Use and maintenance manual Aria

Pag.25 

Rev.0  22/04/2022

EN

 

Use suitable equipment to remove the boards or wooden parts of packing.

 

📌

The end user is responsible for disposing of the packaging in accordance with the laws in force in the country of installation.

Set-ups for the smoke evacuation system 

 

Be  careful  when  building  the  smoke  evacuation  system  and  observe  the  regulations  in  force  in  the  country  where  the 

appliance is installed. 

 

📌

The Manufacturer will not be held liable for incorrectly sized and non-regulation smoke evacuation systems.  

Smoke ducts and fittings

The term smoke duct indicates all ducts that connect the combustion equipment to the chimney. 

The following requirements need to be applied: 

• 

observe product standard EN 1856-2;

• 

the horizontal sections must have a minimum slope of 3% upwards; 

• 

the length of the horizontal section must be as minimum as possible, and its projection on the horizontal plane must not exceed 

2 metres;

• 

changes in direction must not have an angle of more than 90° (45° bends are recommended); 

• 

the number of direction changes, including the one necessary for insertion into the chimney, must not exceed 3;

• 

the cross section must have a constant diameter, the same from where it exits the firebox up to the fitting into the chimney;

• 

it is forbidden to use flexible metal and fibre cement pipes; 

• 

smoke ducts must not cross rooms where the installation of combustion equipment is prohibited. 

In any case, the smoke ducts must be sealed against combustion products and condensation, as well as insulated if they lead outside 

of the installation room. 

Installing manual draught adjustment devices is not allowed.

Chimney

 

T

he chimney is a particularly important element for correct appliance operation. 

 

The chimney must be sized so as to guarantee the draught declared by the Manufacturer.

 

Do not connect the appliance to a collective chimney.

The chimney must be built applying the following regulations: 

• 

it must observe product standard EN 1856-1; 

• 

it must be made of materials that are suitable to guarantee resistance against normal mechanical, chemical and thermal stress 

and be correctly thermally insulated to limit the formation of condensation; 

• 

it must be mainly vertical and not feature any bottlenecks along its entire length; 

• 

it must be correctly spaced with an air gap and insulated from flammable materials; 

• 

there must be a maximum of 2 changes in direction and angles must not exceed 45°; 

• 

the  chimney  inside  the  home,  however,  must  be  insulated  and  can  be  inserted  into  a  skylight  shaft,  as  long  as  it  respects 

standards regarding placing inside a tube; 

• 

the smoke conduit must be connected to the chimney using a “T” fitting with an inspection collection chamber for combustion 

residue and especially for collecting condensation. 

 

📌

It is necessary to check the safety distances that need to be observed when there are flammable materials and the type of 

insulating material that needs to be used is on the chimney data plate.

 

Use watertight pipes with silicone seals.

 

It is forbidden to use the discharge mounted directly on the wall or directed towards indoor spaces and any other type of 

discharge that is not set forth by the regulation in force in the country of installation (Note: in Italy only roof-discharge is 

allowed).

Chimney pot 

The chimney pot, i.e. the top end of the chimney, must fulfil the following characteristics: 

• 

the cross-section of the smoke outlet must be at least twice the internal cross-section of the chimney; 

• 

it must stop water or snow from getting in; 

• 

make sure the smoke is taken away even when there is wind (wind resistant chimney pot); 

• 

the outlet height must be outside of the reflux zone (refer to national and local regulations to calculate the reflux zone); 

• 

it must always be built at a distance from antennas or dishes, it must never be used as support.

Содержание Aria

Страница 1: ...USE AND MAINTENANCE MANUAL Aria...

Страница 2: ......

Страница 3: ...uiksaanwijzing Beachten Sie die Warnungen und Hinweise betreffend die Installation und regelm ige Wartung in der Bedienungsanleitung Respete las advertencias y las indicaciones de instalaci n y manten...

Страница 4: ...c thermostat room temperature control No Useful efficiency NCV as received with electronic room temperature control No Useful efficiency at nominal heat output th nom 91 5 with electronic room tempera...

Страница 5: ...andard The notified laboratory T V Rheinland Energy GmbH NB 2456 performed the determination of the product type on the basis of type testing under system 3 and issued test report K31932021T1 8 Declar...

Страница 6: ...o Trademark Marque Ravelli Modello Model Mod le Aria L oggetto della dichiarazione di cui sopra conforme alla pertinente normativa di armonizzazione dell Unione The object of the declaration described...

Страница 7: ......

Страница 8: ......

Страница 9: ...n do not discard it without reading it Incorrect installation maintenance and improper use of the product relieve the Manufacturer of all liability deriving from use of the stove For further informati...

Страница 10: ...uels 18 TECHNICAL CHARACTERISTICS 19 Technical diagram Aria 20 Main parts 21 Description of operation 21 Recharge the fuel 22 Doors opening 22 User training 22 Safety devices 23 SHIPPING AND INSTALLAT...

Страница 11: ...ing 38 Stove phase general layout 40 MAINTENANCE 43 Safety warnings for maintenance 43 Cleaning 43 Extraordinary maintenance 45 Failure cases 47 TROUBLESHOOTING 50 The appliance does not work 50 Diffi...

Страница 12: ...Maximum water temperature TW max set Maximum adjustable water temperature pWnom Max working pressure 230 V 50 Hz Alimentation Distance to combustible materials dS L Left side dC Ceiling dS R Right si...

Страница 13: ...the gaskets the paint job the stainless steel or cast iron combustion grille the resistance the Majolica cladding the aesthetic parts any damages caused by unsuitable installation and or use of the pr...

Страница 14: ...any inconsistency arises it will be necessary to follow the text in the original language or contact our Technical Documentation Office Symbols used in the manual symbol definition This symbol is use...

Страница 15: ...y use original spare parts Any tampering and or replacements that have not been authorised by Ravelli can pose a danger to the user s safety In the event of particularly adverse weather conditions the...

Страница 16: ...contract and herein the operating manual procedures are followed routine maintenance is carried out according to the times and methods set forth extraordinary maintenance is promptly carried out when...

Страница 17: ...gulation chimney provide a suitable system for the supply of combustion air air intake or intake duct for watertight appliances always perform maintenance with the appliance off and cold perform clean...

Страница 18: ...Ravelli recommends using wood pellet classified A1 and A2 according to the EN ISO 17225 2 2014 standard or certified DIN PLUS more restrictive than the A1 class or ONORM M 7135 Pellet may be light or...

Страница 19: ...nsumption max W 260 Electrical power consumption reduced nominal W 30 50 Stand by electrical consumption W 3 8 smoke air inlet mm 35 smoke outlet pipe mm 80 Hopper capacity kg 17 Seasonal energy effic...

Страница 20: ...Pag 20 Rev 0 22 04 2022 EN 718 621 513 223 156 35 ENTRATA ARIA 80 USCITA FUMI 373 205 45 Measurements Unit of measurement Aria Height mm 718 Width mm 621 Depth mm 513 Weight kg 127 Technical diagram A...

Страница 21: ...electronic control unit that manages the start up operation and shutdown phases and also includes many other functions for control programming and safety The user can choose the operating power from 5...

Страница 22: ...RM button you can read the detail of the warning doors and ash pan open If the combustion chamber door the pellet hopper lid and or the ash drawer are not closed within 1 minute the stove switches off...

Страница 23: ...standard equipped with a grounding circuit and all the safety systems required by the standards It should be noted that the stove s operating program has been designed to stop stove operation in the e...

Страница 24: ...d that the safety distances from flammable materials are observed Verification of system compatibility has a priority over any other assembly or installation operation Local administrative regulations...

Страница 25: ...anufacturer Do not connect the appliance to a collective chimney The chimney must be built applying the following regulations it must observe product standard EN 1856 1 it must be made of materials th...

Страница 26: ...the presence of other combustion appliances or VMC system it is necessary to check the appliance for correct operation The appliance must be placed inside living quarters It must never be installed o...

Страница 27: ...another one installed so that the outside section can be inspected It is prohibited to install two 90 bend since the ashes would quickly obstruct smoke passage causing draught problems in the applianc...

Страница 28: ...ickly obstruct smoke passage causing draught problems in the appliance See Fig 2 INTERNAL CHIMNEY Fig 5 Protection from rain Covering sheet Air tight steel sheet metal T fitting with collection chambe...

Страница 29: ...connected after the installation and assembly has been completed of the appliance and must remain accessible after installation To make the electrical connection proceed as described below First conn...

Страница 30: ...ND Safety devices T1 Pressure switch T2 Resettable thermal breaker T3 Pellet tank contact Motors M1 Infeed screw gear motor M2 Automatic cleaning system M3 Fume exhaust system M4 Room fan Resistance R...

Страница 31: ...ble in the menu Select the desired language with the scroll buttons and confirm your selection with the confirmation button In order to operate correctly the remote control should be interfaced with t...

Страница 32: ...of the battery on the back of the remote control as shown in Figure A and insert the 3 batteries mini pen style battery AAA 1 5V in the housing of the remote control and observe the poles Install the...

Страница 33: ...N ADJUST LANGUAGE SCREW FEEDING CHRONOTHERMOSTAT AIR PELLET SET STOVE STATE The display is subdivided into three parts 1 It shows the current room temperature measured by the handheld set Moreover if...

Страница 34: ...COMFORT CLIMA DELTA RESTART DELTA SHUTDOWN DELAY SETTINGS SCREW FEEDING CHRONOTHERMOSTAT AIR PELLET SET STOVE STATE CONNECT AN EXTERNAL THERMOSTAT WITH A SIMPLE DRY CONTACT THEREFORE NOT POWERED MORE...

Страница 35: ...ct therefore not powered moreover we recommend you use a thermostat with a minimum offset of 3 C if you ntend to use the comfort clima function Description of menu functions Press the key to access th...

Страница 36: ...ure If the type of system designed requires controlling the 3 way valve diagram 1 and 3 it is necessary to purchase the optional kit from the retailer or the authorized Ravelli dealer CHRONO CHRONO EN...

Страница 37: ...RECOMMEND YOU USE A THERMOSTAT WITH A MINIMUM OFFSET OF 3 C IF YOU INTEND TO USE THE COMFORT CLIMA FUNCTION Operating phases of the appliance Modulation During the work phase the appliance should rea...

Страница 38: ...FW VERSION LANGUAGE LANGUAGE LANGUAGE LANGUAGE ADJUST ADJUST ADJUST ADJUST In Home mode instead of room temperature measured and settable appears the line T ON if the room in which the thermostat is i...

Страница 39: ...l confirm of data and switch to the page within SETTINGS menu The stoves equipped with ventilation system can heat the area in which are installed through the heat generated by the window and the room...

Страница 40: ...set is reached see the dedicated section WAITING START RESTART Switch on is requested but with the stove in cooling phase once this condition is met it restarts automatically IGNITION RESTART The HOT...

Страница 41: ...or is connected incorrectly Contact the Support Service No power to fume extractor Contact the Support Service The fume extractor is blocked Contact the Support Service AL 05 NO IGNITION The pellet ta...

Страница 42: ...obstruction or voltage drop Check the mains voltage AL 14 AUGER PHASE No cable connection to power the gear motor Check the mains voltage AL 15 AUGER TRIAC An internal part of the electronic board tha...

Страница 43: ...e stove operating mode and combustion control can affect maintenance activity frequency Cleaning Perform the cleaning operations so as to guarantee correct stove operation The table below lists the ne...

Страница 44: ...cold stove clean the glass with a cloth and glass cleaner Note there are stove glass cleaning products available on the market Combustion chamber cleaning To clean the ash drawer proceed as follows s...

Страница 45: ...ng with their replacement Replace a worn component before it is completely broken to prevent any damage caused by sudden component breakage PARTS FREQUENCY 1 SEASON Deep combustion chamber cleaning Do...

Страница 46: ...operation must be carried out by a Ravelli Assistance Centre Schedule this type of cleaning with the Ravelli Assistance Centre The stove is equipped with some hatches for cleaning the internal smoke d...

Страница 47: ...eplace the electronic board contact the Technical Assistance Service AL 15 The flame does not ignite Check that the igniter warms up Check and if necessary replace the igniter AL 05 Air inlet duct blo...

Страница 48: ...sed perfectly or the gasket are worn Close the door and have the gaskets replaced with original ones AL 05 AL 06 The stove stops automatically Alarm presence Check the alarm table Any alarm Active chr...

Страница 49: ...ot work Remote control battery low Replace battery or connection to the stove via cable Faulty remote control Replace remote control The stove always works at maximum power Temperature not set correct...

Страница 50: ...s at the inlet and outlet for prolonged downtime DISPOSAL AT END OF SERVICE LIFE Warnings for the correct disposal of the product Demolition and disposal of the appliance is under the exclusive liabil...

Страница 51: ...lays Sensors Spark plugs Electronic boards Batteries Dispose of separately at authorised centres in accordance with WEEE 2012 19 EU and its national transposition E METAL STRUCTURE Dispose of separate...

Страница 52: ...r s parer cet appareil et ou les piles ou les accumulateurs des autres types de d chets et de le confier au service municipal de collecte On peut demander au distributeur de pr lever le d chet d appar...

Страница 53: ...r at forebygge ventuelle skader for milj et eller sundheden bedes brugeren om at behandle dette udstyr og eller de medf lgende batterier eller akkumulatorerne separat fra andre affaldstyper og at leve...

Страница 54: ......

Страница 55: ......

Страница 56: ...f free to make any variations to the features of its products without notice Aico S p A Headquarter Via Consorzio Agrario 3 25032 Chiari BS Italy Research and Development Centre Viale del commercio 12...

Отзывы: