30
WARNING:
Vent connectors serving any other
appliances shall not be connected into any portion of
mechanical draft systems operating under a positive
pressure. If an MVB heater is installed to replace an
existing heater, the vent system MUST be verified to
be of the correct size and of Category IV vent mate-
rial construction. If it is NOT, it MUST be replaced.
NOTE:
For extractor sizing, typical CO
2
levels are
9.0% for natural gas and 10.2% for propane gas and
flue temperature of 300°F, at 100% firing rate. meas-
ured at test port 12" above the flue collar.
* NOTE: Data for 100% firing rate.
Table L: Typical Vent Pressure and Volume
of Flue Products
Fig. 30: Typical Common Venting
Model
Vent
Size (in.)
Vent
Pressure
(in. WC)
Volume of
Flue Products
(CFM)
503A
0.1
160
753A
0.2
240
1003A
6
0.3
320
1253A
0.2
400
1503A
0.3
480
1753A
0.4
560
2003A
8
0.5
640
Fig. 29: Vertical Venting
8’ OR LESS