background image

R A M S E T

z

R A M S E T

z

R A M S E T

RA

MS

ET

z

RA

MS

ET

z

RA

MS

ET

- 2 -

Installation should be done by a qualified installer only.

Prior to Installation, the following must be
observed: (per UL 325 51.8.4)

a)

Install the vehicular gate operator only when:

1) The Vehicular Gate Operator is appropri-

ate for the construction of the gate and
the usage Class of the gate,

2) All openings of a horizontal slide gate are

guarded or screened from the bottom of
the gate to a minimum of 4 feet (1.2 m)
above the ground to prevent a 2-1/4 inch
(57.15 mm) diameter sphere from pass-
ing through the openings anywhere in the
gate, and in that portion of the adjacent
fence that the gate covers in the open
position.

3) All exposed pinch points are eliminated or

guarded, and

4) Guarding is supplied for exposed rollers.

b)

The Vehicular Gate Operator is intended for
installation only on gates used for vehicles.
Pedestrians must be supplied with a separate
access opening.

c)

The gate must be installed in a location so
that enough clearance is supplied between
the gate and adjacent structures when open-
ing and closing to reduce the risk of entrap-
ment. Swinging gates shall not open into
public access areas.

d)

The gate must be properly installed and work
freely in both directions prior to the installa-
tion of the Vehicular Gate Operator. Do not
over-tighten the operator clutch to compen-
sate for a damaged gate.

e)

Controls must be far enough from the gate so
that the user is prevented from coming in
contact with the gate while operating the con-
trols. Controls intended to be used to reset a
Vehicular Gate Operator after 2 sequential
activations of the entrapment protection
device or devices must be located in the line-
of-sight of the gate. Outdoor or easily acces-
sible controls shall have a security feature to
prevent unauthorized use.

f)

All warning signs and placards must be
installed where visible in the area of the gate.

g)

For Vehicular Gate Operators utilizing a non-
contact sensor in accordance with 30A.1.1
Type B1 non-contact sensor (photo electric
sensor or the equivalent)

1) See instructions on the placement of

non-contact sensors for each Type of
application,

2) Care shall be exercised to reduce the risk

of nuisance tripping, such as when a
vehicle, trips the sensor while the gate is
still moving, and

3) One or more non-contact sensors shall

be located where the risk of entrapment
or obstruction exists, such as the perime-
ter reachable by a moving gate or barrier.

h)

For a Vehicular Gate Operator utilizing a con-
tact sensor in accordance with 30A.1.1

1) One or more contact sensors shall be

located at the leading edge, trailing edge,
and postmounted both inside and outside
of a vehicular horizontal slide gate.

2) One or more contact sensors shall be

located at the bottom edge of a vehicular
vertical lift gate.

3) One or more contact sensors shall be

located at the pinch point of a vehicular
vertical pivot gate.

4) A hardwired contact sensor shall be

located and its wiring arranged so that
the communication between the sensor
and the vehicular gate operator is not
subjected to mechanical damage.

5) A wireless contact sensor such as one

that transmits radio frequency (RF) sig-
nals to the vehicular gate operator for
entrapment protection functions shall be
located where the transmission of the
signals are not obstructed or impeded by
building structures, natural landscaping
or similar obstruction. A wireless contact
sensor shall function under the intended
end-use conditions.

Содержание RAM-5500 UL

Страница 1: ... No 545327 US C Instruction Manual Model RAM 1000 UL RAM 5500 UL For Class I II III IV Vehicular Gate Operators Rev 060202 ...

Страница 2: ... a rigid object or stop when an object activates the non contact sensors After adjusting the limit of travel retest the Vehicular Gate Operator Failure to adjust and retest the Vehicular Gate Operator properly can increase the risk of injury or death 5 Use the Emergency Release only when power switch or circuit breaker has been turned off Using the Emergency Release during a power failure can be a...

Страница 3: ...ent protection device or devices must be located in the line of sight of the gate Outdoor or easily acces sible controls shall have a security feature to prevent unauthorized use f All warning signs and placards must be installed where visible in the area of the gate g For Vehicular Gate Operators utilizing a non contact sensor in accordance with 30A 1 1 Type B1 non contact sensor photo electric s...

Страница 4: ...d 12 inches per second Reduction By worm gearbox continually lubricated in an oil bath By worm gearbox continually lubricated in an oil bath Finish Chassis Rust preventing Gold Zinc coated 3 16 sheet metal Rust preventing Gold Zinc coated 3 16 sheet metal Gate Stops with limit switches with limit switches Chain 20 ft of Nickle plated chain to inhibit corrosion 20 ft of Nickle plated chain to inhib...

Страница 5: ...ars and wire mesh 5 Mix concrete pour mixture into form Tamp mixture Level and finish surface after pouring is complete 6 Allow pad to cure 48 hours and remove forms Figure 1 6 1 2 6 MIN 4 MIN WALL 4 6 1 2 24 Conduit for power Conduit for Master Slave Conduit for low voltage wires 18 x 18 x 24 Concrete Pad 24 6 4 4 MIN 18 B 4 1 2 C 18 concrete concrete A Gate L C Wall Figure 2 LH installation gate...

Страница 6: ... IN FEET USING COPPER WIRE BY WIRE SIZE INPUT POWER MOTOR HP RECOMMENDED WIRE GAUGE VOLTAGE DROP CHART Low voltage control wires must be run in a separate conduit to the operator E D Rear Installation Gate Shown Fully Open No tail on gate required Figure 4 24 Dim D minus distance deter mined by pulleys E D Center Installation Gate Shown Fully Open Figure 5 6 min Concrete Pad 2 1 2 diameter UHMW Pu...

Страница 7: ...p switches for manual operation of the gate see Figure 7 The open stop and close buttons can be utilized to set limit switches and verify proper system opera tion when installing or servicing an operator Open Pressing this button will cause the gate to open Stop Pressing this button will cause the gate to stop moving Close Pressing this button will cause the gate to close TURN POWER OFF BEFORE ATT...

Страница 8: ...te is clear of people or obstructions BEFORE turning power ON to avoid injury nWARNING ALWAYS TURN OFF POWER WHEN SERVICING OPERATOR MAIN CPU CHIP OPEN FULLY OPEN FULLY CLOSED ALARM JP6 1 2 A 10 A JP5 JP7 JP2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 STOP CLOSE A M1 M2 B COMMON REVERSE FIREBOX EXIT PHANTOM ADDRESS 1 ADDRESS 0 MECH LOCK DOOR IN DOOR HIGH ERD SENS SECURE CLOSE MOM SOS RADIO...

Страница 9: ... moving until a close contact is reached DIP SWITCH A8 LOW ERD HIGH ERD Sensitivity DIP FUNCTION off Normal ERD sensitivity Adjusts the ERD for standard sensitivity on Adjusts the ERD sensitivity so that more pressure is needed to stop the gate recommended only use in windy areas DIP SWITCH B1 SECURE CLOSE Secure Close DIP FUNCTION off Normal operation on When power is lost then regained control b...

Страница 10: ...PUT DESCRIPTION Limit 1 Limit 2 Depending on dip switch B7 see dip switch features stops the motor from moving in one direc tion These wires are preset in factory and should not be moved Becomes active with a closed contact to common Phantom Keeps the gate open when the open limit switch A or B is activated Used with loop detectors Becomes active with a closed contact to common Rev Loop Stops the ...

Страница 11: ...2 MOTOR 1 AC HOT NEUTRAL MAG SOLENOID CLOSE Figure 10 3 Wire Radio Receiver Capacitor Radio Terminal Strip Mag Lock Solenoid BL BK BK RD WH Legend RD Red WH White BL Blue GR Green Ground BK Black YL Yellow WH WH WH WH YL GR RD RD BL BK BK BK Motor BL RD TO 120VAC TO NEUTRAL POWER SWITCH 120V AC 120V AC or 220V AC or 220V AC N C N O N O Limit Switch Limit Switch C C N C Firebox Pedestrian Switch Ph...

Страница 12: ... INSTALLATION 6 feet min typical Inside Property Outside Property Twist wires outside of loop 3 feet min Reversing Loop Reversing Loop Exit Loop 3 feet min 3 feet min Figure 11 4 feet min 4 feet min 4 feet min 2 4 feet Primary Operator is factory pre set for LH operation Do not twist wires inside loops 1 4 1 1 2 Figure 12 Use 3 stranded shielded wires not supplied from Master to Slave Use jumper J...

Страница 13: ...x 7 limit switch shaft 1 32 50 247 3 4 ball bearrings 2 2 33 50 248 4 pin disc release 1 1 34 50 249 1 arbor release 1 1 35 50 250 41 b 27 clutch release sprocket 1 1 36 50 251 41 b 12 x 3 4 sprocket 1 1 37 50 252 board metal cover 1 38 50 253 3 4 shaft collar 2 2 39 50 254 spring load bracket 1 40 50 256 3 4 HP 120 VAC electric motor 1 41 50 264 1 4 x 1 1 2 key way 1 1 42 50 265 3 16 x 3 4 key wa...

Страница 14: ...58 45 62 26 52 51 21 61 20 11 8 47 22 6 7 19 43 44 16 5 58 36 42 13 48 1 33 34 41 3 12 14 57 17 56 59 35 15 23 53 54 55 38 24 63 RAM 1000 UL PARTS DIAGRAM RAMSETz RAMSETz RAMSET R A M S E T z R A M S E T z R A M S E T 13 Figure 13 ...

Страница 15: ...ure 14 4 20 32 31 39 25 37 18 60 2 58 27 62 26 52 51 21 61 20 11 8 29 22 6 7 19 43 44 16 5 58 36 42 13 28 40 33 34 41 3 12 14 57 17 56 59 35 15 23 53 54 55 38 24 63 RAMSETz RAMSETz RAMSET R A M S E T z R A M S E T z R A M S E T 14 ...

Страница 16: ...r system intended for use in a home of one to four single family dwellings or a garage or parking area associated therewith COMMERCIAL GENERAL ACCESS VEHICULAR GATE OPERATOR CLASS II A vehicular gate operator or system intended for use in an commercial location or building such as a multi family housing unit five or more single family units hotels garages retail stores or other buildings serving t...

Отзывы: