Chapter 7: Sensor-Mixing Connections
69
The daisy chain procedure is identical to the one described any topic
below:
Cascading DX2 Sensor Packages
(on page 17)
Cascading DX Sensor Packages
(on page 36)
Cascading DPX3 Sensor Packages
(on page 41)
Same as a pure DX2, DX or DPX3 sensor chain, you can replace the final
sensor package with a DPX2 sensor package. See
Connecting a DPX2
Sensor Package to DX2, DX or DPX3
(on page 49).
Mixing DPX, DPX2, DPX3, DX and DX2 Sensor Packages
You can mix DPX, DPX2, DPX3, DX and DX2 sensor packages per SENSOR
port according to the following sensor combinations. In some scenarios,
the DPX3-ENVHUB4 sensor hub is required.
1 DX + 1 DPX :
It is strongly recommended to use an RJ-12 to RJ-45 adapter to
connect the DPX sensor package to the DX sensor package.
You can replace the DX in the following diagram with one DPX3
package, but NOT with DX2.
Combinations via the DPX3-ENVHUB4 sensor hub:
You must use the DPX3-ENVHUB4 sensor hub instead of the old
DPX-ENVHUB4 sensor hub. Each port on the hub supports any of the
following:
One individual DX2 sensor package
A chain of DX2 sensor packages
One individual DX sensor package
A chain of DX sensor packages