IMPORTANT: Please lubricate the
internal part of the seals before
fitting.
26
TYPE OF FLUE SYSTEM (All types) - minimum and maximum distance
TABLE 4
Flue type C
13
C
33
C
53
1
Flue Diameter 60/100 80/125 60/100 80/125 80 mm
(concentric) (concentric) (concentric) (concentric) single pipe
Minimum length (m) 0.3 0.3 1.0 1.0 0.5
(horizontal length) (horizontal length) (vertical length) (vertical length)
Maximum length (m) 8.0 23.0 13.0 26.0 43.0
Equivalent length of 45° bend (m) 0.5 1.25 0.5 1.25 1.25
Equivalent length of 90° bend (m) 1.0 2.5 1.0 2.5 2.5
5.6 OPTIONAL EXTRAS
HORIZONTAL FLUE KIT BOX CONTAINING
(Fig 10):
52 - Self-cutting joint securing screw
57 - Elbow header
59 - Rubber seal Ø 60
56 - Rubber seal Ø 100
60 - Fumes sample point
61 - Flue exhaust duct
62 - Air intake duct
69 - Air sample point
127 - Terminal Rubber wall seal
Fig 11
Fig 10
WARNING:
With horizontal concentric fl ue, the
maximum fl ue length is 8 metres, duct extension can be
used with the standard fl ue (see table 4).
FLUE EXTENSION BOX CONTAINING (Fig. 11):
1000 mm fl ue extension duct as an extra cost only
when requested for side and vertical fl ue applications.
59 - Rubber seal Ø 60
63 - Air intake duct extension
64 - Flue exhaust duct extension
Generally speaking, oils and greases are not
suitable for the “peroxide -EPDM”,
therefore we suggest a correct lubrication
using silicon-substances, for instance
“Silikon Spray“ (Arexons).
Содержание HE 25 S COMPACT
Страница 2: ...2...
Страница 4: ...4...
Страница 5: ...5...
Страница 25: ...5 5 FLUE TERMINAL POSITION 25...
Страница 54: ...10 ELECTRICAL SYSTEM DIAGRAM 54 Fig 55...
Страница 55: ...55 11 SPARE PARTS Fig 56...
Страница 61: ...61...
Страница 62: ...62...
Страница 63: ...63 www centralheating co uk Benchmark Commissioning and Servicing Section...
Страница 64: ...64 FLOWCHART FOR CO LEVEL AND COMBUSTION RATIO CHECK ON COMMISSIONING A CONDENSING BOILER...
Страница 65: ...65 12 1 ANALYSER CHECK LIST...
Страница 66: ......