CLEARANCE TO NON-COMBUSTIBLE WALL
We recommend a minimum clearance to non-combustible material of at least 2” (50
mm) so that cleaning is easy. The cleaning door of the chimney should be accessible at
all times.
Clearances may only be reduced by means approved by the regulatory authority.
INSTALLATION
VENTILATION
Extractor fans may not be fitted in the same room as the stove, as this can cause the
stove to emit smoke and fumes into the room.
The stove requires a permanent and adequate air supply to operate safely and effec-
tively. The installer may have fitted a permanent air supply vent into the room in which
the stove is installed to provide combustion air.
This air vent should not be shut off or sealed under any circumstances.
INSTALLATION