Use and maintenance manual
Chronos, Zeus, Ercole e Ermes
Page 65
Rev.1 12/12/2019
External air intake
If the fitting to the chimney is horizontal, it
is necessary to not insert the last section of
pipe too far, to avoid throttling the smoke.
Any free thickness between the hole in the
existing chimney and the smoke duct pipe
must be duly sealed.
NO
YES
Installation examples
The smoke evacuation system is essential for correct chimney operation. Make sure that the installed chimney has at least one
inspection hatch located in an easily accessible point to aid cleaning.
Chimneys in poor conditions can only be used by inserting a regulation smoke duct inside them (see standards on ducting).
Insulated pipe
Insulated T fitting for
condensation
Insulated chimney
External air intake
External air intake
MAX 2m
slope min 3%
External air intake
MIN 1 m
MIN 1 m
MIN 1 m
Protection from rain
MIN 1 m