16
4. COLD WATER START-
MULTIPLE BOILER
(Maximum 4 Boilers)
Materials Included
• 1 Cold Start Control Box
• 1 Multi-Boiler Interlock Box
• 1 Water Sensor & Well
• 1 Three-way Diverting Valve assembly with Actuator
NOTE:
Flanges, bolts and gaskets for flanged valves
supplied by others.
Installation
Mounting the Control Boxes
Cold Start Control and Multi-Boiler Interlock should be
mounted in such a manner as to allow for easy access for
wiring of the boiler interlock connections.
Installing the Temperature Sensor
Temperature sensor to be installed in a drywell with thermal
paste at the location indicated in the diagram on page 21
to ensure proper operation of the control system. Installer
must ensure the drywell extends at least 2 inches into the
water flow path. Sensor wiring must be run in separate
conduit from line voltage and should be a minimum of 18
AWG shielded cable. Refer to "Wiring Diagram" on page
19 for wiring information.
Installing the Three-way Valve
Install three-way diverting valve into common boiler piping
manifold as shown in the diagram on page 18. Boiler
common outlets to be connected at port AB. Discharge to
system from port A with bypass port being port B. Common
pipe sizing may be larger than three-way valve port
connections requiring the use of increasers for installation
(see
Table B
for valve sizing). It is recommended that three-
way valve be installed as near the main system piping as
is feasible. Route control wiring in separate conduit to the
Cold Water Start control box and wire as shown in the
diagram on page 19.
Connecting Power to the Controller
Installer to provide a dedicated 120V circuit with local
disconnect to the Cold Water Start Control. Refer to wiring
Figure 9
for detailed instruction.
Connecting the CWS Control to the
Multi-Boiler Interlock Box
Installer to provide four 18AWG stranded wires between
pins 7-10 on the Cold Start Control and 7-10 on the Multi-
Boiler Interlock as shown in "Wiring Diagram" on page
19. Do not use solid-core wire when wiring any portion
of the Cold Start Multi-Boiler system.
Connecting the Boiler to the CWS
Multi-Boiler Interlock
Installer to provide five 18AWG stranded wires between
each boiler and Multi-Boiler Interlock box. Wiring to be
run in separate conduit from line voltage to ensure proper
operation. Refer to "Wiring Diagram" on page 19 for
connection points depending on Raypak product being
used.
Connecting the Actuator
The 4-inch valve is shipped loose, and must be field wired.
Connect the actuator leads to the Cold Water Start control
panel, as indicated in the wiring diagram on page 14.
The actuator for the 4" valves rotates opposite to the
direction of the smaller actuators.
Actuator to Valve Orientation
Install the actuator so that the tail is pointing horizontally
as shown in "Valve Orientation (Actuator)" on page 17 is
pointing down. DO NOT mount it so that the tail is pointing
Total Load
(MBTU)
Valve Size
Minimum
Pipe Size
in. (mm)
Cv
Flow Rate
GPM (lpm)
Valve
Pressure Drop
Ft. hd. (kPa)
∆T @ Max
Size
º
F (
º
C)
∆T @ Min.
Size
º
F (
º
C)
Order No.
600-1000
2" NPT
2 (51)
57
70 (265)
3.5 (10.5)
22 (12.2)
14.4 (8.0)
012228
1001-1800
2.5" NPT
2.5 (63)
74
100 (379)
4.2 (12.6)
30.2 (16.8)
16.8 (9.3)
012229
1801-2600
2.5" NPT
3 (76)
100
150 (568)
5.2 (15.5)
29.1 (16.2) 20.1 (11.2)
012230
2601-4000
4" FLG*
4 (102)
152
220 (833)
4.8 (14.3)
30.5 (17.1) 22.9 12.7)
012231
4001-6000
4" FLG*
4 (102)
254
330 (1249)
3.9 (11.7)
30.5 (17.1) 20.3 (11.3)
012232
6001-8000
4" FLG*
6 (152)
327
440 (1666)
4.2 (12.2)
30.5 (17.1) 22.5 (12.5)
012233
Standard boiler pump options offered by Raypak may
NOT
be appropriate for these applications.
*CAUTION:
Approved for closed-loop systems only.
Table B. Valve Sizing Chart
Содержание Raypak Delta Limited WH1-399B
Страница 14: ...14 Wiring Diagrams Cold Water Start ...
Страница 19: ...19 CWS CONTROL BOX ASSY SEE PAGE 16 FOR HEATER INTERFACE WIRING SEE PAGE 17 Wiring Diagram Multiple Boiler ...
Страница 29: ...29 Wiring Diagrams Cold Water Run SEE PAGE 17 ...
Страница 31: ...31 7 ILLUSTRATED PARTS LISTS Cold Water Start Manufactured from 2006 through current ...
Страница 32: ...32 1 M 8 M Cold Water Start ...
Страница 33: ...33 Cold Water Start Multiple Boiler Interlock ...
Страница 34: ...34 NOTE Sizing is specific to the application ...
Страница 36: ...36 9 M 4 M RAYTHERM MODELS 2100 4001 ONLY 1 H 5 M 6 M 7 M 8 M 10 M 12 M 11 M 4 M 2 M 1 M Cold Water Run ...
Страница 37: ...37 NOTE Sizing is specific to the application ...
Страница 38: ...38 NOTES ...
Страница 39: ...39 NOTES ...