5973132-10

8.  If "

VENTILATION (N.O)

" was selected, the distance the door is to open needs to be set. The display should read "

OPEN

   VENT TIME

" , the distance is determined by the number of seconds the door will open. This is done in 1 second intervals

     from 3 to 30 seconds. Use the open and close buttons on the board to set the time. Press the

stop button

 to

continue

 to

     the next option.

9.  If "

FIRE STATION (N.O)

" was selected, the timer to close needs to be set. "

FS: TIME TO CLOSE

" will display. This is

    done in 10 second intervals from 60 to 900 seconds. Use the open and close buttons on the board to set the time. Press
    the

stop button

 to

continue

to the next option.

10.  "

AUX INPUT 2 TYPE

" will display, this is used for a second auxiliary contact to open or close the door.  Repeat steps 7

       through 9 if a second auxiliary contact is required.

11. "

MIDWAY STOP

", this allows the door to stop midway through the open cycle. If a midway stop is not required, select

      "

OFF

". If the midway stop is required, select "

ON

". Press the

stop button

 to

continue

.

12. If a midway stop is requried, "

MIDWAY TIME

" will display, the distance is determined by the number of seconds the door

      will open. This is done in 1 second intervals from 3 to 30 seconds. Use the open and close buttons on the board to set
      the time. Press the

stop button

 to

continue

to the next option.

13. If there is no auxiliary board, then programming the logic board is complete. If there is an auxiliary board, then continue
      through steps 14 - 16.

14. "

LIGHT ON TIME

" will display, this is used to turn on a light and shut off a light after a determined amount of time. This is

      done in 10 second intervals from 10 to 240 seconds. Use the open and close buttons on the board to set the time. Press
      the

stop button

 to

continue

to the next option.

15. "

CLOSE WARNING LIGHT

" will display, this is used to activate a warning light a determined amount of time before the

       door times out and closes. If no warning light is required, select "

OFF

". If a warning light is required, select "

ON

".

       Press the

stop button

 to

continue

.

16. If a warning light is "

ON

", "

WARNING TIME

" will display. The time is set in 1 second intervals from 3 seconds to 10

      seconds. If there is a timer to close, the close warning light time must be set lower than the timer to close time. Use the
      open and close buttons on the board to set the time. Press the

stop button

 to

end

 programing.

SPECIAL PROGRAMMING INSTRUCTIONS

The maximum run timer and reverse limits option are factory set and you are not required to set these in the initial set up.
However, in the event that you need to modify either one of these options, use the instructions below.

Maximum Run Timer

To help prevent damage to the operator, it is supplied with a maximum run timer (factory set at 40 seconds) with a maximum
run time of 120 seconds.

To change factory default, press and hold the stop button and program button until you enter the programing mode. Once in

the program, release both buttons. Then press and hold the program button for approximately 30 seconds, or until an
asterisk shows up on the screen. Then release the program button. You can now use the stop button to advance through the
program until you see the maximum run timer. Use the open and close buttons to adjust the time. Once finished, use the
stop button to advance the rest of the way through the program.

Reverse Limits

For ease of changing the operator position, it has been supplied with a “reverse limits” option. If you need to switch the open
and close limit switches, press and hold the stop button and program button until you enter the programming mode. Once in
the program, release both buttons. Then press and hold the program button for approximately 30 seconds, or until an
asterisk shows up on the screen. Then release the program button. You can now use the stop button to advance through the

program until you see the reverse limits option. Use the open and close buttons to select “yes” or “no” (factory default is “no”).
Once finished, use the stop button to advance the rest of the way through the program.

Содержание COH

Страница 1: ...Chain Hoist Special Application Jackshaft IMPORTANT PLEASE READ THESE INSTRUCTIONS BEFORE STARTING INSTALLATION IT IS IMPORTANT THAT THIS OPERATOR BE INSTALLED CORRECTLY IN ORDER TO ACHIEVE SAFE AND...

Страница 2: ...y of the consumer and must be performed by an authorized Raynor Dealer This warranty extends only to the original purchaser This warranty is not transferable Raynor shall not be liable for any consequ...

Страница 3: ...s 9 Do not place hands in area of pulleys V belt sprockets chain or rotating shafts 10 Install warning placard on wall next to push button 11 Attach instruction booklet to wall near push button 12 Do...

Страница 4: ...ining the operator itself one drive and one driven sprocket one length of chain one control station and one package of small hardware Unpack carton being certain that all loose parts are removed befor...

Страница 5: ...est results Place small drive sprocket on proper side of operator shaft as shown in Fig 3 Remove base mounting plate from operator see Fig 3 and use as a template for drilling holes in wall then re in...

Страница 6: ...ator and set limit switches in this mode Once correct rotation has been established manually lower door to fully closed position Set close limit nut at desired position by depressing limit nut keeper...

Страница 7: ...ten the belleville springs See Fig 6 If additional tension is required add extra belleville springs to clutch assembly WARNING Do NOT over tension clutch Note The clutch is set loose at the factory an...

Страница 8: ...Power Connection Terminal Block 1 Terminal Block 2 High Voltage Wire Harness Connection LIGHT CCM NO1 SER C1NC1 NO2 C2NC2 ON OFF OPEN CLOSE ON OFF 24VDC 24VDC 24VAC 24VAC Terminal Block 3 24V DC Power...

Страница 9: ...sing RD or RC wiring photo eye s or edge must be selected even though they are not required Note The photo eye or an electric edge must be monitored 5 SENSOR 2 TYPE will display there are three option...

Страница 10: ...warning light is required select OFF If a warning light is required select ON Press the stop button to continue 16 If a warning light is ON WARNING TIME will display The time is set in 1 second inter...

Страница 11: ...r death 8 SAVE THESE INSTRUCTIONS OPERATING INSTRUCTIONS Operating the 3 Button Control Station 1 Press OPEN button The door should move in the open direction 2 Press STOP button The door should stop...

Страница 12: ...eset press reset button on outside of control box When overload trips it cuts power to the 24 volt control circuit only To reset open control box cover and press red reset button PERIODIC INSPECTION A...

Страница 13: ...ng Off Stop button pressed or NOT connected On Open button sending signal pressed Off Open button is not sending signal 2 Open D12 6 I Lock D24 7 I Lock D23 On Chain hoist interlock circuit is open ch...

Страница 14: ...ton to pause this countdown Sensor 1 activated This message will display anytime the board is not receiving a signal from the sensor 1 when close button is pressed Whether it is not connected activate...

Страница 15: ...minate stress on rollers and cables 1 Sunlight is blocking the receiving photo eye 2 Faulty photo eyes 1 Connect Operator to power source 2 Check voltage at L1 L2 for single phase and at L1 L2 L3 for...

Страница 16: ...oard Verify power consumption of the device s before installing You may have to power the device from an external power source using only the contacts of the device to activate the operator 3 The comm...

Страница 17: ...use the dry contacts of that relay to activate the device If more than 3 amps of power is being consumed through the auxiliary board then damage to the board may occur 2 There is a 14 pin connector o...

Страница 18: ...nger anger La Label el Door oor Safet Safety y La Label el Spring Spring Warning ning Tag ag Pu Push Button h Button Placa Placard Locate n Locate near Push Button Push Button Door oor Safet Safety y...

Отзывы: