55
9. MAINTENANCE
9.1. Suggested Minimum
Maintenance Schedule
Regular service by a qualified service agency and
maintenance must be performed to ensure maximum
operating efficiency.
Daily and monthly maintenance as outlined below may be
performed by onsite maintenance staff.
9.1.1. Daily
1. Check that the area where the heater is installed is
free from combustible materials, gasoline, and other
flammable vapors and liquids.
2. Check for and remove any obstruction to the flow of
combustion or ventilation air to heater.
9.1.2. Monthly
1. Check for piping leaks around pumps, mixing valves,
relief valves, and other fittings. If found, repair at
once. DO NOT use petroleum-based stop-leak
compounds.
2. Visually inspect venting system for proper function,
deterioration or leakage.
3. Visually inspect for proper operation of the
condensate drain in the venting. If leaks are observed
repair at once.
4. Check air vents for leakage.
9.1.3. Yearly (Beginning of each Heating
Season)
Schedule annual service by qualified service agency.
1. Visually check top of vent for soot. Call service
person to clean. Some sediment at bottom of vent
is normal.
2. Visually inspect venting system for proper function,
deterioration or leakage. Ensure that condensate
drain is inspected and ensure that condensate is
being directed to appropriate condensate treatment
system or drain, as required by local codes.
3. Check that area is free from combustible materials,
gasoline, and other flammable vapors and liquids.
4. Check air filter and replace as necessary.
5. Follow pre-start-up check in the Start-up section.
6. Check flame strength signal as noted on display
Remove and visually inspect hot surface igniter and
sensor for damage, cracking or debris build-up.
7. Check operation of safety devices. Refer to
manufacturer’s instructions.
Water Sensor / Outdoor Sensor
Water Temperature
Resistance (ohms)
32°F (0°C)
32550
41°F (5°C)
25340
50°F (10°C)
19870
59°F (15°C)
15700
68°F (20°C)
12490
77°F (25°C)
10000
86°F (30°C)
8059
95°F (35°C)
6535
104°F (40°C)
5330
113°F (45°C)
4372
122°F (50°C)
3605
131°F (55°C)
2989
140°F (60°C)
2490
149°F (65°C)
2084
158°F (70°C)
1753
167°F (75°C)
1481
176°F (80°C)
1256
185°F (85°C)
1070
194°F (90°C)
915
203°F (95°C)
786
212°F (100°C)
667
8.4.3. Sensor Resistance Values
Table AC. Approximate Sensor Resistance Values
Содержание Xtherm 1005A
Страница 62: ...62...
Страница 63: ...63...
Страница 64: ...www raypak com Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 Fax 805 278 5468 Litho in U S A...