D9000/D7000 Series Installation and Troubleshooting Quick Reference

Page  9

33317D  4/97

Communications Failure 

(Continued)

Symptom

Diagnosis

Remedy

The line rings but
the D6500
receiver does not
pick up.

RING indicator on
line card does not
light. Can not hear
ring with headset
at receiver
location.

Line is not ringing at
the receiver.

1.

Verify that the lines are correctly
connected to the receiver.

2.

Verify that correct prefixes and phone
numbers for the receiver have been
programmed into the D9412/D9112.

If completing the steps above does not correct
the problem, contact your telephone company
repair service.

The panel is
unable to call out
when all 248
points are faulted.

The total current draw
is too much for the
panel.

Put command centers on a separate power
supply to get maximum current draw from
points in alarm.

The line rings but
the receiver does
not pick up.

RING indicator on
line card lights.
Can hear ring with
test set at receiver
location.

Line card in receiver
may be faulty.

Review receiver manuals for trouble shooting
procedures.

The D9412/D9112
reaches a busy
signal for all ten
attempts to reach
the receiver.

Calls are not reaching
the receiver.

1.

Verify that correct prefixes and phone
numbers for the receiver have been
programmed into the D9412/D9112.

2.

Verify that the phone lines are not shorted
between the phone company's equipment
and the receiver by placing a call to the
number for the receiver. If you hear the
line ring, but the ring detector doesn't light,
or if you hear a busy signal and the green
on line (OL) indicator is not lit, call the
phone company for service.

The receiver's call
load is too great.

Additional line cards and phone lines may be
needed for the receiver.

The receiver
answers the call
and provides an
acknowledgment
tone, but the
communicator
does not transmit
reports.

The receiver is not
producing the correct
acknowledgment tone.

Verify that the receiver is producing a 1400
Hz, 2300 Hz, or Modem II acknowledgment
tone.

www.PDF-Zoo.com

firealarmresources.com

Содержание D9000 Series

Страница 1: ...icator 12 D7212Control Communicator 13 QuickReferenceTerminalDescription 14 Introduction This reference contains the very basic information a trained installer needs to install and troubleshoot a D900...

Страница 2: ...oint tested for 60 seconds After 60 seconds the display returns to the points to test message Extra Points display default text If you incorrectly set the switches on a POPIT to a point number that is...

Страница 3: ...NTESTED N EXT SERVICE WALK 246 PTS TO TEST 245 PTS TO TEST 244 PTS TO TEST POINT TEXT POINT TEXT POINT TEXT 1 PTS TO TEST 0 PTS TO TEST IDLE TEXT POINT TEXT Test a device Text displays 60 seconds Test...

Страница 4: ...d at the last address on the ZONEX bus Install a D8125 POPEX and D9127 POPITs for points 121 127 on ZONEX 1 and for points 241 247 on ZONEX 2 Sensor loop switch 1 to 8 is turned off on OctoPOPIT If th...

Страница 5: ...res input from all points in the same area programmed for sensor reset during sensor reset Two points are programmed with the same address Points programmed with the same address do not function corre...

Страница 6: ...d 24 share a common circuit breaker Check wiring and devices connected to these terminals for shorts or grounds If only one POPEX module is connected to the panel POPEX module may be incorrectly conne...

Страница 7: ...programmer connector J7 3 Check each conductor in the data power cord for continuity AC induction through the on board point sensor loops the DATA BUS or the ZONEX BUS 1 Verify a proper earth ground a...

Страница 8: ...contact your telephone company repair service Communications Failure Follow the Phone Line Trouble procedure to verify that there is no problem with the phone lines at the installation If the phone li...

Страница 9: ...s Can hear ring with test set at receiver location Line card in receiver may be faulty Review receiver manuals for trouble shooting procedures The D9412 D9112 reaches a busy signal for all ten attempt...

Страница 10: ...r t 0 0 1 3V DC PER IPH ERAL DE VICE W IR ING Z ONE X O UT 1 ZO NEX IN 1 Z ONE X O UT 2 ZO NEX IN 2 ZON EX P OWE R Z ONE X CO MM ON O p eratio n Mo nito r Puls es W he n No rma l F licke rs W h e n Ri...

Страница 11: ...UT 1 ZO NEX IN 1 ZO NE X O UT 2 ZO NEX IN 2 ZO NEX POW ER Z ON EX CO MMO N O p e ra tion M o n itor P uls es W he n N o rm al Fli cke rs W h en R ing ing PROG CONN RED YELLOW G RE EN B LA CK 1 7 0 58...

Страница 12: ...ZO NEX IN 2 ZO NEX PO WE R Z O NEX CO MMO N O p era tio n M o nit or P uls es W he n No rm al Fli cke rs W h e n R in gi ng PROG CONN RE D YELLO W GRE EN BLACK 1 7 058 23 0 02 3 2 PO W ER DATA BU S A...

Страница 13: ...ON EX IN 2 Z ON EX PO WE R ZO NEX CO MMO N Op erati on Mo nit or Pu lse s W h en No rm al F lick er s W h en Rin gi ng PROG CONN RE D Y EL LO W GREEN BLA CK 17 05 82 3 0 02 3 2 PO W ER DATA BU S A CO...

Страница 14: ...or alarm verification Shares circuit breaker with terminals 6 and 7 D136 Plug in Relay required Install a D136 in socket K1 for output at terminal 8 9 COMMON Terminal 9 is common for Auxiliary Power...

Отзывы: