CVS-21HA.rev.03
33
If the room temperature falls:
NOTE: Heater offset can be adjusted to a positive or negative value. When
positive, stage 3 operates at room temperatures below the set point as
illustrated. When negative, stage 3 may operate at room temperatures
above the set point.
When stage 3 is used for heating, stages 1 and 2 operate as described for
cooling. However stage 3 operates at room temperatures below the set
point, as described hereafter.
HEATING
If stage 3 is configured for heating, stages 1 and 2 operate as described
above (see preceding diagram).
H E AT IN G
S TA G E 3
•
At POINT 1: the stage 3 heating units turn on.
•
At POINT 2: the stage 3 heating units turn off.
If the room temperature rises: