ALL APPLICATIONS (VENTED and VENT FREE OPERATION)

Pilot Adjustment and Operation:

The Pilot flame should be steady and soft blue surrounding 1/8 
inch of the thermocouple tip as shown in Figure 15.

OP AMERICA Standard (Manual Models):
1.

To adjust, insert  a narrow long stem screw driver throughPilot 
Access Port
 (see figure 10) to turn pilot adjustment screw .

2.

Turn clockwise for less pilot flame.

3.

Turn counterclockwise for more pilot flame.

OP AMERICA Millivolt (Switch Model)

NOTE: The OP America Millivolt Pilot/ODS is equipped with a

THERMOGENERATOR (Switch Models)

LP THEMOCOUPLE

NAT  GAS 

THERMOCOUPLE

PIEZO SPARKER

PILOT FLAME

Figure 15

AIR INTAKE

HOLES

quick acting thermocouple allowing gas flow to the pilot after approximately 30-40 seconds.  An additional 60 to 
90 seconds time is required to adequately heat the thermogenerator and allow gas to the main burner(s).

1.

If adjustment is necessary, use a narrow long stem screw driver to turn pilot adjustment screw  (see Figure 12).

2.

To adjust  turn clockwise for less pilot flame, counterclockwise for more pilot flame.

Normal Operating Characteristics:

Each and every CHILLBUSTER that leaves the factory is quality checked to ensure compliance with our

American Gas Association certification.  This check includes an operational test to ensure both satisfactory
combustion and proper operation.

Each installation site for any vent free heater presents its own unique combustion environment.  Specific factors

such as weather tightness of the home, size of the room in which the heater is installed, central heating, ceiling
fans,drafts, altitude, the size of the firebox, paint or soot inside the firebox, etc., all have an influence on the proper
operation of any vent free gas log set.  A normally operating
CHILLBUSTER Gas Log Heater will possess the following
characteristics:

Clean burning combustion, which, after normal break in, will produce

no soot or smoke.

A full bodied, lively flame.  The flame will be blue at the base and a

combination of blue and yellow at the body and tips. Figure 16.

Produce no odor other than the normal odors associated with the

combustion of Natural or Propane gas.

Will produce water  vapor (increase indoor humidity) which may be

beneficial during the dry heating season.

Figure 16

Customer Responsibilities And Annual Maintenance:

• Keep the area around the CHILLBUSTER free and clear from debris. From time to time, visually check pilot and 

burner flames for proper appearance (Figures 15 and 16).  Normal flame color should be yellow body surrounded
by a hard blue haze.

• The pilot, air shutters and burners must be free of lint and dirt for optimum performance.  Air shutters which have 

been closed or are obstructed with debris will not allow sufficient combustion air into burner.  Air shutters should be
periodically cleaned of debris.  Use compressed air or a soft bristle brush to clear pilot and burner(s) air intakes.  Air

shutters should not be altered from factory settings"WARNING: Failure to keep the primary air
opening(s) of the burner(s)clean may result in sooting or property damage."
• Obstructed Pilot Air Intake Ports result in an improper gas/air mixture and a weak pilot flame.  Weak pilot flame 

is the NUMBER 1 SERVICE ISSUE RE NUISANCE SHUT-OFF.  Using canned compressed air , pipe 
cleaner or an artist's brush, clean out the opposing Air Intake Ports located at base of Pilot (where gas supply line 
attaches to pilot).  (Figure 15)

Do not operate in a dirty firebox or in a previously used firebox which has not had all soot completely removed or it's

chimney  flue cleaned. Previously used fireboxes must have flue and stack professionally cleaned by a chimney
sweep.  Additionally, firebox walls and damper must also be thoroughly cleaned of all burn residue and soot using a
damp cloth, sponge or brush.

Do not operate this set with any logs other than the RASMUSSEN CHILLBUSTER Refractory Logs specifically

designed and approved for use with this Burner System.

Do not use with blower inserts or heat exchangers.

If used, glass doors must be wide open when burner is on.

Do not remove Rating Plate/Warning Tags. These tags serve you and any future user as an integral safety and

identification component of the CHILLBUSTER gas log heater.  Removing these tags voids the warranty.

WARNING:  Do not allow fans to blow directly into fireplace.  Avoid any drafts that alter burner

flame patterns. Do not place blower inside area of firebox. Ceiling fans may create drafts that alter burner flame
patterns. Sooting and improper burning may occur. Sooting can settle on household surfaces outside the fireplace.

During periods of heavy use, inspect frequently for evidence of sooting. If sooting is present, discontinue

use until source of sooting is determined and corrected.

Maintain log positioning as shown in Figures 5 and 6 or 7 and 8 at all times.

10

Содержание K18-C1C-M-N

Страница 1: ...sted ventless firebox enclosure DO NOT install this appliance in a factory built fireplace that includes instructions stating it has not been tested or should not be used with unvented gas logs WARNIN...

Страница 2: ...a CHILLBUSTER is installed 3 The minimum size in inches of the fireplace in which this CHILLBUSTER is to be installed must be as follows SET SIZE MODEL NUMBER FRONT WIDTH HEIGHT DEPTH 18 24 30 18 24...

Страница 3: ...USTER is very realistic in appearance it is not a real wood burning fireplace Matches paper garbage or any other material must not be thrown on top of the logs or into the flames Avoid contact with th...

Страница 4: ...table Btu Hr 72 000 Btu Hr Actual Btu Hr Used 11 840 Btu Hr Excess Non Supportable Btu Hr In the example because the Actual Btu Hr Used exceeds the Maximum Supportable Btu hr the space would be consid...

Страница 5: ...bing electrical and gas lines and at other openings WARNING CARBON MONOXIDE POISONING MAY LEAD TO DEATH When used without fresh air gas log sets may give off carbon monoxide an odorless colorless pois...

Страница 6: ...OX Figure 3 4 Standard Fireplace Hood with a minimum 4 inch horizontal projection beyond vertical surface ABOVE hood as provided by most major fireplace manufacturers IF YOU CANNOT MEET THESE MINIMUM...

Страница 7: ...VIEW FRONT VIEW Front Log Rear Log Top Log Large R Top Log Large L Top Log Small L Top Log Small R Front Log Rear Log Top Log Large R Top Log Small R Top Log Large L Top Log Small L Main burner 24 30...

Страница 8: ...Valve Knob until air is bled and gas flows to pilot Press PIEZO IGNITOR Button Figure 9 to light pilot Continue to hold valve knob in until Pilot remains lit when knob is released 5 Slowly turn knob t...

Страница 9: ...ared and operate instantly and requires you to aim and hold the transmitter for 1 to 3 seconds to operate Manual Operation Receiver switch position ON or OFF does not require batteries Remote Operatio...

Страница 10: ...the area around the CHILLBUSTER free and clear from debris From time to time visually check pilot and burner flames for proper appearance Figures 15 and 16 Normal flame color should be yellow body sur...

Страница 11: ...20 21 22 24 26 31 30 23 25 2 8 32 33 40 41 42 43 50 51 60 61 62 1 O22 Burner 40 000 BTU or 9 Push Button Ignitor DFC1 C1C Double Face 43 Valve Knob O38 Burner 23 000 BTU 10 Inlet Aluminum Connector 30...

Страница 12: ...as set forth herein and applies only for the periods designated above 2 RASMUSSEN shall not be liable for any loss damage incidental or consequential damages of any kind whether based upon warranty c...

Страница 13: ...CPW CB 2 96 CHANGES next page 1 standard update z21 11 2a 2001 DUE 4 03 standard update z21 11 2b 2002 DUE 12 03 13...

Отзывы: