Step 4:
Install the floor sensor (mandatory for floor sensing mode or room sensing mode with floor
temperature limiter). The floor sensor should be installed in a separate flexible conduit all the
way to the end, covering the end of the sensor, for easy replacement and to avoid possible signal
disturbance on the sensor. For best control performance, position the floor sensor between two
heating cables as close as possible to the top floor surface.
Do not position the floor sensor tip closer than 3 cm to the heating cable.
The floor sensor cable can be extended up to 100 m with a separate standard installation cable 2 x
1.5 mm
2
(230VAC).
Step 5:
Connect the electrical power supply, the sensor and the cold lead of the electrical floor
heating system to the Green Leaf according to the electrical diagram. If you connect heating cables
exceeding 13A for constant wattage or 10A for self-regulating cables you must use a contactor with
an integrated suppression device.
For the earth connection of the floor heating, you must use a separate earth terminal connection
block.