump Valve Balance Valve Vacuum Relief Valve Temperatur...

Страница 13: ...lve and piping Low Water Cutoff If a boiler is installed above any radiation elements it must be fitted with a low water cutoff device Refer to the wiring diagram supplied with the boiler water heater...

Страница 14: ...ated on pump flange On multiple boiler installations the flow switch may fail due to trapped air See manual for procedure 3 All boilers furnished with factory mounted outlet water temperature gauge No...

Страница 15: ...filled Use purge valves provided Purge valve may be located on pump flange On multiple boiler installations the flow switch may fail due to trapped air See manual for procedure 4 All boilers furnished...

Страница 16: ...usion water heater is 97 GPM 6 1 L s on 500 through 1000 models and 136 GPM 8 9 L s for 1250 through 2000 models The cupro nickel heat exchanger allows for 108 GPM 6 8 L s on 500 through 1000 models a...

Страница 17: ...xchanger Selection Graph To properly size the pump a grain hardness and pH test must be taken at the installation site before the order is placed Proper pump sizing will improve heater performance and...

Страница 18: ...be equipped with a combination temperature pressure relief valve 6 MA Code requires an 1 8 hole in check valve to compensate for thermal expansion 7 Use balance valve to set the temperature rise throu...

Страница 19: ...equipped with a combination temperature pressure relief valve 6 MA Code requires an 1 8 hole in check valve to compensate for thermal expansion 7 Use balance valve to set the temperature rise through...

Страница 20: ...make sure that the boiler water heater is for the type of gas that will be used If it isn t do not connect the boiler water heater to the gas supply Gas supply piping must be in accordance with the N...

Страница 21: ...roceeding read and fully understand the instructions contained in this manual Do not attempt to operate this boiler water heater if it has not been installed in accordance with the guidelines set fort...

Страница 22: ...voisin Suives les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur appelez le service de incendies C Do not use this appliance if any part has been under water Immediately call...

Страница 23: ...allumage 14 R glez la pression de la veilleuse tel qu indiqu la section V RIFICATION ET R GLAGES 15 Commutez nouveau le Honeywell 7897C en mode marche 10 Monitor the flame current on the Honeywell Bu...

Страница 24: ...ith the main and pilot gas manual valves in the closed position energize the unit Observe the trial for ignition to confirm that the spark is strong and continuous If not check and adjust the spark ga...

Страница 25: ...gulations install a low water cutoff in appropriate piping Wire the switch and any external controls in series to the Interlock contacts in the junction box see the attached Connection Diagrams for de...

Страница 26: ...the boiler water heater when the operating sensor is 1 2 of the differential setting below the boiler target temperature and will stop the boiler water heater once the modulating output is at the mini...

Страница 27: ...OCKOUT HI LIMIT GAS PRESSURE Indicates that both the high limit and gas pressure interlocks are open MULTIPLE INTERLOCK Indicates that there are more than 2 interlocks that are open Check the high lim...

Страница 28: ...tubes and remove 5 Install and swage expand in place the new tube s 6 Replace the pipe plugs using a suitable thread sealant on each one 7 Sagging or distorted heat exchanger tubes are an indication...

Страница 29: ...Wire power venter as shown in connection power venter external power diagram Defective power venter timer TD1 Replace power venter timer TD1 Defective flame sense relay Replace flame sense relay Powe...

Страница 30: ...uring ignition trial adjust as necessary Defective flame sense relay Replace flame sense relay Main valve malfunctioning Replace main valve Insufficient heating Target temperature set too low Increasi...

Страница 31: ...TION AND OPERATION INSTRUCTIONS Figure 18 Exploded View RIOM 20 REV B SEE VIEW A SEE VIEW B 15B 15A 41 32 36 57 46 13 35 40 33 31 23 27 60A 24 62 28 47 39 15 SEE VIEW C 38 37 25 67 66 62 65 30 63 43 4...

Страница 32: ...32 FUTERA FUSION INSTALLATION AND OPERATION INSTRUCTIONS 74 1 73 71 12 8 70 10 71 72 3 8 3 8 1 8 75 76 6 10 4 11 75 12 5 9 5 10 1 2 1 2 4 12 70 7 VIEW C RIOM 73 VIEW B ROTATED VIEW 16 18 VIEW A...

Страница 33: ...2 2 04 1074 2 2 2 2 14 Gas Train Support Bracket Assembly 70 2344 1 1 70 2345 1 1 1 70 2346 1 1 15 Burner 10 0280 1 10 0309 1 10 0308 1 10 0286 1 10 0288 1 10 0290 1 10 0292 1 15a Burner Gasket 06 002...

Страница 34: ...e KBVF 14W 15 0227 1 1 1 Frequency Drive KBVF26D 15 0226 1 1 1 1 27 Jacket Top Panel 70 2412 1 1 1 70 2413 1 1 1 1 28 Upper Rear Panel 70 2414 1 1 1 70 2415 1 1 1 1 29 Rear Pipe Enclosure Assembly 70...

Страница 35: ...icator CB 30 50 psi 13 0308 1 1 1 1 1 1 1 Tridicator CB 60 160 psi 13 0305 1 1 1 1 1 1 1 46 Heat Exchanger Copper 70 2186 1 70 2187 1 70 2188 1 70 2189 1 70 2190 1 70 2191 1 70 2192 1 Heat Exchanger C...

Страница 36: ...1 1 70 2377 1 1 1 1 NS Harness RM7800 40 0117 1 1 1 1 1 1 1 NS Harness 120V Switch 40 0118 1 1 1 1 1 1 1 NS Harness Tekmar 40 0119 1 1 1 1 1 1 1 NS Harness Transformer 40 0120 1 1 1 1 1 1 1 NS Harness...

Страница 37: ...4 1 1 1 1 1 1 1 NS Futera Fusion Overlay 82 0195 1 1 1 1 1 1 1 NS Paint 66 0013 1 1 1 1 1 1 1 NS Silicone 66 0151 1 1 1 1 1 1 1 OPTIONS NS Alarm Bell 70 2232 1 1 1 1 1 1 1 NS Main Flame Status Contact...

Страница 38: ...ated on the display board Also locate the gas pressure tapping upstream of the main gas valve 1 Cycle boiler and hold at trial for pilot ignition 2 Set pressure to 2 2 5 W C Flame signal should read 5...

Страница 39: ...WITCH HIGH LIMIT COMMISSIONING THE BOILER WATER HEATER UNIT CYCLED MIN OF 15 TIMES CUSTOMER INSTRUCTED ALL COVERS REPLACED CUSTOMER GIVEN MANUAL TARGET TEMP SET PER CUSTOMER COMMISSIONED BY __________...

Страница 40: ...www rbiwaterheaters com 260 North Elm Street 7555 Tranmere Drive Westfield MA 01085 Mississauga Ontario L5S 1L4 Canada Phone 413 568 9571 Phone 905 670 5888 Fax 413 568 9613 Fax 905 670 5782...

Отзывы: