15
Tank/
Return
Temp
(°F / °C)
Model 1005A
Model 1505A
Model 2005A
Supply
Temp
1
(°F / °C)
Min. Tubing Size
2
Supply
Temp
1
(°F / °C)
Min. Tubing Size
2
Supply
Temp
1
(°F / °C)
Min. Tubing Size
2
<80' equiv.
80-200'
equiv.
<80' equiv.
80-200'
equiv.
<80' equiv.
80-200'
equiv.
60 (15)
147 (64)
2" NPT
2-1/2" NPT
147 (64)
2" NPT
2-1/2" NPT
154 (68)
2" NPT
2-1/2" NPT
80 (27)
147 (64)
2" NPT
2-1/2" NPT
147 (64)
2" NPT
2-1/2" NPT
154 (68)
2-1/2" NPT
3" NPT
100 (38)
147 (64)
2-1/2" NPT
3" NPT
147 (64)
2-1/2" NPT
3" NPT
154 (68)
2-1/2" NPT
3" NPT
120 (49)
145 (63)
2-1/2" NPT
3" NPT
158 (70)
2-1/2" NPT
3" NPT
170 (77)
2-1/2" NPT
3" NPT
140 (60)
165 (74)
2-1/2" NPT
3" NPT
178 (81)
2-1/2" NPT
3" NPT
190 (88)
2-1/2" NPT
3" NPT
160 (71)
185 (85)
2-1/2" NPT
3" NPT
198 (92)
2-1/2" NPT
3" NPT
210 (99)
2-1/2" NPT
3" NPT
1
Approximate high fire heater outlet temperature based on the standard heater pump and the recommended connecting pipe size.
2
Minimum pipe size based on total equivalent feet of supply and return piping between the system loop and heater, not to exceed 2.7 ft of head at 70 gpm.
Table H.
Boiler Temperatures and Minimum Pipe Size at Varying Return Temperatures
System Return Temperature
50°F (°C)
70°F (°C)
90°F (°C)
110°F (°C)
120°F (°C)
Model Low Fire
(gpm/lpm)
High Fire
(gpm/lpm)
Low Fire
(gpm/lpm)
High Fire
(gpm/lpm)
Low Fire
(gpm/lpm)
High Fire
(gpm/lpm)
Low Fire
(gpm/lpm)
High Fire
(gpm/lpm)
Low Fire
(gpm/lpm)
High Fire
(gpm/lpm)
1005A
4 (15)
21 (79)
5 (19)
27 (102)
8 (32)
38 (144)
20 (76)
61 (231)
70 (265)* 87 (329)** 70 (265)* 87 (329)**
1505A
6 (23)
31 (117)
8 (30)
39 (148)
12 (45)
53 (201)
29 (110) 70 (265)* 82 (310)** 70 (265)* 113 (428)** 70 (265)* 113 (428)**
2005A
7 (27)
38 (143)
10 (38)
48 (182)
16 (61)
63 (238)
37 (140) 70 (265)* 91 (344)** 70 (265)* 116 (439)** 70 (265)* 116 (439)**
* Flow rates are shown for standard models. Pipe size selection not to exceed 2.7 ft hd pressure drop at 70 gpm (265 lpm)
** For High Temp/Process unit utilizing a single injector pump, pipe sizing to be based on the following:
H7-1005A - 87 gpm @ 3.5 ft (329 lpm @ 1 m) hd pressure drop
H7-1505A - 113 gpm @ 7.6 ft (428 lpm @ 2.3 m) hd pressure drop
H7-2005A - 116 gpm @ 8 ft (439 lpm @ 2.4 m) hd pressure drop
NOTE: System flow must be greater than boiler flow at all time for proper operation.
Table I.
Injection Flow Rates vs Return Water Temperatures
3.9.6.
Applications and Modes - Primary/
Secondary Piping
The VERSA IC Control system is designed for a wide range
of applications. The installer/design engineer should refer
to the following Modes to determine which best fits the
intended application and functionality for the unit being
installed. Type H models of XTherm have three modes
available to them to address the various applications the
units can be applied to. Type WH units will only have the
WH configuration available to them for use with potable
water applications when directly connected to a hot water
storage tank. Type P units will only have the P configuration
available. For detailed information on the VERSA IC control
system, see the VERSA IC manual (5000.72). This manual
can be found in the document library at www.raypak.com.
Mode 1 (Type H Units Only)
This mode selection is for hydronic heating systems with
single or multiple heaters (Maximum 4 heaters) in primary/
secondary piping configuration with or without Outdoor
Air Reset (S4).
See
Figure 16
and
Figure 17
.
Sensor
Name
Installed at
Applies to Mode
Factory Field
S1
Inlet
X
All
S2
Outlet
X
All
S3
System
X
All
S4
Outdoor Air
X
H w/ Outdoor Reset
S5
Indirect
DHW
X
H mode 2
X
H mode 3
S6
Indirect
Supply
X
H mode 3
Poolstat
X
P
Table J.
Sensor Usage