background image

The appliance can only be installed in a room which
meets the ventilation regulations in force. But, in any
event the room must have a permanent vent of minimum
free air area, see below.

IMPORTANT: THE LOUVRED AIR INTAKE AT THE
BOTTOM FRONT OF THIS APPLIANCE MUST BE
KEPT CLEAR OF ANY OBSTRUCTIONS

Detailed recommendations for air supply are given in the
Building Regulations, and in BS 5410: Part 1. The
following notes are intended to give general guidance.

1.  

Combustion and ventilation air supply to oil fired

appliance has to comply with the Building Regulations
and with BS 5410: Part 1. The air supply requirement for
oil fired appliances is 550mm

2

per kW of maximum rated

output above 5kW. These requirements are illustrated in
OFTEC Technical Book No.3.

2.  

The combustion air supply to open flued appliances

should normally be provided at high level into a room
where it will not cause discomfort by creating a cold
draught across the floor.

3.  

If combustion air is supplied through an under floor

duct the grilles at each end should be positioned in the
vertical plane to reduce the risk of blockage. Ducts should
be sized so as to reduce resistance to air flow.

4.

The ventilation requirement for kitchens in Part F of the

Building Regulations is for mechanical extract at the rate
of 60 litres per second or 30 litres per second if the fan is
incorporated in a cooker hood. 

Background ventilation is also required, either by
producing a constant mechanical extract rate of one air
change per hour or by having ventilation openings of not
less than 4000mm

2

.

5.

Extract fan should be positioned as far away from the

appliance as possible and should have a sufficient
dedicated air supply. To undertake a test the oil fired
appliance should be set in operation and the doors and
windows of the room containing it should be closed. The
extract fan should then be run at its maximum setting. The
oil fired appliance should be observed to operate
satisfactorily both before and after the fan is switched on.

6.  

It is preferable for the air supply for an extract fan to be

located where it can serve the fan without the air stream
passing close to the oil fired appliance.

7.  

Oil fired appliances must not draw combustion air from

a garage. 

13

Site requirements

AIR SUPPLY

XT (K P/F)

61 cm

2

MODEL

MIN. AIR REQUIREMENT

AIR SUPPLY

Содержание XT- Oil

Страница 1: ...T Oil K P F 10 13 EINS 514137 raywarranty aga web co uk DESN 514112 B Remember when replacing a part on this appliance use only spare parts that you can be assured conform the safety and performance s...

Страница 2: ...S 15 REQUIREMENTS PRELIMINARY INSTALLATION 15 SITE LOCATION 16 INSTALLATION 17 PCB CONNECTIONS 18 COMMISSIONING BURNER ACCESS 19 INSTRUCTIONS ELECTRICAL CONNECTION 19 OIL PUMP CONNECTION 19 ELECTRICAL...

Страница 3: ...armful if inhaled May be irritating to skin eyes nose and throat When handling avoid contact with skin or eyes Use disposable gloves face masks and eye protection After handling wash hands and other e...

Страница 4: ...Appliance 350 Kg Firing Rate 1 44 l h Flue Terminal Dimensions mm Width 500 mm Height 210 mm Depth 180 mm TECHNICAL DATA DESN 514170 B BURNER NOZZLE US g h 0 40 80 H LE DANFOSS 7 6 110 24 14 6 OIL PRE...

Страница 5: ...appliance does not exceed 100 C The constructional hearth described in current Building Regulations does not apply However this appliance must be installed on a solid floor or base of incombustible m...

Страница 6: ...ump for ease of burner removal The minimum recommended oil tank size is 1400 litres Mild Steel Tanks should be to BS 799 Part 5 and plastic tanks to OFTEC standard OFS T100 HOWEVER in the interests of...

Страница 7: ...Site requirements 7 DESN 514167 C DESN 514169 B FIG 2 MAXIMUM LENGTH METRES H METRES 10mm OD 0 100 3 0 100 3 5 88 4 0 40 Single Pipe oil system Two Pipe oil system...

