19
Gas Supply Connection
The heater must be isolated from the gas supply pip-
ing system by closing the manual shut-off valve during
any pressure testing of the gas supply piping system
at test pressures equal to or less than 1/2 psi (3.45
kPa). Relieve test pressure in the gas supply line prior
to reconnecting the heater and its manual shut-off
valve to the gas supply line.
FAILURE TO FOLLOW
THIS PROCEDURE MAY DAMAGE THE GAS
VALVES
. Over pressurized gas valves are not cov-
ered by warranty. The heater and its gas connections
shall be leak-tested before placing the appliance in
operation. Use soapy water for leak test. DO NOT use
an open flame.
CAUTION:
The heater must be disconnected from
the gas supply during any pressure testing of the gas
supply system at test pressures in excess of 1/2 psi
(3.45 kPa).
Fig. 14: Gas Supply Connection
CAUTION:
Do not use Teflon tape on gas line pipe
thread. A pipe compound rated for use with natural
and propane gases is recommended. Apply
sparingly only on male pipe ends, leaving the two
end threads bare.
Table I: Maximum Equivalent Pipe Length
Natural gas – 1,000 BTU per ft
3
, .60 specific gravity at 0.5 in. WC pressure drop
Propane gas – 2,500 BTU per ft
3
, 1.53 specific gravity at 0.6 in. WC pressure drop
Model
No.
3/4”
1”
1-1/4”
1-1/2”
2”
2-1/2”
3”
4”
N
P
N
P
N
P
N
P
N
P
N
P
N
P
N
P
399B
15
25
60
100
260
250
499B
65
150
130
360
500
649B
45
100
95
250
340
749B
35
80
75
180
260
600
899B
20
45
45
110
150
360
400
989B
120
300
300
1259B
75
180
170
325
560
1529B
50
120
125
250
400
1799B
40
100
100
225
340
1999B
30
80
75
175
260
2069B
30
80
75
175
260
2339B
20
55
55
135
160
400
600
regulator must be installed to reduce the gas supply
pressure to a maximum of 10.5 in. WC for natural gas
and 13.0 in. WC for propane gas. The regulator should
be placed a minimum distance of 10 times the pipe
diameter up-stream of the heater gas controls. Refer
to Table I for maximum pipe lengths.