MANUALE ISTRUZIONI / INSTRUCTIONS MANUAL
MTR605/025/DASM - R605/027/DASM - R605/170/DASM
Modello/Model R605DASM
I/ 9
sistema_
elettronico
_60
5_CAN.fm
These values ca be set by string sent to board even when it is working
00 = 07x4 5 04 676700 67
00 = 07x4 5 04 676701 67
02 = 07x4 5 04 676702 67
03 = 07x4 5 04 676703 67
Wher x is a base value.
Base ID 720 724 x=2
5°Byte (Logical level of the home sensor)
The scope of this byte is to set the logical level for the input of the home sensor
when the system is in the home position.
In the case of connection to a fork photocell, this value must be set at 00 for the
photocell that is obscured at zero position (occupied slot) or set at 01 for the photo-
cell that receives light a zero position (free slot).
ID 705h (drive speed)
This controls sets some parameters related to the speed of the electromechanical sys-
tem in question.
1° Byte (mask)
The scope of this byte is to select, wherever necessary, the parameters that need
to be modified within the string. If the respective bit is set at 1, the corresponding
value is transferred, otherwise it will be ignored by the system.
The mask is necessary since a single string contains a number of parameters and
only a third or whatever combination might want to be transferred as valid. In this
case, parameters corresponding to non-selected positions (zero mask bits) will be
ignored and may then assume any value
1° byte.
2° e 3° Byte (Frequenza minima)
The scope of this byte is to set the minimum frequency corresponding to the motor
start-up speed. Set value is in Hertz, minimum value is 125 Hz.
The corresponding angular speed is a function of the following equation:
R.p.m. =
where K is the step fraction and P the number of stepes per revolution.
2
2
2
2
2
2
2
2
Riserv.
Riserv.
Riserv.
Riserv.
Riserv.
Rampa
F.max
F.min
60 * Freq
K * P