Connected loads
3 NAC 400 V
112
112 with
vitro
211
211 with
vitro
311
311 with
vitro
Power (kW)*
17
19
28
31
45
47
Current consumption (A)
23
34
47
47
70
70
Fuse (A)
25
40
50
50
80
80
Cross section
recommended (mm²)
2,5
6
10
10
16
16
3 NAC 400 V Dynamic
112
112 with
vitro
211
211 with
vitro
311
311 with
vitro
Power (kW)*
13
15
22
24
35
37
Current consumption (A)
19
29
37
37
56
57
Fuse (A)
20
32
40
40
63
63
Cross section
recommended (mm²)
2,5
4
6
6
10
10
3 NAC 415 V
112
112 with
vitro
211
211 with
vitro
311
311 with
vitro
Power (kW)*
18
20
30
32
47
50
Current consumption (A)
25
35
49
49
74
74
Fuse (A)
25
40
50
50
80
80
Cross section
recommended (mm²)
2,5
6
10
10
16
16
3 NAC 415 V Dynamic
112
112 with
vitro
211
211 with
vitro
311
311 with
vitro
Power (kW)*
14
17
23
26
37
40
Current consumption (A)
19
30
39
39
58
59
Fuse (A)
20
32
40
40
63
63
Cross section
recommended (mm²)
2,5
4
6
6
10
10
Caution:
As written on page 14, the unit has to be connected through a 30 mA circuit breaker.