40
e) A venting system shall terminate at least 3 feet
above any forced air inlet located within 10 feet.
f) Adjacent brick or masonry surfaces must be pro-
tected with a rust-resistant sheet metal plate.
g) Multiple Outdoor Vent installations require a four
(4) feet clearance between vent caps.
The Stainless Steel non-restricted vent cap must
be furnished by the boiler manufacturer in accor-
dance with its listing.
The outdoor vent terminal must be installed in a hori-
zontal position to prevent recirculation of flue products.
The vent cap must be mounted directly on the vent
pipe of the boiler.
NOTE:
Condensate can freeze on the vent cap.
Frozen condensate on the vent cap can result in a
blocked flue condition.
CONDENSATE DRAIN
The Condensing Heat Exchanger (CHX) can generate
up to 1 (one) gallon per hour (gph) of condensate for
every 100,000 BTUH. The maximum condensation
rate for the ADB 751 is 7.5 gph, the ADB 1001 is 10
gph, and the ADB 1501 is 15 gph.
NOTE:
In areas of high winds (alleyways, air
handlers, etc.), a downward 90° - elbow must be
mounted on the combustion air inlet to prevent any
air flow fluctuation.
WARNING:
All condensation should be disposed of
according to local, county, state, and federal laws.
Refer to NFGC, section 7.9, for additional
information.
Fig. 29: Condensate Trap Alignment
Содержание 751
Страница 2: ...2...
Страница 6: ...6 Component Locations Fig 1 Component Locations...
Страница 14: ...14 Fig 4 Single Boiler Primary Secondary Piping Fig 5 Single Boiler Primary Secondary Piping with CHX...
Страница 15: ...15 Fig 6 Dual Boiler Piping Fig 7 Dual Boiler Piping with CHX...
Страница 20: ...20 Fig 13 Single Boiler Pool Application Fig 14 Single Boiler Pool Application with CHX...
Страница 44: ...44 Figure L 2 WIRING DIAGRAM WIRING DIAGRAM...