28
Cold Water Run Troubleshooting Guide
Step 9
Step 8
Step 10
Step 1
Step 2
Step 3
Step 4
Step 5
Step 6
Step 7
Is there a Call For
Heat at the heater?
Is the inverter in the
cold run controller powered?
Replace inverter or
correct wiring
Does the cold run inverter output 12VDC from PCS to the
reset switch, Pin S1 and pin FS of the cold run circuit board?
Replace circuit board
Are the terminals 1-2 of TB3
connected to N.O. contacts of
DPDT relay?
Does cold run terminal AL0
relay coil receive 24VAC
from MC on circuit board?
Are terminals 1-4 of TB3 correctly
connected back to the heater?
Call our Technical Service Department
1-805-278-5300
NO
Verify 120VAC* or 230VAC*
from separate circuit breaker
YES
Does TB1 of cold run
controller have 120VAC*
or 230VAC*?
Heater is in standby mode
Correct Wiring
YES
NO
NO
YES
YES
NO
NO
NO
YES
YES
NO
The unit is okay
YES
NO
YES
Correct wiring
Is the injector pump
modulating after 2-1/2
minutes?
NO
Correct wiring
YES
Is the heater tripping the high
limit?
YES
NO
Verify pump is rotating in proper
direction
Pump must decrease
RPM’s on decreasing 0-
10VDC signal
YES
Correct 3 phase pump wiring
NO
Is 24VAC present at CFH
connection on cold run circuit
board?
Check and verify 24VAC between pin 4 and 5
of TB3 in cold run controller and correct.
Is 0-10VDC present at
connection FR of cold run circuit
board and pin 0 of the inverter?
NO
Replace cold run circuit board
or correct wiring.
YES
Does cold run circuit board lock-out on
“Sensor out of Range”?
NO
YES
Is sensor resistance correct?
YES
NO
Replace sensor
Is the system
water temperature
below 0ºF?
NO
YES
*NOTE:
See wiring diagrams
for proper supply voltage based
on inverter used on heater.
Содержание Raypak Delta Limited WH1-399B
Страница 14: ...14 Wiring Diagrams Cold Water Start ...
Страница 19: ...19 CWS CONTROL BOX ASSY SEE PAGE 16 FOR HEATER INTERFACE WIRING SEE PAGE 17 Wiring Diagram Multiple Boiler ...
Страница 29: ...29 Wiring Diagrams Cold Water Run SEE PAGE 17 ...
Страница 31: ...31 7 ILLUSTRATED PARTS LISTS Cold Water Start Manufactured from 2006 through current ...
Страница 32: ...32 1 M 8 M Cold Water Start ...
Страница 33: ...33 Cold Water Start Multiple Boiler Interlock ...
Страница 34: ...34 NOTE Sizing is specific to the application ...
Страница 36: ...36 9 M 4 M RAYTHERM MODELS 2100 4001 ONLY 1 H 5 M 6 M 7 M 8 M 10 M 12 M 11 M 4 M 2 M 1 M Cold Water Run ...
Страница 37: ...37 NOTE Sizing is specific to the application ...
Страница 38: ...38 NOTES ...
Страница 39: ...39 NOTES ...