6 | Electrical connection
80.06.562_IM_2-XS_ 2-S_en-INT
37 / 56
4. Insert screws (5) and (6).
5. Lightly press the cover in the area of the respective screw and tighten the
screws (5) and (6) one after the other.
5
6
>>
The electrical compartment is closed and protected against the penetration
of water and humidity.
6.7
Power ratings of different voltage types
Maximum connection voltage
n
Maximum permissible tolerance for input voltage: - 10% to 10%
n
The unit can be used with frequencies of 50 Hz and 60 Hz without making
any technical modifications.
NOTICE
The values stated for the cable cross-section relate to a maximum cable
length of 2 m [78 Inch]. Calculate the conductor cross section according to
the length and quality of the power cable used.
3N AC 400 V
Power kW
Amp draw A
Fuse A
Conductor cross-sec-
tion mm²
iVario 2-XS
14
20
20
2,5
iVario Pro 2-S
21
30
32
4