5
Manual No. 016-0159-845
29
Console Programming and Calibration
Console Programming
Data Entry
Note:
Data must be entered for all booms and for each of the variables. If a boom is not in use, enter 0
as the value for that boom.
1.
Press the number key that corresponds with the variable to be changed:
•
3 - BOOM CAL
•
4 - SPEED CAL
•
5 - METER CAL
•
6 - VALVE CAL
•
7 - RATE 1 CAL
•
8 - RATE 2 CAL
2.
Press ENTER. The name of the variable being changed and the letter E will appear in the display.
3.
Use the number buttons to enter the value.
4.
Complete the data entry by pressing ENTER.
Initial Console Programming
After all installation steps have been performed and the console power is turned on, the message “CAL US -
VOLUME PER ACRE” will appear in the console’s display. This indicates that the console must be calibrated
(or programmed) before it can be operated. Console calibration is a one-time procedure that, once it has been
performed, does not have to be repeated. Turning off the POWER ON/OFF switch does not affect the
console’s memory - all data is retained.
Important:
If an entry or selection error is made during the first six steps of this procedure, turn the
POWER ON/OFF switch to the OFF position, press CE and hold while turning the POWER
ON/OFF switch to the ON position to reset the console.
Refer to the values that were calculated in the Calculating Machine’s Calibration Values
section on page 5 when performing the initial console programming.
1.
Select the unit of measure (US - Volume per Acre, TU - Volume per Square Feet, or SI - Volume per
Hectare) by pressing the CE button until the until the desired unit of measure appears in the display.
2.
Press ENTER. The message “CAL SP1-WHEEL DRIVE” will appear in the console’s display.
3.
Select the type of sensor being used by pressing the CE button until the desired sensor type appears in the
display.
Note:
If the Phoenix 10 GPS speed sensor is being used, select SP-2 RADAR as the speed sensor type.
4.
Press ENTER. The message “LI LIQUID SPRAYER” will appear in the console’s display.
5.
Select the type of application (LI - Liquid Sprayer, GR1 - Single Bed Belt, GR2 - Split Bed Belt) by pressing
the CE button until the desired application type appears in the display.
6.
Press ENTER. The message “CAL C-SD STANDARD VALVE” will appear in the console’s display.
7.
Select the type of valve being used by pressing the CE button until the desired valve type appears in the
display.
Содержание SCS660M
Страница 1: ...SCS 660 660M Serial Interface for Granular Applications Installation Service Manual...
Страница 18: ...Chapter 3 12 SCS 660 660M Serial Interface for Granular Applications Installation Service Manual...
Страница 29: ...4 Manual No 016 0159 845 23 Installation FIGURE 15 SCS 660M Console Cabling Diagram...
Страница 54: ...Chapter 7 48 SCS 660 660M Serial Interface for Granular Applications Installation Service Manual...
Страница 56: ...Chapter 8 50 SCS 660 660M Serial Interface for Granular Applications Installation Service Manual...
Страница 58: ...Index 52 SCS 660 660M Serial Interface for Granular Applications Installation Service Manual...