drain is inspected and ensure that condensate is
being directed to appropriate condensate treat-
ment system or drain, as required by local codes.
3. Check that area is free from combustible mate-
rials, gasoline, and other flammable vapors and
liquids.
4. Check for and remove any obstruction to the flow
of combustion or ventilation air to boiler.
5. Follow pre-start-up check in the Start-up section.
6. Check flame strength signal as noted on display.
Remove and visually inspect hot surface igniter
and sensor for damage, cracking or debris build-
up.
7. Check operation of safety devices. Refer to manu-
facturers’ instructions.
8. Follow oil-lubricating instructions on pump (if
re-quired). Over-oiling will damage pump. Water-
lubricated circulators do not need oiling.
9. To avoid potential of severe burn, DO NOT REST
HANDS ON OR GRASP PIPES. Use a light touch;
return piping will heat up quickly.
10. Check blower and blower motor
11. Check for piping leaks around pumps, relief valves
and other fittings. Repair, if found. DO NOT use
petroleum-based stop-leak.
Periodically
1. Check relief valve. Refer to manufacturer’s instruc-
tions on valve.
2. Test low water cut-off (if equipped). Refer to man-
ufacturer’s instructions.
Preventive Maintenance
Schedule
The following procedures are recommended and are
good practice for all XVers installations.
Daily
1. Check gauges, monitors and indicators.
2. Check instrument and equipment settings.
(See “Post Start-Up Check” in the I&O Manual.)
MAINTENANCE
Suggested Minimum
Maintenance Schedule
Regular service by a qualified service agency and
maintenance must be performed to ensure maximum
operating efficiency.
Maintenance as outlined below may be performed by
the owner.
Daily
1. Check that the area where the boiler is installed
is free from combustible materials, gasoline, and
other flammable vapors and liquids.
2. Check for and remove any obstruction to the flow
of combustion or ventilation air to boiler.
Monthly
1. Check for piping leaks around pumps, mixing
valves, relief valves, and other fittings. If found,
repair at once. DO NOT use petroleum-based
stop-leak compounds.
2. Visually inspect venting system for proper func-
tion, deterioration or leakage.
3. Visually inspect for proper operation of the con-
densate drains in the venting, and the internal
condensate trap. Clean trap as necessary. If leaks
are observed, repair at once.
4. Check air vents for leakage.
Yearly (Beginning Of Each Heating
Season)
Schedule annual service call by qualified service
agency.
1. Visually check top of vent for soot. Call service
person to clean. Some sediment at bottom of vent
is normal.
2. Visually inspect venting system for proper function,
deterioration or leakage. Ensure that condensate