Страница 8: ...em To convert to a two pipe system See Fig 4 Sections BURNER ACCESS steps 1 to 3 BURNER REMOVAL steps 1 to 5 PUMP FILTER REPLACEMENT steps 1 2 1 Remove middle screw 2 Remove horseshoe washer 3 Replace...

Страница 9: ...per factory set remove bend from manifold and pipe A Smear sealant on the end of the manifold and replace bend onto the manifold ensuring it is fully on and sweeps under the burner chamber 5 Smear the...

Страница 10: ...n the first end of pipe A and the surface of the 28mm branch towards the bend Slide the flexible pipe completely over the branch pipe should point towards burner chamber 7 Push the first end of pipe A...

Страница 11: ...ce via 1 bend See Fig 11 Horizontal runs must be as level as possible Care must be taken on mounting the terminal and routing the flue a Damage to damp proof course b Height above ground c General ter...

Страница 12: ...TECTION D BELOW A GUTTER OR A BALCONY 600mm WITHOUT PROTECTION E FROM VERTICAL SANITARY PIPEWORK 300mm F FROM AN INTERNAL OR EXTERNAL 300mm CORNER G ABOVE GROUND OR BALCONY LEVEL 300mm H FROM A SURFAC...

Страница 13: ...rtical plane to reduce the risk of blockage Ducts should be sized so as to reduce resistance to air flow 4 The ventilation requirement for kitchens in Part F of the Building Regulations is for mechani...

Страница 14: ...connection to the mains should be readily accessible and adjacent to the appliance The installation should be protected by a 30mA Residual Current Circuit Breaker RCCB The minimum requirement for the...

Страница 15: ...oil filter and the flexible oil feed pipe FLUE PIPE KIT Flue pipe kit comprises of 3 x 1 metre length of flue pipe 3 elbows 3 straight couplers 6 support brackets saddle and clamps 1 tube ultra grey...

Страница 16: ...lectric 3 Flue Pipe 4 Fit plinth assembly See Fig 14 5 Fit handrail assembly See Fig 15 as follows i Fit mounting brackets to top plate loose ii Fit handrail to brackets Tigten up screw fixing bracket...

Страница 17: ...ay require to be shortened or lengthened depending on wall thickness See Fig 18 7 Using the large wall fixings permanently fix back plate to the wall remove outer cover first 8 Wire the fan to the sup...

Страница 18: ...18 Installation Requirements FIG 20 EXTERNAL CONNECTIONS FAN CONNECTIONS AT TERMINAL MAINS CONNECTIONS PCB CONNECTIONS...

Страница 19: ...nsing phial of the fire valve through the grommet in the left hand side panel and locate behind the casting to the left of the burner opening 2 Connect the flexible hose to the outlet pipe from the oi...

Страница 20: ...manual reset button If the overheat stat trips the cooker will not operate until the button has been pushed in reset The engineer needs to follow Fault Finding Guide to establish why it has tripped Th...

Страница 21: ...f the signal light in the reset button of the control box see Fig 24 In this event wait at least one minute then press the re set button to restart SEE FIG 23 Whilst the burner is running vent air fro...

Страница 22: ...ew and insert the sensing end of a portable indicator to check the CO2 Carbon Dioxide level Adjust the burner air intake until a reading of 11 0 CO2 is recorded on the indicator Check Smoke Remove the...

Страница 23: ...l then be illuminated WAIT 1 MINUTE BEFORE RESETTING THE CONTROL BOX 1 Advise the User that for continued efficient and safe operation of the appliance it is important that adequate servicing is carri...

Страница 24: ...24 Wiring Diagram FIG 27 WIRING DIAGRAM APPLIANCE...

Страница 25: ...NG ALL WIRING TO THE IEE REGULATION BY A QUALIFIED ENGINEER USERS INSTRUCTIONS GUIDE PROGRAMMER AND TIMER COMBINATION 1 The Time of Day alarm and Minute Minder functions can all be used without effect...

Страница 26: ...26...

Страница 27: ...27...

Страница 28: ...er s policy of continuous product improvement the Company reserves the right to change specifications and make modifications to the appliance described at any time Manufactured by AGA Rangemaster Stat...

Отзывы: