PROPANE SUPPLY

PRESSURE TEST POINT

MODELS 502CD-2342CD

Figure 4.  FlexGas Gas Pressure Measurement Locations

ADJUSTMENT SCREW

MODELS: 302CD - 902CD

MODELS: 992CD - 2342CD

GAS VALVE 

OUTLET TAP

GAS VALVE 

OUTLET TAP

Start-Up

For Your Safety

A

WARNING:

  If  you  do  not  follow these  instructions 

exactly, a fire or explosion may result causing property 

damage, personal injury or loss of life.

This appliance has a hot surface igniter(s). It is equipped 

with  an  ignition  device(s)  which  automatically  lights  the 

burners. Do not try to light the burners by hand.
BEFORE  OPERATING,  smell  all  around  the  appliance 

area  for  gas.  Be  sure  to  smell  near  the  floor  because 

some gas is heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS:

•  Do not try to light any appliance.
•  Do not touch any electrical switch; do not use any 

telephone in your building.

•  Immediately call your gas supplier from a neighbor’s 

telephone. Follow the gas supplier’s instructions.

•  If you cannot reach your gas supplier, call the fire 

department.

•  Use only your hand to push in or turn the gas control 

knob.  Never  use  tools.  If  the  knob  will  not  turn  by 

hand, do not try to repair it, call a qualified service 

technician. Forced or attempted repair may result in 

a fire or explosion.

•  Do not use this appliance if any part has been under 

water, immediately call a qualified service technician 

to inspect the appliance and to replace any part of 

the  control  system  and  any  gas  control  which  has 

been under water.

•  Check around unit for debris and remove combustible 

products, i.e. gasoline, etc.

Pre Start-up Check

1.  Verify heater is filled with water.
2.  Check  system  piping  for  leaks.  If  found,  repair 

immediately.

3.  Vent air from system. Air in system can interfere with 

water circulation.

4.  Purge air from gas lines up to FlexGas gas train.

Initial Start-up
Tools Needed:

•  (1) 12-0-12, 24" scale U-tube manometer
•  (4) 6-0-6, 12" scale U-tube manometers (min.)
•  (1) Screwdriver
•  (1) Multi-meter
•  (1) 3/16" Allen wrench

NOTE:

 Digital manometers are not recommended.

APPROVED 

UNCONTROLLED DOCUMENT IF PRINTED 

 

Содержание FlexGas Hi Delta H 302CD-2342CD

Страница 1: ...or fire WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phon...

Страница 2: ...First paragraph text revised on page 4 Bleeds Vents paragraph text revised on page 5 Revised Figure 4 on page 6 Safety Inspection point 7 text revised on page 8 Updated gas supply pressures from 5 0 t...

Страница 3: ...ngs and Certifications 4 Component Locations 5 Installation Codes 5 Gas Supply 5 Bleed Vents 6 Start up 7 FlexGas System Start Up 8 FlexGas Operation 9 Wiring Diagram 10 Illustrated Parts List 11 APPR...

Страница 4: ...Raypak product We hope you will be satisfied with the high quality and durability of our equipment Model Identification The model identification number and heater serial number are found on the heater...

Страница 5: ...National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition NFGC National Electrical Code ANSI NFPA 70 latest edition NEC For Canada only CAN CGA B149 Installation Code B149 1 and CSA C22 1 C E C Part 1...

Страница 6: ...tor s on the Hi Delta heater are nominally preset at 3 5 in WC The pressure regulator on the FlexGas propane system is nominally set at 2 2 0 1 in WC This can be verified by measuring the propane gas...

Страница 7: ...the gas supplier s instructions If you cannot reach your gas supplier call the fire department Use only your hand to push in or turn the gas control knob Never use tools If the knob will not turn by h...

Страница 8: ...control operation Ensure the manual valve on the natural gas supply is open and the manual valve on the propane supply is closed 2 Turn on the unit wait 15 seconds and the igniter should glow Look in...

Страница 9: ...ront control panel 2 Turn FlexGas key to OFF 3 Close PRO manual valve 4 Open NAT manual valve 5 Turn FlexGas key to NAT 6 Turn the boiler on Safety Inspection 1 Check all thermostats and high limit se...

Страница 10: ...10 Figure 5 FlexGas Control Panel Figure 6 Wiring Diagram Wiring Diagram APPROVED UNCONTROLLED DOCUMENT IF PRINTED...

Страница 11: ...11 1 S 2 G 6 G 5 G 4 G 1 S 1 G 1 S 7 G 8 G 1 G 1 C ILLUSTRATED PARTS LIST APPROVED UNCONTROLLED DOCUMENT IF PRINTED...

Страница 12: ...0F 4 G MANUAL GAS VALVE NAT 011945F 011945F 007665F 007665F 5 G MANUAL GAS VALVE PRO 011944F 011945F 011945F 011945F F 8 4 9 1 1 0 F 7 4 9 1 1 0 F 7 4 9 1 1 0 F 6 4 9 1 1 0 E V L A V R O T A L U G E R...

Страница 13: ...Raypak Inc 2151 Eastman Avenue Oxnard CA 93030 805 278 5300 www raypak com ISO 9001 REGISTERED QUALITY MANAGEMENT SYSTEM www raypak com APPROVED UNCONTROLLED DOCUMENT IF PRINTED...

Отзывы: