Chapter 2: DX2 Series
17
When the Normal state is set to Normally Open (N.O):
LED
Sensor state
Off Open
Lit Closed
Cascading DX2 Sensor Packages
To increase the number of connected DX2 sensor packages per SENSOR
port, you can cascade DX2 using standard network patch cables (CAT5e
or higher). A maximum of 12 DX2 sensor packages can be daisy chained.
Tip: You can also make a sensor chain comprising DX2, DX and DPX3
sensor packages. See
Cascading DX2, DX and DPX3 Sensor Packages
(on page 68).
To cascade DX2 sensor packages:
1.
Connect a standard network patch cable to either RJ-45 port of the
first DX2 sensor package.
Exception: For a Raritan PDU or EMX with an "RJ-12" SENSOR port,
an RJ-12 to RJ-45 adapter cable (part number: RJ12M-RJ45M) is
needed, which you can request from Raritan.
2.
If you want to cascade DX2 packages, get an additional standard
network patch cable (CAT5e or higher) and then:
a.
Plug one end of the cable into the remaining RJ-45 port on the
prior DX2 package.
b.
Plug the other end into either RJ-45 port on an additional DX2
package.
Repeat the same steps to cascade more DX2 packages.