D9000/D7000 Series Installation and Troubleshooting Quick Reference

Page  6

33317D  4/97

Problems with Points 

(Continued)

Extra Points

If the panel is not in the service walk test mode when an extra point trips, the panel
responds to it as a local TROUBLE event at the control center or central station (see
Routing in the Program Entry Guide). It displays the custom text for the point number set
in the point’s dipswitch or on-board point location.

When an extra point is tripped during the service walk test, it reports as an EXTRA point
in the panel’s event log and at the local printer (if installed). Once an extra point is
identified you can check the programming to see if it has a 

Point Index programmed.

You can then determine if the point index is appropriate for the application and that the
area assignment is correct.

Symptom

Diagnosis

Remedy

All off-board
points are
MISSING.

Short on Aux Power,
terminal 3 or ZONEX
power, terminal 24.

Terminals 3 and 24 share a common circuit
breaker. Check wiring and devices connected
to these terminals for shorts or grounds.

If only one POPEX
module is connected
to the panel, POPEX
module may be
incorrectly connected
to the panel or Data
Expansion Loop may
be disconnected from
POPEX module.

Check POPEX module for correct connections
to the D9412/D9112 and the Data Expansion
Loop.

If you find missing points, the service walk test
may help you diagnose the problem (see
Extra Points below).

Keyswitch points
(

P## Type is

programmed as 4,
5, 6, 7, or 9) report
as missing. If area
is armed, the point
reports a
MISSING ALARM.
If the area is
disarmed, the
point reports a
MISSING
TROUBLE.

Point is disconnected
from the SDI data bus.

The POPIT cover may
have been removed
and not replaced or
the cover is not seated
properly.

The point will restore when the SDI bus is
reconnected or when the POPIT cover is
seated firmly on the POPIT.

Connected points
show as extra
points when the
point bus is
shorted beyond
the programmed
debounce time.

The points have no
point index
programmed.

This will be corrected when the short is
returned to normal.

www.PDF-Zoo.com

firealarmresources.com

Содержание D9000 Series

Страница 1: ...icator 12 D7212Control Communicator 13 QuickReferenceTerminalDescription 14 Introduction This reference contains the very basic information a trained installer needs to install and troubleshoot a D900...

Страница 2: ...oint tested for 60 seconds After 60 seconds the display returns to the points to test message Extra Points display default text If you incorrectly set the switches on a POPIT to a point number that is...

Страница 3: ...NTESTED N EXT SERVICE WALK 246 PTS TO TEST 245 PTS TO TEST 244 PTS TO TEST POINT TEXT POINT TEXT POINT TEXT 1 PTS TO TEST 0 PTS TO TEST IDLE TEXT POINT TEXT Test a device Text displays 60 seconds Test...

Страница 4: ...d at the last address on the ZONEX bus Install a D8125 POPEX and D9127 POPITs for points 121 127 on ZONEX 1 and for points 241 247 on ZONEX 2 Sensor loop switch 1 to 8 is turned off on OctoPOPIT If th...

Страница 5: ...res input from all points in the same area programmed for sensor reset during sensor reset Two points are programmed with the same address Points programmed with the same address do not function corre...

Страница 6: ...d 24 share a common circuit breaker Check wiring and devices connected to these terminals for shorts or grounds If only one POPEX module is connected to the panel POPEX module may be incorrectly conne...

Страница 7: ...programmer connector J7 3 Check each conductor in the data power cord for continuity AC induction through the on board point sensor loops the DATA BUS or the ZONEX BUS 1 Verify a proper earth ground a...

Страница 8: ...contact your telephone company repair service Communications Failure Follow the Phone Line Trouble procedure to verify that there is no problem with the phone lines at the installation If the phone li...

Страница 9: ...s Can hear ring with test set at receiver location Line card in receiver may be faulty Review receiver manuals for trouble shooting procedures The D9412 D9112 reaches a busy signal for all ten attempt...

Страница 10: ...r t 0 0 1 3V DC PER IPH ERAL DE VICE W IR ING Z ONE X O UT 1 ZO NEX IN 1 Z ONE X O UT 2 ZO NEX IN 2 ZON EX P OWE R Z ONE X CO MM ON O p eratio n Mo nito r Puls es W he n No rma l F licke rs W h e n Ri...

Страница 11: ...UT 1 ZO NEX IN 1 ZO NE X O UT 2 ZO NEX IN 2 ZO NEX POW ER Z ON EX CO MMO N O p e ra tion M o n itor P uls es W he n N o rm al Fli cke rs W h en R ing ing PROG CONN RED YELLOW G RE EN B LA CK 1 7 0 58...

Страница 12: ...ZO NEX IN 2 ZO NEX PO WE R Z O NEX CO MMO N O p era tio n M o nit or P uls es W he n No rm al Fli cke rs W h e n R in gi ng PROG CONN RE D YELLO W GRE EN BLACK 1 7 058 23 0 02 3 2 PO W ER DATA BU S A...

Страница 13: ...ON EX IN 2 Z ON EX PO WE R ZO NEX CO MMO N Op erati on Mo nit or Pu lse s W h en No rm al F lick er s W h en Rin gi ng PROG CONN RE D Y EL LO W GREEN BLA CK 17 05 82 3 0 02 3 2 PO W ER DATA BU S A CO...

Страница 14: ...or alarm verification Shares circuit breaker with terminals 6 and 7 D136 Plug in Relay required Install a D136 in socket K1 for output at terminal 8 9 COMMON Terminal 9 is common for Auxiliary Power...

Отзывы: