Figure 34: Fixed Mounting Bracket
5.1
Options
Options are those items that are factory installed and must be
ordered with base model units
ISO Calibration Certificate, based on NIST/DKD certified
probes (GPR: XXXGPCERT, GPS: XXXGPSCERT)
Air/water-cooled housing (...W)
5.1.1
Air/Water-cooled Housing (GPR/GPS)
The air/water-cooled housing option allows the sensor to be used in
ambient temperatures up to 120°C (250°F) for air-cooled and 177°C
(350°F) for water-cooled. It is supplied with two 1/8” NPT brass
fittings. Air flow should be 25°C (77°F) at 2.8 liters/sec (0.74
gallon/sec) with a pressure drop across the housing of 0.63 kg/cm²
(9 PSI). Water flow should be approximately 2 liters (0.5 gallons) per
minute. Water temperature should be 10-27°C (50-80°F) for efficient
cooling. Using chilled water below 10°C (50°F) is not recommended.
To avoid condensation, it is recommended to use the Air Purge
Collar with the Water Cooled Housing.