PowerPlus System 100-3-1U
INSTALLATION INSTRUCTION & OPERATION MANUAL
www.raycap.com
(
320-1398) QRC | Rev.A
•
© Raycap | All rights reserved.
Page 20 of 34
9.5
Initial Settings Menu:
Parallel Mode
System Units Selection
Cable Cross Section Selection
Cable Length Selection
Finish-Top Voltage Target Selection
Finish
•
The top level target is the final step of the initial settings menu. Next the system will display the
calculated cable resistance in
ohms
. It then starts the main parallel mode operation cycle.
Slot 1
Primary
Main Parallel
Mode Operation
Slot 1
Primary
Slot 2
Slot 2
Slot 3
Slot 3
9.4
Initial Settings Menu:
Parallel Mode
System Units Selection
Cable Cross Section Selection
Cable Length Selection
Top Voltage Target Selection
•
The next step is the ‘
Top Voltage Target
’ selection. The range of this parameter is from -60V to -54V
and could be selected by pressing the
‘UP’
and
‘DOWN’
buttons of the primary module in a step of
1V. The top voltage target is the minimum operational voltage threshold for the RRU and the default
value is -54V. Top voltage target value below -58V (-59V or -60V) could cause eventually RRU high
voltage alarms and is not recommended.
Up/Down +/- 1V
Slot 1
Slot 2
Slot 3