Americas Tel: + 1 613 2709990
4. Open the terminal block enclosure. Wire the Mains cable into the terminal block. Provision
has been made for this and identified as the E (Earth), L1 (Live switched), L2 (Live
permanent) and N (Neutral) terminals. There are two pairs of contacts for each of these
to facilitate a mains cable that can be looped in and out of the unit, in non LL versions an
identical terminal block is also available at the other end of the luminaire
t
o allow the unit
to be through wired. The L2 terminals on a standard unit is not electrically connected
but allows them to be used on the same circuits as
emergency luminaires.
5. Installer should earth the unit separately – an internal and external earth point are
provided as standard at each end of the luminaire
6.
Connect wires to mains supply.
7.
If the unit is opened for any reason, disconnect mains –
On emergency luminaires
there may be more than one mains supply
8.
All WARRIOR luminaires have terminal blocks suitable for looping at least 4mm2
cable, only one cable should be connected to each terminal block connection
9.
The battery fuse is located in the compartment that contains the battery, the fuse is
disconnected after final manufacturing testing. When installing the linear the battery
fuse will need to be reconnected and the unit charged for 24 hours and then
discharged (repeated 3 times) to bring the battery up to peak capacity. (Unless an
‘EMX’ intelligent emergency variant – see notes below)
10. If a 4 core cable is used on emergency luminaires – L1, L2, N and E the link cable
at the frontof the terminal block between L1 and L2 should be removed
11. During emergency operation the light output and duration will be determined by the
variant purchased
12. Once wiring is complete replace terminal enclosure covers. Ensure gasket is located
neatly in channel and no wires are trapped between cover and body. Tighten screws
to 3Nm.