34
Resets board to factory default settings.
Resets faults in the History File.
Change from Fahrenheit to Celsius.
SPA setpoint maximum adjustment.
POOL setpoint maximum adjustment.
SETdef – Default Settings
Refer to step one above to access the program
screen.
SETdef
should appear on the screen. If not,
press the
Mode
button until
SETdef
appears on the
digital display. Press and hold both UP and DOWN
buttons for 5-7 seconds until 3 dashes (---) appear.
This operation resets the operating program to its fac-
tory default values. Both the POOL and SPA setpoints
will revert to 65°F (18.5°C) and both POOL and SPA
maximum temperature settings will be 104°F (40.0°C).
Once this is done, reassemble the control panel.
RESfl – Reset Fault History
Refer to step one above to access the program
screen. Press the
Mode
button until
RESfl
appears
on the digital display. Press and hold both UP and
DOWN buttons for 5-7 seconds until 2 dashes (--)
appear. This operation resets the Fault History file to
“0” and clears all the stored faults. Once this is done,
reassemble the control panel.
Program Button
1) To access the program screen, press the Mode
button until the display reads
OFF
. Remove the
four screws holding the control cover on. Swing
control panel down so the back side of the board
is visible (see page 31). Locate the Program Mode
button as shown in the figure on page 33. Press
the program button (5-7 seconds) until
SETdef
appears on the digital display. Release the pro-
gram button.
2) Press the
Mode
button sequentially until the
desired program event is reached. There are 5 dif-
ferent events that can be programmed. They
appear in the sequence listed below:
F/Cfff – Fahrenheit to Celsius
Refer to step one above to access the program
screen. Press the
Mode
button until
F/Cfff
appears on
the digital display. The digital display is capable of dis-
playing Celsius as well as Fahrenheit temperatures.
The UP or DOWN buttons will select “F” or “C” on the
temperature display. Choose the desired temperature
scale. Once this is done, reassemble the control panel.
SETspa 104 – SPA Set Point Maximum Adjustment
Refer to step one above to access the program
screen. Press the
Mode
button until
SETspa 104
appears on the digital display. Using the UP and
DOWN buttons will change the Maximum Temperature
Setting to your desired value. The control can be set
for a maximum of 107°F. Once this is done, reassem-
ble the control panel.
SETpool 104 – POOL Set Point Maximum Adjustment
Refer to step one above access into the program
screen. Press the
Mode
button until
SETpool 104
appears on the digital display. Using the UP and
DOWN buttons will change the Maximum Temperature
Setting to your desired value. The control can be set
for a maximum of 107°F. Once this is done, reassem-
ble the control panel.